Changes for page 3.3 Control

Last modified by Admin on 2025/11/10 11:41

From version 47.2
edited by Admin
on 2025/11/10 11:40
Change comment: There is no comment for this version
To version 48.1
edited by Admin
on 2025/11/10 11:41
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -323,7 +323,7 @@
323 323  
324 324  To change the parameters of discharging process status, select the "Control → Discharging status" section:
325 325  
326 -[[image:1762774840204-111.png]]
326 +[[image:1762774840204-111.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="146" width="800"]]
327 327  In this section:
328 328  
329 329  * Current to set the "Discharging current present" – a current level to generate the "Discharging current present" signal, А;
... ... @@ -332,6 +332,9 @@
332 332  * Use actual voltage to generate the "Ready to discharge" signal if the current is positive – a flag to disable voltage correction for "Ready to discharge" signal only at charging current;
333 333  * Voltage to clear the “Ready to discharge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
334 334  * Voltage to reset the “Ready to discharge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
335 +* Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
336 +* Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;
337 +* Discharge current limit to set the 'Ready to discharge' – a tolerant discharging current limit value, A; if the limit is //below //this level, the “Ready to discharge” signal is set;
335 335  * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
336 336  
337 337  === Precharge ===