Changes for page 3.3 Control

Last modified by Admin on 2025/04/09 12:15

From version 11.1
edited by Admin
on 2025/02/24 11:31
Change comment: Загрузить новое вложение 1740396670709-638.png
To version 15.2
edited by Admin
on 2025/02/24 11:41
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -166,6 +166,34 @@
166 166  The "Low SOC signal" is indicative and can be output to a discrete output or a power switch.
167 167  )))
168 168  
169 +=== High charging current (signal) ===
170 +
171 +To change the parameters of the generation high-current signal, select the "Control → High charging current (signal)" section:
172 +
173 +[[image:1740396996935-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="144" width="800"]]
174 +
175 +In this section:
176 +
177 +* Enable – a flag to enable signal generation;
178 +* Maximum charging current, А;
179 +* Tolerant charging current, А;
180 +* Delay before setting the signal, second;
181 +* Delay before clearing the signal, second;
182 +* Lock – lock the signal until the device is reset.
183 +
184 +Signal generation conditions:
185 +
186 +* the measured current is greater than the “Maximum charging current” value during the “Delay before setting the signal” time.
187 +
188 +Conditions for clearing the signal:
189 +
190 +* the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
191 +
192 +(% class="box infomessage" %)
193 +(((
194 +The "High charging current" signal is indicative and can be output to a discrete output or a power switch.
195 +)))
196 +
169 169  === Charge map ===
170 170  
171 171  The BMS Mini device calculates maximum allowable charge current values in respect to SOC, battery temperature, contactor temperature and cell voltage.
... ... @@ -174,31 +174,25 @@
174 174  
175 175  To configure parameters for determining the charge current limit, select the "Control → Charge map" section:
176 176  
177 -[[image:1733746766504-864.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
178 -
205 +[[image:1740397188247-315.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="179" width="800"]]
179 179  In this section:
180 180  
181 181  * Enable – a flag to start calculation of the charge current limit;
182 -* Maximum charge current – a maximum allowable value of the charge current (under normal conditions):
183 -* Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and battery temperature;
209 +* Maximum charge current – a maximum allowable value of the charge current (under normal conditions), A;
210 +* Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
211 +* Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current** Kcs** depending on SOC and battery temperature;
184 184  * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
185 -
186 -[[image:1733746766506-660.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="196" width="800"]]
187 -
188 -* Option 2: Limit charge current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on contactor temperature;
213 +* Option 2: Limit charge current by the contactor temperature – a flag to enable correction of maximum allowable charging current **Kcc** depending on contactor temperature;
189 189  * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
215 +* Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current **Kcv** depending on maximum cell voltage;
216 +* Option 3: Cell voltage x Factor – the dependence of the correction factor on maximum cell voltage;
217 +* Option 4: Limit charge current by the cell temperature - a flag to enable correction of maximum allowable charging current **Kct** depending on maximum cell temperature;
218 +* Option 4: Cell temperature x Factor – the dependence of the correction factor on maximum cell temperature.
190 190  
191 -[[image:1733746766508-178.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="184" width="800"]]
220 +Value of the charge current limit at given SOC, temperature, contactors temperature, maximum cell voltage and maximum cell temperature is calculated as follows:
192 192  
193 -* Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage;
194 -* Option 3: Cell voltage x Factor – the dependence of the correction factor on maximum cell voltage.
222 +**Charge current limit = Maximum charge current × Kcs × Kcc × Kcv × Kct**
195 195  
196 -[[image:1733746766509-971.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="217" width="800"]]
197 -
198 -Value of the charge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows:
199 -
200 -Charging current limit = Maximum charging current × Kcs × Kcc × Kcv
201 -
202 202  === Discharge map ===
203 203  
204 204  The BMS Mini device calculates maximum allowable discharge current values in respect to SOC, battery temperature, contactor temperature and cell voltage.
1740396996935-403.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +21.7 KB
Content
1740397115348-751.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +31.2 KB
Content
1740397167225-463.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +44.4 KB
Content
1740397188247-315.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +49.0 KB
Content