409 409  * Allow charging only when the "Ready to charge" signal is set – charging contactor will open if "Ready to charge" signal is cleared;
410 410  * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
411 411  * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
412 -* Control the precharging contactor – a flag that allows control of the precharging contactor;
412 +* Control the precharging contactor – a flag that allows control of the precharging contactor (see [[Precharge>>url:http://#HPrecharge]]);
413 413  * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
414 414  * Errors 1, 2 to open the charging contactor – bitfields to choose the errors which will open the charging contactor;
415 415  * Custom delay: <error> – specific error delay, millisecond;
... ... @@ -421,50 +421,36 @@
421 421  
422 422  The device supports three algorithms to control battery discharging:
423 423  
424 -* load is always connected;
425 -* load is connected when there is no signal “Charger connected”;
426 -* load is connected when there is signal “Discharge request”.
424 +* Always on – load is always connected;
425 +* On charger disconnected – load is connected when there is no signal “Charger connected”;
426 +* On discharge request – load is connected when there is signal “Discharge request”.
427 427  
428 -When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors appears:
428 +When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
429 429  
430 -* Undervoltage;
431 -* Overvoltage (optional);
432 -* Overcurrent;
433 -* High temperature (DCH);
434 -* Low temperature (DCH) (optional);
435 -* HYG offline (optional);
436 -* Combilift offline (optional);
437 -* Spirit offline (optional);
438 -* Spirit charger error (optional);
439 -* Short circuit (optional);
440 -* High contactor temperature (optional);
441 -* DCH contactor cycles error;
442 -* Critical error
430 +* Service reset
431 +* Power down request
432 +* Inhibit discharging
443 443  
444 444  the discharging contactor opens.
445 445  
446 -If the algorithm "**On Charger disconnected**" is selected, the control is performed as follows:
436 +If the algorithm "**On charger disconnected**" is selected, the control is performed as follows:
447 447  
448 -* if there is no signal “Charger connected”, the charging contactor is opened and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
449 -* If the signal “Charger connected” appears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
438 +* if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
439 +* If the signal “Charger connected” appears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
450 450  
451 -When the "**On Discharge request**" algorithm selected, the control is performed as follows:
441 +When the "**On discharge request**" algorithm selected, the control is performed as follows:
452 452  
453 -* if there is signal “Discharge request”, the charging contactor is opened and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
454 -* If the signal “Discharge request” disappears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
443 +* if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
444 +* If the signal “Discharge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
455 455  
456 456  (% class="box infomessage" %)
457 457  (((
458 -Note: in case of errors in the system operation, the opening of the **discharging **contactor is performed either immediately or with a delay T,,off,, (depends on the settings described below).
448 +**Note: **when errors occur in the system, the **Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
459 459  )))
460 460  
461 -The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted.
462 -
463 -When the power down request occurs, the discharging contactor opens after delay T,,off,,. Reclosing the discharging contactor is performed if the power down request is removed.
464 -
465 465  To change the parameters of the battery discharge control algorithm, select the "Control → Discharge" section:
466 466  
467 -[[image:1733746885414-479.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="319" width="800"]]
453 +[[image:1740399783613-216.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="311" width="800"]]
468 468  
469 469  In this section:
470 470  
... ... @@ -473,28 +473,51 @@
473 473  ** Always on – load is always connected;
474 474  ** On charger disconnected – load is connected when there is no signal “Charger connected”;
475 475  ** On discharge request – load is connected when there is signal “Discharge request”;
476 -* Current corresponding to discharging – a current level to generate the "Discharging current present" signal, А;
477 -* Current indicating no discharging – a current level to clear the "Discharging current present" signal, А;
462 +* Allow charging only when the "Ready to discharge" signal is set – discharging contactor will open if "Ready to discharge" signal is cleared;
478 478  * Delay before starting discharging – a time delay T,,on,, before closing the discharging contactor, millisecond;
479 479  * Delay before stopping discharging – a time delay T,,off,, before opening the discharging contactor, millisecond;
465 +* Control the precharging contactor – a flag that allows control of the precharging contactor while closing the discharge contactor (see [[Precharge>>path:#HPrecharge]]);
466 +* Errors 1, 2 to open the discharging contactor – bitfields to choose the errors which will open the discharging contactor;
480 480  * Use custom delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
481 481  * Custom delay: <error> – specific error delay, millisecond;
482 482  * Switch off the discharging contactor on errors without delay – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
483 -* Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond;
484 -* Voltage to clear the “Ready to discharge” – a threshold voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
485 -* Voltage to reset the “Ready to discharge” – a tolerant voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set.
486 486  
487 487  === Charge/Discharge ===
488 488  
489 489  The BMS Mini device can control the charging/discharging contactor that is used to both charge and discharge the battery.
490 490  
491 -The charging/discharging contactor combines algorithms of charging and discharging contactor. It behaves as a charging contactor when «Charge reques or «Charger connected» are set, otherwise – as a discharging contactor.
475 +Charge/Discharge contactor has three algorithms of operation:
492 492  
477 +* Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
478 +* Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
479 +* Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs.
480 +
481 +TBA
482 +
483 +(% class="box infomessage" %)
484 +(((
485 +**Note: **when errors occur in the system, the **Charge/Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
486 +)))
487 +
493 493  The charging/discharging contactor control is configured in the “Control – Charge/Discharge” section:
494 494  
495 -[[image:1733746901779-991.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="95" width="800"]]In this section:
490 +[[image:1740400166950-906.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="211" width="800"]]
496 496  
492 +In this section:
493 +
497 497  * Enable – a flag to enable the charge/discharge controller.
495 +* Algorithm:
496 +** Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
497 +** Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
498 +** Independent (on Charge request or Discharge request);
499 +* Delay before starting charging or discharging, millisecond;
500 +* Delay before stopping charging or discharging, millisecond;
501 +* Control the precharging contactor – a flag that enables control of precharging contactor while closing the charge/discharge contactor;
502 +* Emulate the "Charging" and "Discharging" signals – a flag to enable generation of "Charging" and "Discharging" signals when closing charge/discharge contactor;
503 +* Errors 1, 2 to prevent CHARGING through charging/discharging contactor, Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor – bitfields to choose the errors which will open the charging/discharging contactor. This bitfields are combined by bitwise OR and intended to separate settings for charging and discharging processes;
504 +* Errors 1, 2 which affect the contactor only if battery CHARGING is detected – a bitfield to choose the errors which will trigger only if charging current is present. This bitfield is combined with "Errors 1, 2 to prevent CHARGING through charging/discharging contactor" by bitwise AND;
505 +* Errors 1, 2 which affect the contactor only if battery DISCHARGING is detected – a bitfield to choose the errors which will trigger only if discharging current is present. This bitfield is combined with "Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor" by bitwise AND;
506 +* Switch off the charging/discharging contactor on errors without delay – a flag to protectively open the charging/discharging contactor without a delay. In the opposite case, when an error is detected, the charging/discharging contactor opens always with the delay “Delay before stopping discharging”.
498 498  
499 499  === Discharge (AUX) ===
500 500  
... ... @@ -510,8 +510,9 @@
510 510  
511 511  To change the parameters of the powering of external equipment, select the "Control → Discharge (AUX)" section:
512 512  
513 -[[image:1733746932199-845.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="137" width="800"]]
514 514  
523 +[[image:1740400254884-851.png]]
524 +
515 515  In this section:
516 516  
517 517  * Enable – a flag to activate the auxiliary discharge control;
1740399783613-216.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +59.8 KB
Content
1740400166950-906.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +49.2 KB
Content
1740400254884-851.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +40.2 KB
Content