Changes for page 3.3 Control

Last modified by Admin on 2026/04/30 15:58

From version 50.2
edited by Admin
on 2026/01/30 15:38
Change comment: There is no comment for this version
To version 53.1
edited by Admin
on 2026/04/27 12:53
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -334,7 +334,7 @@
334 334  * Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
335 335  * Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;
336 336  * Discharge current limit to set the 'Ready to discharge' – a tolerant discharging current limit value, A; if the limit is //below //this level, the “Ready to discharge” signal is set;
337 -* Clear the 'Ready to charge' signal if the 'Low SOC' signal is set – a
337 +* Clear the 'Ready to discharge' signal if the 'Low SOC' signal is set;
338 338  * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
339 339  
340 340  === Precharge ===
... ... @@ -623,13 +623,13 @@
623 623  
624 624  To change the parameters of the heater control algorithm, select the "Control → Heater" section:
625 625  
626 -
627 -[[image:1740404973346-344.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
626 +[[image:1777293968000-235.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="141" width="800"]]
628 628  In this section:
629 629  
630 630  * Enable – a flag to enable heater control;
631 631  * Minimum cell temperature, °C;
632 632  * Tolerant cell temperature, °C;
632 +* Start the heater only if "Charger connected" signal is set;
633 633  * Delay before starting the heater, millisecond;
634 634  * Delay before stopping the heater, millisecond;
635 635  * Errors 1, 2 to turn off the heater – bitfields to choose the errors which will turn off the heater.
1777293968000-235.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +25.5 KB
Content