3
4 == Safety rules ==
5
6 To perform the protection functions, the BMS must be able to disconnect the battery from the load and charger. To do this, **at least one contactor** able to break the load and charge circuits must be connected to the BMS.
7
8 Before use, **configure the system**. Proper operation of the BMS is possible only if it is correctly configured.
9
10 It is not recommended to use the system in batteries formed by several series of cells connected in parallel. To increase capacity, it is recommended to connect several cells in parallel groups, and then connect the groups in series.
11
12 (% class="box errormessage" %)
13 (((
14 The BMS can be connected to batteries with life-threatening and health-hazardous voltage levels. When working with high-voltage batteries, observe electrical safety regulations, use safety glasses, protective clothing, insulated tools and appliances. To prevent the damage of device avoid electrostatic discharges while working with the battery.
15 )))
16
17 (% class="box errormessage" %)
18 (((
19 The system is not designed to operate with batteries whose total voltage exceeds 60 V.
20 )))
21
22 == Installation procedure ==
23
24 The mounting area of the BMS Mini S must be protected from mechanical particles (dust, dirt, large objects) and water. The BMS Mini S is recommended to be placed close to the cells it controls, but away from high current circuits to reduce interference to measuring circuits and increase overall reliability of installation.
25
26 The installation site must provide convenient access for subsequent connection to the device’s headers for connecting other system elements: a current sensor, contactors, display panels.
27
28 The BMS Mini S has a heat sink to dissipate the heat generated during the balancing of the cells. When used in enclosed enclosures, heat must be removed from the sink, otherwise it may damage the device.
29
30 Overall and mounting dimensions of the BMS Mini S are shown on figures below.
31
32
33 [[image:1733740731815-730.png||data-xwiki-image-style-alignment="center" height="454" width="516"]]
34
35 [[image:1733740731820-300.png||data-xwiki-image-style-alignment="center" height="172" width="453"]]
36
37 |**Parameter**|**Value **
38 |Overall dimensions (length × width × height), mm|124.5 × 117 × 17
39 |Mounting dimensions (length × width), mm|115 × 111
40 |Mounting holes|M3
41
42 == Headers ==
43
44 There are names and locations of the BMS Mini S headers on figure below.
45
46 [[image:1733740765989-365.png||data-xwiki-image-style-alignment="center" height="423" width="526"]]
47
48 === X1 – header for contactors ===
49
50 Receptacle Housing: Molex 430251800. Terminals: Molex 43030
51
52 [[image:1733738660904-795.jpeg||data-xwiki-image-style-alignment="center" height="96" width="316"]]
53
54 |**Pin**|**Name**|**Description**
55 |**1**|**-**|-
56 |**2**|**+12V**|Supply voltage from the internal 12V DC/DC converter
57 |**3**|**GND**|Ground
58 |**4**|**+12V**|Supply voltage from the internal 12V DC/DC converter
59 |**5**|**GND**|Ground
60 |**6**|**+12V**|Supply voltage from the internal 12V DC/DC converter
61 |**7**|**GND**|Ground
62 |**8**|**+12V**|Supply voltage from the internal 12V DC/DC converter
63 |**9**|**GND**|Ground
64 |**10**|**-**|-
65 |**11**|**FB1**|Feedback signal from contactor 1
66 |**12**|**OUT1**|Contactor control 1 (low side switch), 60V, max 5A
67 |**13**|**FB2**|Feedback signal from contactor 2
68 |**14**|**OUT2**|Contactor control 2 (low side switch), 60V, max 5A
69 |**15**|**FB3**|Feedback signal from contactor 3
70 |**16**|**OUT3**|Contactor control 3 (low side switch), 60V, max 5A
71 |**17**|**FB4**|Feedback signal from contactor 4
72 |**18**|**OUT4**|Contactor control 4 (low side switch), 60V, max 5A
73
74 (% class="box warningmessage" %)
75 (((
76 **ATTENTION!!!**
77 The load should be connected to +12V and OUTx pins. The feedback signal should be connected to FBx and GND pins. Below is an example of connecting the BMS to a contactor:
78 [[image:1733738760833-185.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true"]]
79 )))
