Last modified by Admin on 2025/03/18 12:50

From version 8.1
edited by Admin
on 2025/02/20 13:13
Change comment: There is no comment for this version
To version 1.1
edited by Admin
on 2024/12/16 13:23
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -Battery management systems.BMS Main X.WebHome
1 +drafts.BMS Main X.WebHome
Content
... ... @@ -3,11 +3,11 @@
3 3  
4 4  == Installation ==
5 5  
6 -The mounting area of the BMS Main X must be protected from mechanical particles (dust, dirt, large objects) and water.
6 +The mounting area of the BMS Main X 2.x must be protected from mechanical particles (dust, dirt, large objects) and water.
7 7  
8 8  The installation site must provide convenient access for subsequent connection to the device’s headers for connecting other system elements: contactors, temperature sensors, etc.
9 9  
10 -Overall and mounting dimensions of the BMS Main X are shown below.
10 +Overall and mounting dimensions of the BMS Main X 2.x are shown in Figures 6 and 7.
11 11  
12 12  [[image:1734355103230-973.png||data-xwiki-image-style-alignment="center" height="460" width="450"]]
13 13  [[image:1734355103237-284.png||data-xwiki-image-style-alignment="center" height="207" width="450"]]
... ... @@ -31,8 +31,6 @@
31 31  
32 32  === Х1 – header for power supply ===
33 33  
34 -Receptacle Housing: Molex 436450200. Terminals: Molex 43030
35 -
36 36  [[image:1734355208747-667.png||data-xwiki-image-style-alignment="center"]]
37 37  
38 38  |**Pin**|**Name**|**Description**
... ... @@ -43,8 +43,6 @@
43 43  
44 44  === X3 – header for CAN (INT) interface ===
45 45  
46 -Receptacle Housing: Molex 430250400. Terminals: Molex 43030
47 -
48 48  [[image:1734355229969-197.png||data-xwiki-image-style-alignment="center"]]
49 49  
50 50  |**Pin**|**Name**|**Description**
... ... @@ -55,8 +55,6 @@
55 55  
56 56  === Х4 – header for RS-485 interface ===
57 57  
58 -Receptacle Housing: Molex 430250400. Terminals: Molex 43030
59 -
60 60  [[image:1734355229969-197.png||data-xwiki-image-style-alignment="center"]]
61 61  
62 62  |**Pin**|**Name**|**Description**
... ... @@ -70,75 +70,3 @@
70 70  To connect the terminal resistor between the** RS485_A** and **RS485_B** lines, install the jumper J1 according to the following figure:
71 71  
72 72  [[image:1734355346488-798.png||data-xwiki-image-style-alignment="center"]]
73 -
74 -=== Х5 – header for CAN (EXT) interface ===
75 -
76 -Receptacle Housing: Molex 430250400. Terminals: Molex 43030
77 -
78 -[[image:1734355229969-197.png||data-xwiki-image-style-alignment="center"]]
79 -
80 -|**Pin**|**Name**|**Description**
81 -|**1**|**СAN_EXT_H**|CAN-H line of the external CAN bus (communication with a top-level system)
82 -|**2**|**CAN_EXT_L**|CAN-L line of the external CAN bus (communication with a top-level system)
83 -|**3**|**CAN_EXT_5V**|Isolated 5V power supply for external devices, max 200 mA
84 -|**4**|**CAN_EXT_GND**|Isolated ground
85 -
86 -=== J2 – jumper for switching CAN (EXT) terminal resistor ===
87 -
88 -To connect the terminal resistor between the** CAN_EXT_H** and **CAN_EXT_L** lines, install the jumper J2 according to the following figure:
89 -
90 -[[image:1734355346488-798.png||data-xwiki-image-style-alignment="center"]]
91 -
92 -=== Х6 – header for sold-state relays ===
93 -
94 -Receptacle Housing: Molex 430250600. Terminals: Molex 43030
95 -
96 -[[image:1734355584041-898.jpeg||data-xwiki-image-style-alignment="center" height="65" width="90"]]
97 -
98 -|**Pin**|**Name**|**Description**
99 -|**1**|**NO1**|Normally open contact of the relay 1
100 -|**2**|**NO2**|Normally open contact of the relay 2
101 -|**3**|**NO3**|Normally open contact of the relay 3
102 -|**4**|**COM1**|Common contact of the relay 1 (55V, 2A)
103 -|**5**|**COM2**|Common contact of the relay 2 (55V, 2A)
104 -|**6**|**COM3**|Common contact of the relay 3 (55V, 2A)
105 -
106 -=== X7 – header for discrete inputs/outputs ===
107 -
108 -Receptacle Housing: Molex 430251800. Terminals: Molex 43030
109 -
110 -[[image:1734355584043-416.jpeg||data-xwiki-image-style-alignment="center" height="79" width="260"]]
111 -
112 -|**Pin**|**Name**|**Description**
113 -|**1**|**GND**|Discrete input 1 “dry contact” (ground)
114 -|**2**|**GND**|Discrete input 2 “dry contact” (ground)
115 -|**3**|**GND**|Discrete input 3 “dry contact” (ground)
116 -|**4**|**GND**|Discrete input 4 “dry contact” (ground)
117 -|**5**|**-**|-
118 -|**6**|**GND**|Discrete output 1 (ground)
119 -|**7**|**GND**|Discrete output 2 (ground)
120 -|**8**|**GND**|Discrete output 3 (ground)
121 -|**9**|**GND**|Discrete output 4 (ground)
122 -|**10**|**D_IN1**|Discrete input 1 “dry contact” (+5V)
123 -|**11**|**D_IN2**|Discrete input 2 “dry contact” (+5V)
124 -|**12**|**D_IN3**|Discrete input 3 “dry contact” (+5V)
125 -|**13**|**D_IN4**|Discrete input 4 “dry contact” (+5V)
126 -|**14**|**-**|-
127 -|**15**|**D_OUT1**|Discrete output 1 (+5V, 20mA)
128 -|**16**|**D_OUT2**|Discrete output 2 (+5V, 20mA)
129 -|**17**|**D_OUT3**|Discrete output 3 (+5V, 20mA)
130 -|**18**|**D_OUT4**|Discrete output 4 (+5V, 20mA)
131 -
132 -=== Х8 – header for temperature sensors ===
133 -
134 -Receptacle Housing: Molex 430250400. Terminals: Molex 43030
135 -
136 -[[image:1734355229969-197.png||data-xwiki-image-style-alignment="center"]]
137 -
138 -|**Pin**|**Name**|**Description**
139 -|**1**|**TEMPG1**|Ground of the thermistor 1
140 -|**2**|**TEMPG2**|Ground of the thermistor 2
141 -|**3**|**TEMP1**|Signal from the thermistor 1
142 -|**4**|**TEMP2**|Signal from the thermistor 2
143 -
144 -
1734355584041-898.jpeg
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -12.0 KB
Content
1734355584043-416.jpeg
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -24.8 KB
Content