3.5 External equipment

Version 7.6 by Admin on 2025/02/11 17:25

Settings

External equipment

The BMS Main 3X device supports joint operation with vehicle controllers.

BKM controller

Communication parameters for the BKM controller are configured in the section "External equipment - BKM controller":

1739294349994-539.png

In this section:

  • Enable – a flag to enable communication with the BKM controller;
  • CAN port – port which is used to communicate with the charger:
    • CAN1 (ext);
    • CAN2 (int);
  • Receive timeout – a timeout for receiving packets from the controller (if no data is received from the BKM controller during this time, then the communication loss flag is set), ms;
  • Maximum voltage – a maximum charge voltage, V;
  • Maximum current – a maximum charge current, A;
  • SOC of the partially charger battery – a charge level of the partially charged battery, %;
  • SOC of the fully charger battery – a charge level of the fully charged battery, %.

Basic J1939 vehicle

The basic vehicle protocol J1939 is developed by Movicom Electric, and its description is available upon request. Using this protocol, information about the parameters of the modular battery can be obtained. The protocol also implements the management of battery operation modes.

Communication parameters via the Basic J1939 protocol are configured in the “External equipment – Basic J1939 vehicle” section:

1739294413209-387.png

In this section:

  • Enable – a flag to enable communication using the protocol;
  • CAN port – port which is used to communicate with the vehicle:
    • CAN1 (ext);
    • CAN2 (int);
  • BMS message ID – an identifier of the first message of the device in the J1939 network;
  • Vehicle Message ID – an identifier of the first message of the vehicle in the J1939 network.

Evocargo vehicle

Communication parameters for the Evocargo vehicle are configured in the section "External equipment – Evocargo vehicle":

1739294432727-315.png

In this section:

  • Enable – a flag to enable communication with the Evocargo vehicle;
  • CAN port – port which is used to communicate with the vehicle:
    • CAN1 (ext);
    • CAN2 (int);
  • Minimum voltage – minimum battery voltage, V;
  • Maximum voltage – maximum battery voltage, V.

BMS IMD

To change communication parameters with an insulation monitoring device BMS IMD, select the "External equipment → BMD IMD " section:

1739294477662-343.png

In this section:

  • Enable – a flag to enable communication with the IMD;
  • CAN port – port which is used to communicate with the IMD:
    • CAN1 (ext);
    • CAN2 (int);
  • Node ID – a CANopen address of the BMS IMD device;
  • Configure IMD – a flag to override the IMD warning and alarm settings;
  • Allow work if battery modules are joined – a flag to allow the BMS IMD to work only if battery modules are joined;
  • Alarm threshold – a threshold resistance value to set insulation alarm, Ohm;
  • Warning threshold – a threshold resistance value to set insulation warning, Ohm.

Unibat vehicle

To change communication parameters with vehicle with Unibat battery installed, select the "External equipment → Unibat vehicle" section:

1739294567774-840.png

In this section:

  • Enable – a flag to enable communication with the vehicle;
  • CAN port – port which is used to communicate with the vehicle;
  • Use CRC – a flag to enable checking the checksum of the control message;
  • Use DTC – a flag to enable transmit of error codes on battery failures;
  • Use additional current sensors to determine error – a flag to use measuring of second and third current sensor to determine errors in battery work;
  • Number of modules – total number of battery modules;
  • Receive timeout – a timeout for receiving packets from the vehicle (if there is no messages during that time, an error generates), millisecond;
  • HVIL delay – a delay before generating a signal of high-voltage interrupt loop breakage, millisecond;
  • Nominal voltage, V;
  • Maximum charge voltage, V;
  • Lower voltage limit, V;
  • Upper voltage limit, V;
  • Lower temperature limit, °C;
  • Upper temperature limit, °C;
  • Lower SOC limit, %;
  • Upper SOC limit, %;
  • Lower cell voltage limit, V;
  • Upper cell voltage limit, V;
  • Nominal capacity – nominal battery capacity, Wh;
  • Current threshold for contactor opening – a current value for safe contactor opening, A;
  • Waiting time until the current drops below the threshold – a waiting time for current to drop below estimated value before safe contactor opening, millisecond;
  • Control ventilation fans – a flag to send command messages to control battery ventilation fans;
  • Version: Manufacturer;
  • Version: Hardware ID;
  • Version: Software ID;
  • Version: Confoguration;
  • Version: Serial Number;
  • Version: Production date;
  • Errors 1, 2 for emergency shutdown – a bitfield with errors to emergency shutdown the vehicle.