80
81 === X2 – mini-USB connector. ===
82
83 Mini-USB connector is used for configuring the BMS via ElectricDeviceMonitor.
84
85 === X3 – header for discrete inputs and outputs signals ===
86
87 Receptacle Housing: Molex 430251600. Terminals: Molex 43030
88
89 (% class="wikigeneratedid" %)
90 [[image:1733738860923-996.png||data-xwiki-image-style-alignment="center" height="90" width="283"]]
91
92 |**Pin**|**Name**|**Description**
93 |**1**|**DIN1**|Discrete input 1 “dry contact” (+5V)
94 |**2**|**DIN2**|Discrete input 2 “dry contact” (+5V)
95 |**3**|**DIN3**|Discrete input 3 “dry contact” (+5V)
96 |**4**|**DIN4**|Discrete input 4 “dry contact” (+5V)
97 |**5**|**DOUT1**|Discrete output 1 (+5V, 20mA)
98 |**6**|**DOUT2**|Discrete output 2 (+5V, 20mA)
99 |**7**|**DOUT3**|Discrete output 3 (+5V, 20mA)
100 |**8**|**DOUT4**|Discrete output 4 (+5V, 20mA)
101 |**9**|**GND**|Discrete input 1 “dry contact” (ground)
102 |**10**|**GND**|Discrete input 2 “dry contact” (ground)
103 |**11**|**GND**|Discrete input 3 “dry contact” (ground)
104 |**12**|**GND**|Discrete input 4 “dry contact” (ground)
105 |**13**|**GND**|Discrete output 1 (ground)
106 |**14**|**GND**|Discrete output 2 (ground)
107 |**15**|**GND**|Discrete output 3 (ground)
108 |**16**|**GND**|Discrete output 4 (ground)
109
110 === Х4 – header for САN and RS485 interfaces ===
111
112 Receptacle Housing: Molex 430250600. Terminals: Molex 43030
113
114 [[image:1733738660905-974.jpeg||data-xwiki-image-style-alignment="center" height="70" width="97"]]
115
116 |**Pin**|**Name**|**Description**
117 |**1**|**RS485_B**|RS485 line B
118 |**2**|**+5V**|Isolated supply voltage 5V, max 400mA
119 |**3**|**CAN_L**|CAN-L line of the CAN bus
120 |**4**|**RS485_A**|RS485 line A
121 |**5**|**GND**|Isolated ground
122 |**6**|**CAN_H**|CAN-H line of the CAN bus
123
124 === Х5 – header for ON/OFF button ===
125
126 (% class="wikigeneratedid" %)
127 Receptacle Housing: Molex 430250200. Terminals: Molex 43030
128
129 (% class="wikigeneratedid" %)
130 [[image:1733739076878-324.png||data-xwiki-image-style-alignment="center" height="70" width="41"]]
131
132 |**Pin**|**Name**|**Description**
133 |**1**|**BTN**|Signal to turn on/off the BMS (“dry contact”, +3.3V)
134 |**2**|**GND**|Signal to turn on/off the BMS (“dry contact”, ground)
135
136 === X6 – header for cells temperature sensors ===
137
138 Receptacle Housing: Molex 430251200. Terminals: Molex 43030
139
140 [[image:1733738660906-697.png||data-xwiki-image-style-alignment="center" height="91" width="190"]]
141
142 |**Pin**|**Name**|**Description**
143 |**1**|**TEMPG1**|Ground of the thermistor 1
144 |**2**|**TEMPG2**|Ground of the thermistor 2
145 |**3**|**TEMPG3**|Ground of the thermistor 3
146 |**4**|**TEMPG4**|Ground of the thermistor 4
147 |**5**|**TEMPG5**|Ground of the thermistor 5
148 |**6**|**TEMPG6**|Ground of the thermistor 6
149 |**7**|**TEMP1**|Signal from the thermistor 1
150 |**8**|**TEMP2**|Signal from the thermistor 2
151 |**9**|**TEMP3**|Signal from the thermistor 3
152 |**10**|**TEMP4**|Signal from the thermistor 4
153 |**11**|**TEMP5**|Signal from the thermistor 5
154 |**12**|**TEMP6**|Signal from the thermistor 6
155
156 === X7 - header for current sensor ===
157
158 (% class="wikigeneratedid" %)
159 Receptacle Housing: Molex 430250400. Terminals: Molex 43030
160
161 (% class="wikigeneratedid" %)
162 [[image:1733739118831-618.png||data-xwiki-image-style-alignment="center" height="79" width="71"]]
163
