208 208  * Enable – a flag to start calculation of the charge current limit;
209 209  * Maximum charge current – a maximum allowable value of the charge current (under normal conditions), A;
210 210  * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
211 -* Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current** Kcs** depending on SOC and battery temperature;
211 +* Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current** Kcs** depending on __maximum cell SOC__ and battery temperature;
212 212  * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
213 213  * Option 2: Limit charge current by the contactor temperature – a flag to enable correction of maximum allowable charging current **Kcc** depending on contactor temperature;
214 214  * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
215 -* Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current **Kcv** depending on maximum cell voltage;
215 +* Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current **Kcv** depending on __the maximum cell U,,ocv,, voltage__ (corrected due to current and cell resistance)
216 216  * Option 3: Cell voltage x Factor – the dependence of the correction factor on maximum cell voltage;
217 217  * Option 4: Limit charge current by the cell temperature - a flag to enable correction of maximum allowable charging current **Kct** depending on maximum cell temperature;
218 218  * Option 4: Cell temperature x Factor – the dependence of the correction factor on maximum cell temperature.
... ... @@ -236,11 +236,11 @@
236 236  * Enable – a flag to start calculation of the discharge current limit;
237 237  * Maximum discharge current – a maximum allowable value of the discharge current (under normal conditions), A;
238 238  * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
239 -* Option 1: Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current **Kds **depending on SOC and temperature;
239 +* Option 1: Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current **Kds **depending on __minimum cell SOC__ and temperature;
240 240  * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
241 241  * Option 2: Limit discharge current by the contactor temperature – a flag to enable correction of maximum allowable discharging current **Kdc** depending on contactor temperature;
242 242  * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
243 -* Option 3: Limit discharge current by the cell voltage - a flag to enable correction of maximum allowable discharging current **Kdv** depending on minimum cell voltage;
243 +* Option 3: Limit discharge current by the cell voltage - a flag to enable correction of maximum allowable discharging current **Kdv** depending on __the minimum cell U,,ocv,, voltage__ (corrected due to current and cell resistance)
244 244  * Option 3: Cell voltage x Factor – the dependence of the correction factor on minimum cell voltage;
245 245  * Option 4: Limit discharge current by the cell temperature - a flag to enable correction of maximum allowable discharging current **Kdt** depending on maximum cell temperature;
246 246  * Option 4: Cell voltage x Factor – the dependence of the correction factor on minimum cell temperature.
... ... @@ -302,8 +302,8 @@
302 302  
303 303  * Current to set the "Charging current present" – a current level to generate the "Charging current present" signal, A;
304 304  * Current to clear the "Charging current present" – a current level to clear the "Charging current present" signal, A;
305 -* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
306 -* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
305 +* Voltage to clear the “Ready to charge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
306 +* Voltage to reset the “Ready to charge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
307 307  * Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0;
308 308  * Errors 1, 2 to clear the "Ready to charge" – bitfields to choose the errors which will clear the "Ready to charge" signal.
309 309  
... ... @@ -323,8 +323,8 @@
323 323  
324 324  * Current to set the "Discharging current present" – a current level to generate the "Discharging current present" signal, А;
325 325  * Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
326 -* Voltage to clear the “Ready to discharge” – a threshold voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
327 -* Voltage to reset the “Ready to discharge” – a tolerant voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
326 +* Voltage to clear the “Ready to discharge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
327 +* Voltage to reset the “Ready to discharge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
328 328  * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
329 329  
330 330  === Precharge ===
... ... @@ -618,7 +618,7 @@
618 618  * Tolerant cell temperature, °C;
619 619  * Delay before starting the heater, millisecond;
620 620  * Delay before stopping the heater, millisecond;
621 -* Errors 1, 2 to turn off the heater – bitfields to choose the errors which will turn off the heater;
621 +* Errors 1, 2 to turn off the heater – bitfields to choose the errors which will turn off the heater.
622 622  
623 623  As a result of operating the heating algorithm, the “Heater” signal is generated.
624 624  
... ... @@ -639,8 +639,8 @@
639 639  
640 640  To change the parameters of the cooler control algorithm, select the "Control → Cooler" section:
641 641  
642 -[[image:1733746808497-424.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="113" width="800"]]
643 643  
643 +[[image:1740405145695-704.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="149" width="800"]]
644 644  In this section:
645 645  
646 646  * Enable – a flag to enable cooler control;
... ... @@ -648,7 +648,7 @@
648 648  * Tolerant cell temperature, °C;
649 649  * Delay before starting the cooler, millisecond;
650 650  * Delay before stopping the cooler, millisecond;
651 -* Switch off the cooler contactor on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
651 +* Errors 1, 2 to turn off the heater – bitfields to choose the errors which will turn off the cooler.
652 652  
653 653  As a result of operating the cooling algorithm, the "Cooler" signal is generated.