Changes for page 3.3 Control

Last modified by Admin on 2026/01/30 15:38

From version 50.2
edited by Admin
on 2026/01/30 15:38
Change comment: There is no comment for this version
To version 48.1
edited by Admin
on 2025/11/10 11:41
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -323,7 +323,8 @@
323 323  
324 324  To change the parameters of discharging process status, select the "Control → Discharging status" section:
325 325  
326 -[[image:1762774840204-111.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="146" width="800"]]In this section:
326 +[[image:1762774840204-111.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="146" width="800"]]
327 +In this section:
327 327  
328 328  * Current to set the "Discharging current present" – a current level to generate the "Discharging current present" signal, А;
329 329  * Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
... ... @@ -334,7 +334,6 @@
334 334  * Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
335 335  * Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;
336 336  * Discharge current limit to set the 'Ready to discharge' – a tolerant discharging current limit value, A; if the limit is //below //this level, the “Ready to discharge” signal is set;
337 -* Clear the 'Ready to charge' signal if the 'Low SOC' signal is set – a
338 338  * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
339 339  
340 340  === Precharge ===
... ... @@ -343,11 +343,9 @@
343 343  
344 344  BMS Main 3 device detects errors while pre-charging the load capacity by monitoring the current and voltage difference before and after contactors. Also BMS can measure the power dissipated on precharge resistor and generate an error if it greater than configured limit.
345 345  
346 -To change the parameters of precharge contactor, select the "Control → Precharge" section:
347 -
348 348  [[image:1754931813173-804.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="172" width="800"]]
349 349  
350 -In this section:
348 +To change the parameters of precharge contactor, select the "Control → Precharge" section:
351 351  
352 352  * Precharge current threshold to finish precharging – a minimum current value at which precharging process assumed to be finished, A;
353 353  * Keep the precharging relay closed until precharge is finished – a flag to ignore the Precharge time and wait precharging to finish before open precharge relay;
1769787007221-936.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -38.3 KB
Content