Configuration
Inputs and outputs
Discrete inputs
The BMS Main X device has 4 discrete inputs of the "dry contact" type. For each discrete input, its assignment and inversion flag are set.
Assignments of discrete inputs are configured in the "Signals - Input discrete signals - Assignments" section:
The device supports the following discrete inputs assignments:
- No input – input is not used;
- Battery cover – a signal from the battery cover;
- Charge request – a request to close the main charging contactor;
- Precharge request – a request to close the main precharging contactor;
- Discharge request – a request to close the main discharging contactor;
- Charging contactor feedback – a feedback signal from the charging contactor;
- Discharging contactor feedback – a feedback signal from the discharging contactor;
- Charging/Discharging contactor feedback – a feedback signal from the charging/discharging contactor;
- Insulation status – a signal from an insulation monitoring device;
- Join to charge – a request to join (connect in parallel) battery modules to charge the battery;
- Join to discharge – a request to join (connect in parallel) battery modules to discharge the battery.
Inversion flags for discrete inputs are configured in the "Signals - Input discrete signals - Inversion" section:
Discrete outputs
The BMS Main X device has 4 +5V digital outputs. For each discrete output, its assignment and inversion flag are set.
Assignments of discrete outputs are configured in the "Signals - Output discrete signals - Assignments" section:
The device supports the following digital output assignments:
- No output – output is not used.
Inversion flags for discrete outputs are configured in the "Signals - Output discrete signals - Inversion" section:
Relays
The BMS Main X device has 3 opto-relays for controlling main contactors. For each opto-relay, its assignment and inversion flag are set.
Assignments of relays are configured in the "Signals - Relays - Assignments" section:
The device supports the following relay assignments:
- No relay – relay is not used;
- Charging – main charging contactor;
- Precharging – main precharging contactor;
- Discharging – main discharging contactor;
- Charging/Discharging – main charging/discharging contactor.
Inversion flags for relays are configured in the “Signals – Relays – Inversion” section: