... ... @@ -88,7 +88,7 @@
88 88  
89 89  === SOC correction ===
90 90  
91 -The BMS Mini device can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see [[SOC estimation>>doc:||anchor="HSOCestimation"]]).
91 +The BMS Mini device can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see section **SOC estimation**).
92 92  
93 93  To configure parameters for periodically correcting the battery state of charge, select the "Control → SOC correction" section:
94 94  
... ... @@ -133,7 +133,7 @@
133 133  * Minimum SOC – minimum cell SOC value for resistance calculation;
134 134  * Maximum SOC – maximum cell SOC value for resistance calculation.
135 135  
136 -The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
136 +The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see Common settings). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
137 137  
138 138  === Charge map ===
139 139  
... ... @@ -273,10 +273,7 @@
273 273  * Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
274 274  * Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0.
275 275  
276 -(% class="box infomessage" %)
277 -(((
278 278  Note – The allow charging contactor closes under two independent conditions: 1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and 2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
279 -)))
280 280  
281 281  === Discharge ===
282 282