Content
... ... @@ -14,8 +14,24 @@
14 14  
15 15  [[image:1734022225578-818.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="153" width="600"]]
16 16  
17 -A list of available discrete input assignments is available in [[Input signals>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HInputsignals"]].
17 +The device supports the following assignments for discrete inputs:
18 18  
19 +* No input – input is not used;
20 +* Battery cover – a signal from the battery cover;
21 +* Charge request – a request to close the charging contactor;
22 +* Precharge request – a request to close the precharging contactor;
23 +* Discharge request – a request to close the discharging contactor;
24 +* Charging contactor feedback – a signal from charging contactor feedback loop;
25 +* Discharging contactor feedback – a signal from discharging contactor feedback loop;
26 +* Charging/Discharging contactor feedback – a signal from charging/discharging contactor feedback loop;
27 +* Insulation status – a signal from an insulation monitoring device;
28 +* Join to charge – a request to join (connect in parallel) battery modules to charge the battery;
29 +* Join to discharge – a request to join (connect in parallel) battery modules to discharge the battery;
30 +* Precharge contactor feedback – a signal from precharging contactor feedback loop;
31 +* Main contactor feedback – a signal from main contactor feedback loop;
32 +* Interlock – a signal from interlock loop;
33 +* Power down request – a request to power down the BMS.
34 +
19 19  Inversion flags for discrete inputs are configured in the "Signals → Input discrete signals → Inversion" section:
20 20  
21 21  [[image:1734022225583-740.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="137" width="600"]]
... ... @@ -86,8 +86,19 @@
86 86  
87 87  [[image:1734022225588-223.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="131" width="600"]]
88 88  
89 -A list of available discrete output assignments is available in [[Internal signals>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HInternalsignals"]].
105 +The device supports the following assignments for discrete outputs:
90 90  
107 +* No output – output is not used.
108 +* Charging – state of the charging contactor;
109 +* Discharging – state of the discharging contactor;
110 +* Charging/Discharging - state of the charging/discharging contactor;
111 +* Precharging – state of the precharging contactor;
112 +* Heater – a command to turn on a heater;
113 +* Cooler – a command to turn on a cooler;
114 +* Main contactor – state of the main contactor;
115 +* Critical error – a signal indicating there is a Critical error on BMS Main 3X;
116 +* General error (modules) – a signal indicating there is a General error on one of the modules;
117 +
91 91  Inversion flags for discrete outputs are configured in the "Signals → Output discrete signals → Inversion" section:
92 92  