1 | (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %) | ||
2 | = Configuration = | ||
3 | |||
4 | (% data-numbered-headings-start="2" style="--numbered-headings-start: 1;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %) | ||
5 | == Inputs and outputs == | ||
6 | |||
7 | === Discrete inputs === | ||
8 | |||
9 | The BMS Main 3X device has **6 discrete inputs** that detect signal line closing to the virtual ground, and **2 inputs** that detect 9-32V input voltage. For each discrete input, its assignment and inversion flag are set. | ||
10 | |||
11 | Also, BMS has two additional configurable inputs named “KEYRUN” and “CHARGE_ON”, each serves 9-32V input voltage. Those inputs serve as power buttons with additional functions that can be set. | ||
12 | |||
13 | Assignments of discrete inputs are configured in the "Signals → Input discrete signals → Assignments" section: | ||
14 | |||
15 | [[image:1734022225578-818.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="153" width="600"]] | ||
16 | |||
17 | A list of available discrete input assignments is available in [[Input signals>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HInputsignals"]]. | ||
18 | |||
19 | Inversion flags for discrete inputs are configured in the "Signals → Input discrete signals → