4.3 Modules

Last modified by Admin on 2026/09/04 13:59

Monitoring

Modules

Summary information on battery modules is in the "Modules" section:

1740999241699-436.png

In this section:

  • Number of modules – number of modules discovered by the device;
  • Modules: Not present – indication of battery modules that are enabled in settings but not detected by the device;
  • Modules: Present – indication of battery modules that are enabled in settings and detected by the device;
  • Modules: Online – indication of battery modules which have no errors in communication;
  • Modules: Offline – indication of battery modules which don’t communicate with the device;
  • Modules: Balancing – indication of battery modules which are disabled by the balancing algorithm;
  • Modules: Ready to join to charge – indication of battery modules which are ready to join to charge;
  • Modules: Ready to join to discharge – indication of battery modules which are ready to join to discharge;
  • Modules: Joined to charge – indication of battery modules which are joined for charging;
  • Modules: Joined to discharge – indication of battery modules which are joined discharging;
  • Minimum cell temperature – minimum temperature among all the battery cells, °C;
  • Min. cell temp.: module index – a module number with the cell having the minimum temperature;
  • Min. cell temp.: Logic index – a BMS Logic number to which the cell with the minimum temperature is connected;
  • Min. cell temp.: cell index – a number of the cell that has the minimum temperature;
  • Maximum cell temperature – maximum temperature among all the battery cells, °C;
  • Max. cell temp.: module index – a module number with the cell having the maximum temperature;
  • Max. cell temp.: Logic index – a BMS Logic number to which the cell with the maximum temperature is connected;
  • Max. cell temp.: cell index – a number of the cell that has the minimum temperature;
  • Minimum cell voltage – minimum voltage among all the battery cells, V;
  • Min. cell volt.: module index – a module number with the cell having the minimum voltage;
  • Min. cell volt.: Logic index – a BMS Logic number to which the cell with the minimum voltage is connected;
  • Min. cell volt.: cell index – a number of the cell that has the minimum voltage;
  • Maximum cell voltage – maximum voltage among all the battery cells, V;
  • Max. cell volt.: module index – a module number with the cell having the maximum voltage;
  • Max. cell volt.: Logic index – a BMS Logic number to which the cell with the maximum voltage is connected;
  • Max. cell volt.: cell index – a number of the cell that has the maximum voltage;
  • Minimum module voltage – minimum voltage among all the battery modules, V;
  • Min. mod. volt.: module index – a module number that has the minimum voltage;
  • Maximum module voltage – maximum voltage among all the battery modules, V;
  • Max. mod. volt.: module index – a module number that has the maximum voltage.

Module #1-32

Detailed information on each module is in the sections "Modules → Module #1".. "Modules → Module #32":

1740999363518-362.png

In these sections:

  • State – state of the battery module:
    • Discharging ON – battery module is discharging;
    • Discharging OFF – battery module is idle after discharging;
    • Relaxed (after discharging) – battery module is relaxed after discharging;
    • Charing ON – battery module is charging;
    • Charging OFF – battery module is idle after charging;
    • Relaxed (after charging) – battery module is relaxed after charging;
  • Firmware version – version of the embedded software;
  • Voltage – voltage of the battery module, V;
  • Current – current of the battery module, A;
  • Internal resistance – internal resistance of the battery module, Ohm;
  • Minimum temperature – minimum temperature among all the cells, °C;
  • Min. cell temp.: Logic index – a BMS Logic number to which the cell with the minimum temperature is connected;
  • Min. cell temp.: cell index – a number of the cell that has the minimum temperature;
  • Maximum temperature – maximum temperature among all the cells, °C;
  • Max. cell temp.: Logic index – a BMS Logic number to which the cell with the maximum temperature is connected;
  • Max. cell temp.: cell index – a number of the cell that has the maximum temperature;
  • Minimum voltage – minimum voltage among all the cells, V;
  • Min. cell volt.: Logic index – a BMS Logic number to which the cell with the minimum voltage is connected;
  • Min. cell volt.: cell index – a number of the cell that has the minimum voltage;
  • Maximum voltage – maximum voltage among all the cells, V;
  • Max. cell volt.: Logic index – a BMS Logic number to which the cell with the maximum voltage is connected;
  • Max. cell volt.: cell index – a number of the cell that has the maximum voltage;
  • SOC – state of charge of the battery module, %;
  • SOH – state of health of the battery module, %;
  • Capacity – capacity of the battery module, Ah;
  • Charge current limit – maximum allowed charging current of the battery module, A;
  • Discharge current limit – maximum allowed discharging current of the battery module, A;
  • Balancing efficiency – balancing efficiency of the battery module, %;
  • Energy+ - energy received by the module from the charger and during recuperation, Wh;
  • Energy- - energy spent by the module on the load, Wh;
  • Balanced energy – energy dissipated by the module on balancing resistors, Wh;
  • Cycles – a number of charge-discharge cycles (1 cycle equals 80% SOC);
  • Input signals – input signals of the module (see Input signals).
  • Internal signals – module internal signals (see Internal signals);
  • Errors (1), Errors (2) – registers with module errors (see Errors).