164 |**Pin**|**Name**|**Description**
165 |**1**|**+5V**|Supply voltage for a current sensor 5V, max 50 mA
166 |**2**|**GND**|Ground
167 |**3**|**Vcs**|ADC input (current sensor output)
168 |**4**|**Vref**|Auxiliary ADC input (current sensor reference signal)
169
170 === Х8 – header for battery cells ===
171
172 Receptacle Housing: Molex 430251400. Terminals: Molex 43030
173
174 [[image:1733740846257-439.png||data-xwiki-image-style-alignment="center" height="89" width="219"]]
175
176 |**Pin**|**Name**|**Description**
177 |**1**|**C0**|Minus of the cell stack (for measuring purposes only)
178 |**2**|**C2**|Cell 2
179 |**3**|**C4**|Cell 4
180 |**4**|**C6**|Cell 6
181 |**5**|**C8**|Cell 8
182 |**6**|**C10**|Cell 10
183 |**7**|**C12**|Cell 12 (maximum potential of the cell stack, for measuring purposes only)
184 |**8**|**NC**|Not connected
185 |**9**|**C1**|Cell 1 (minimum potential with respect to C0)
186 |**10**|**C3**|Cell 3
187 |**11**|**C5**|Cell 5
188 |**12**|**C7**|Cell 7
189 |**13**|**C9**|Cell 9
190 |**14**|**C11**|Cell 11
191
192 === Х9 – header to power the device ===
193
194 Receptacle Housing: Molex 436450200. Terminals: Molex 43030
195
196 [[image:1733738660910-242.png||data-xwiki-image-style-alignment="center" height="61" width="78"]]
197
198 |**Pin**|**Name**|**Description**
199 |**1**|**VBAT+**|Supply voltage for BMS Mini S
200 |**2**|**VBAT-**|BMS Mini S power ground
201
202 (% class="box warningmessage" %)
203 (((
204 **Attention! **The BMS Mini S device is **galvanically connected** to the battery (the minus of the battery is the device ground). In view of this, when a BMS Wi-Fi or BMS GSM module is connected to the device, the antenna braid will also be galvanically connected to the battery (connected to the battery negative). It is recommended to** isolate the antenna cable from the battery case **to prevent negative potential from appearing on the case.
205 )))
206
207 === J1 – jumper for switching CAN bus terminal resistor ===
208
209 To connect the terminal resistor between the** CAN_H** and **CAN_L** lines, install the jumper J1 according to the following figure:
210
211 [[image:1733738660910-372.png||data-xwiki-image-style-alignment="center" height="85" width="162"]]
212
213 === J2 – jumper for switching RS-485 terminal resistor ===
214
215 To connect the terminal resistor between the** RS485_A** and **RS485_B** lines, install the jumper J1 according to the following figure:
216
217 [[image:1733738660910-372.png||data-xwiki-image-style-alignment="center" height="85" width="162"]]
218
219 == Connection procedure ==
220
221 === Connecting battery cells ===
222
223 To connect battery cells, follow figure below. Incorrect connection of the cells can damage the BMS Mini.
224
225 Begin the connection with the negative line of the battery: the “C0“ is connected to the “B-“, then the first cell (C1) is connected, then the second (С2), etc. If not all inputs of the cells are used, then the remaining inputs are connected to the cell with the most potential.
226
227 [[image:1733740980966-804.png||data-xwiki-image-style-alignment="center" height="471" width="721"]]
228
229 (% class="box warningmessage" %)
230 (((
231 **Attention!**
232 Connect the battery according to the diagram, otherwise the device may be damaged.
233 )))
234
235 === Connecting thermistors ===
236
237 Thermistors should be fastened to the cells, excluding short circuits to the cell terminals (for example, isolate thermistors with heat shrink).