Changes for page 3.3 Control
Last modified by Admin on 2025/04/09 12:15
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -527,14 +527,13 @@ 527 527 * Switch off the discharging (AUX) contactor if the SOC is too low; 528 528 * Minimum SOC – a minimum SOC value, when reached, the auxiliary (AUX) discharging contactor opens, %; 529 529 * Tolerant SOC – a permissive SOC value, upon reaching which the auxiliary (AUX) discharging contactor re-closes, %; 530 -* Switch off the discharging (AUX) contactor if the cell voltage is out of the range; 531 -* Minimum cell voltage, V; 532 -* Maximum cell voltage, V; 533 533 * Switch off the discharging (AUX) contactor if the battery voltage is out of the range; 534 -* Minimum battery voltage, V; 535 -* Maximum battery voltage, V; 536 -* Errors1,2to open the auxiliary discharging contactor–bitfieldsto choosetheerrorswhichwillopeneauxiliarydischargingcontactor.531 +* Minimum voltage – minimum battery voltage, V; 532 +* Maximum voltage – maximum battery voltage, V; 533 +* Switch off the discharging (AUX) contactor on errors – the auxiliary (AUX) discharging contactor opens if the following errors occur: Undervoltage, Overcurrent, High temperature (DCH), Short circuit, Critical error. 537 537 535 +=== === 536 + 538 538 === Cell balancing === 539 539 540 540 Balancing makes the voltage of all cells be equal to the minimum cell voltage.