Changes for page 3.3 Control

Last modified by Admin on 2025/04/09 12:15

From version 4.1
edited by Admin
on 2025/01/28 15:19
Change comment: There is no comment for this version
To version 6.2
edited by Admin
on 2025/02/24 10:56
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -8,7 +8,7 @@
8 8  
9 9  To change the common BMS settings, select the "Control → Common settings" section:
10 10  
11 -[[image:1733746733473-873.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="124" width="800"]]
11 +[[image:1740394523706-519.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="127" width="800"]]
12 12  
13 13  In this section:
14 14  
... ... @@ -16,13 +16,18 @@
16 16  * Cell resistance – nominal (maximum) internal resistance of the cell, Ohm;
17 17  * Relax time (after charging) – a relaxation time after charging, second;
18 18  * Relax time (atfer discharging) – the relaxation time after discharging, second;
19 -* Number of cycles – a number of charge-discharge cycles;
20 20  * Reset parameters– a command to reset cells state of charge, capacity, and resistance.
21 21  
22 -The values “Capacity”, “Resistance”, “Cycles” are used to calculate the SOC of cells and the battery.
21 +The values “Capacity” and “Resistance” are used to calculate the SOC of cells and the battery.
23 23  
24 24  The values of “Relax time” are used to determine the state of the battery. If the battery is in a state of relaxation, the system recalculates the voltage on the cells to the state of charge of the battery.
25 25  
25 +The “Reset parameters” will reset:
26 +
27 +* state of charge (new cell SOC values will be calculated based on cell voltage and “Uocv (open-circuit voltage) table”: in the “Control → SOC estimation” section);
28 +* cell resistance to “Cell resistance” value;
29 +* battery capacity to “Cell capacity” value.
30 +
26 26  The “Reset parameters” command is used for starting-up and adjustment of the battery.
27 27  
28 28  === SOC estimation ===
... ... @@ -201,7 +201,6 @@
201 201  
202 202  Discharging current limit = Maximum discharging current × Kds × Kdc × Kdv
203 203  
204 -
205 205  === Charge ===
206 206  
207 207  There are two contactors that serve charging the battery: a charging contactor and an allow charging contactor. With the help of the allow charging contactor, the BMS commands the charger to start or stop charging.
... ... @@ -357,7 +357,6 @@
357 357  
358 358  [[image:1733746901779-991.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="95" width="800"]]In this section:
359 359  
360 -
361 361  * Enable – a flag to enable the charge/discharge controller.
362 362  
363 363  === Discharge (AUX) ===
1740394523706-519.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +21.3 KB
Content