Changes for page 3.3 Control

Last modified by Admin on 2025/11/10 11:41

From version 47.2
edited by Admin
on 2025/11/10 11:40
Change comment: There is no comment for this version
To version 49.1
edited by Admin
on 2025/11/10 11:41
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -323,8 +323,7 @@
323 323  
324 324  To change the parameters of discharging process status, select the "Control → Discharging status" section:
325 325  
326 -[[image:1762774840204-111.png]]
327 -In this section:
326 +[[image:1762774840204-111.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="146" width="800"]]In this section:
328 328  
329 329  * Current to set the "Discharging current present" – a current level to generate the "Discharging current present" signal, А;
330 330  * Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
... ... @@ -332,6 +332,9 @@
332 332  * Use actual voltage to generate the "Ready to discharge" signal if the current is positive – a flag to disable voltage correction for "Ready to discharge" signal only at charging current;
333 333  * Voltage to clear the “Ready to discharge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
334 334  * Voltage to reset the “Ready to discharge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
334 +* Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
335 +* Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;
336 +* Discharge current limit to set the 'Ready to discharge' – a tolerant discharging current limit value, A; if the limit is //below //this level, the “Ready to discharge” signal is set;
335 335  * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
336 336  
337 337  === Precharge ===
... ... @@ -340,9 +340,11 @@
340 340  
341 341  BMS Main 3 device detects errors while pre-charging the load capacity by monitoring the current and voltage difference before and after contactors. Also BMS can measure the power dissipated on precharge resistor and generate an error if it greater than configured limit.
342 342  
345 +To change the parameters of precharge contactor, select the "Control → Precharge" section:
346 +
343 343  [[image:1754931813173-804.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="172" width="800"]]
344 344  
345 -To change the parameters of precharge contactor, select the "Control → Precharge" section:
349 +In this section:
346 346  
347 347  * Precharge current threshold to finish precharging – a minimum current value at which precharging process assumed to be finished, A;
348 348  * Keep the precharging relay closed until precharge is finished – a flag to ignore the Precharge time and wait precharging to finish before open precharge relay;