Wiki source code of BMS Main 2.1

Version 13.1 by Admin on 2025/05/29 14:02

Hide last authors
Admin 7.1 1 (% class="box infomessage" %)
2 (((
Admin 5.1 3 BMS Main 2.1 firmware update procedure is described [[here>>doc:Battery management systems.BMS Main 2\.1.4\. Firmware update.WebHome]].
Admin 7.1 4 )))
Admin 4.1 5
Admin 13.1 6 = v1.70.2 =
7
8 [[BMS_Main_2.1_v1.70.2.srec>>FileManager.BMS_Main_2\.1_v1\.70\.2\.srec]]
9
10 == Improvements ==
11
12 * new parameter setting a delay before measuring battery current during precharge (see the "Cells - Discharging control" section)
13 * new counter of retry attempts showing the communication problems with BMS Logic devices (see the "Logic/Cell - Overview" section)
14 * new flag to keep the precharging contactor closed until the precharging process is finished (in this case the "Precharge error" will not occur; see the "Cells - Discharging control" section)
15 * new flags that force only positive and negative currents to be used to determine open circuit voltages to control the "Ready to charge" and "Ready to discharge" signals respectively
16
17 == Fixes ==
18
19 * resolving the issue of not being able to send log files to a remove FTP server due to a change in the file name format (v1.70.0)
20 * increased number of retries when sending commands to BMS Logic devices, which reduces the number of false offline event detections
21
Admin 12.1 22 = v1.70.1 =
23
24 [[BMS_Main_2.1_v1.70.1.srec>>FileManager.BMS_Main_2\.1_v1\.70\.1\.srec]]
25
26 == Improvements ==
27
28 * new assignments "Low SOC" and "High charging current" for relays
29
30 == Fixes ==
31
32 * resolving the issue of ill-considered reduction of the battery SOC level when the cell voltage is close to the level corresponding to SOC=0% (due to the flow of a large discharge current leading to the high voltage drop on the cells)
33
Admin 10.1 34 = v1.70.0 =
35
36 [[BMS_Main_2.1_v1.70.0.srec>>FileManager.BMS_Main_2\.1_v1\.70\.0\.srec]]
37
38 == Features ==
39
Admin 11.1 40 * new parameters allowing to set different delays for battery discharge mode to detect the overcurrent error (see the "Protections - Overcurrent protection" section)
Admin 10.1 41 * new flag that sets whether the BMS should wait for confirmation messages from the Combilift truck to start charging or not (see the "External equipment - Combilift truck" section)
42
43 == Fixes ==
44
45 * optimization of the logging process, minimizing the time to open the next log file if the current one is full
46
Admin 9.1 47 = v1.69.1 =
48
49 [[BMS_Main_2.1_v1.69.1.srec>>FileManager.BMS_Main_2\.1_v1\.69\.1\.srec]]
50
51 == Fixes ==
52
53 * check the HYG and Combilift confirmation flags only if the truck offline error is not set
54 * small internal fixes
55
Admin 8.1 56 = v1.69.0 =
57
58 [[BMS_Main_2.1_v1.69.0.srec>>FileManager.BMS_Main_2\.1_v1\.69\.0\.srec]]
59
60 == Features ==
61
62 * new parameter for setting the condition for starting balancing: automatically (regardless of the command) or on the balancing request (see the "Cells - Cell balancing" section)
63 * new option to start balancing if the cell voltage exceeds the "Voltage for forced balancing" value (see the "Cells - Cell balancing" section)
64 * new assignment "Balancing request" for the discrete inputs (see the "Signals - Input signals" section)
65 * new Max-Min algorithm for calculating the final battery SOC in the "Cells - SOC estimation" section
66 * new algorithms "Automatic" and "On command" for the main contactor (see the "Cells - Main contactor" section)
67 * new assignment "Close Main contactor" for the discrete inputs to close the main contactor by a command
68 * new assignment "Close External 1" for the discrete inputs (see the "Signals - Input signals" section)
69 * new assignment "External 1" for the discrete outputs and relays (see the "Signals - Output signals" section). The "External 1" output is directly controlled by the "Close External 1" command.
70 * new "Precharge error" flag that is set when precharging cannot be completed
71 * new flags in the "Protections - Undervoltage protection" and "Protections - Overvoltage protection" sections which allow using the calculated open circuit cell voltage instead of the actual voltage to detect the "Undervoltage" and "Overvoltage" errors, respectively
72 * ability to check the "Ready to charge" and "Ready to discharge" signals to control the charging and discharging contactors (see the "Cells - Charging control" and "Cells - Discharging control" sections)
73
74 == Improvements ==
75
76 * ignoring the "Need acknowledge" flag when generating Modbus input register 0x2128 ("Error")
77 * explicit flags to enable the use of the charging current limit for fast and/or normal charging when using the CCS Fast charge controller (see the "External equipment - CCS Fast charge controller" section)
78 * improving resistance calculation
79
80 == Fixes ==
81
82 * resolving the issue where the "Need acknowledge" signal is not set if any of the device errors are not acknowledged in the error journal
83 * using the calculated open circuit voltage to set/clear the "Ready to charge" and "Ready to discharge" signals
84
Admin 6.1 85 = v1.68.0 =
86
87 [[BMS_Main_2.1_v1.68.0.srec>>FileManager.BMS_Main_2\.1_v1\.68\.0\.srec]]
88
89 == Features ==
90
91 - support for charge/discharge cycling using XD Discharger (see the sections "External equipment - Battery cycling" and "External equipment - XD Discharger (cycling)")
92
Admin 3.1 93 = v1.67.0 =
94
95 [[BMS_Main_2.1_v1.67.0.srec>>FileManager.BMS_Main_2\.1_v1\.67\.0\.srec]]
96
97 == Features ==
98
99 * new additional heater controller (see the "Protections - Heater (AUX) control" section), which generates the "Heater (AUX)" signal, which can be assigned to a discrete output or relay
100
101 == Improvements ==
102
103 * new balancing strategy that attempts to keep the temperature of BMS Logic devices below a set value by discharging cells with higher voltages first than others (see the "Cells - Cell balancing" section)
104
105 = v1.66.1 =
106
107 [[BMS_Main_2.1_v1.66.1.srec>>FileManager.BMS_Main_2\.1_v1\.66\.1\.srec]]
108
109 == Improvements ==
110
111 * closing all TCP connections over Ethernet if the interface link is down
112
Admin 2.1 113 = v1.66.0 =
Admin 1.2 114
115 [[BMS_Main_2.1_v1.66.0.srec>>FileManager.BMS_Main_2\.1_v1\.66\.0\.srec]]
116
Admin 2.1 117 == Features ==
118
119 * support for the insulation monitoring device BMS IMD (see the section "External equipment - BMS IMD device")
120
121 == Improvements ==
122
123 * new parameters for switching off the Discharging (AUX) relay when the cell voltage is too low (see the "Cells - Discharging (AUX) control" section)