297 297  
298 298  To change the parameters of charging process status, select the "Control → Charging status" section:
299 299  
300 -[[image:1754931617275-503.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="135" width="800"]]
300 +[[image:1740399071280-626.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="123" width="800"]]
301 301  In this section:
302 302  
303 303  * Current to set the "Charging current present" – a current level to generate the "Charging current present" signal, A;
304 304  * Current to clear the "Charging current present" – a current level to clear the "Charging current present" signal, A;
305 -* Use actual voltage to generate the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal;
306 -* Use actual voltage to generate the "Ready to charge" signal if the current is negative – a flag to disable voltage correction for "Ready to charge" signal only at discharging current;
307 -* Voltage to clear the “Ready to charge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
308 -* Voltage to reset the “Ready to charge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
305 +* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
306 +* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
309 309  * Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0;
310 310  * Errors 1, 2 to clear the "Ready to charge" – bitfields to choose the errors which will clear the "Ready to charge" signal.
311 311  
... ... @@ -320,13 +320,13 @@
320 320  
321 321  To change the parameters of discharging process status, select the "Control → Discharging status" section:
322 322  
323 -[[image:1754931699901-802.png]]
321 +[[image:1740399096018-240.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="110" width="800"]]
324 324  In this section:
325 325  
326 326  * Current to set the "Discharging current present" – a current level to generate the "Discharging current present" signal, А;
327 327  * Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
328 -* Voltage to clear the “Ready to discharge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
329 -* Voltage to reset the “Ready to discharge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
326 +* Voltage to clear the “Ready to discharge” – a threshold voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
327 +* Voltage to reset the “Ready to discharge” – a tolerant voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
330 330  * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.