... ... @@ -338,6 +338,7 @@
338 338  To change the parameters of precharge contactor, select the "Control → Precharge" section:
339 339  
340 340  * Precharge current threshold to finish precharging – a minimum current value at which precharging process assumed to be finished, A;
341 +* Minimum voltage difference to finish precharging – minimal voltage difference before and after contactors at which precharge process is meant to be finished, V;
341 341  * Number of precharging attempts – maximum number of precharging attempts before setting the "Precharge error";
342 342  * Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond;
343 343  * Relaxation between attempts – a duration between precharge attempts, millisecond;
... ... @@ -351,6 +351,7 @@
351 351  “Precharge error” generation conditions if any of the following is true:
352 352  
353 353  * the precharge current does not decrease during the "Precharge time" after "Number of precharging attempts";
355 +* voltages before and after contactors are not equal during the "Precharge time" after "Number of precharging attempts";
354 354  * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
355 355  
356 356  (% class="box warningmessage" %)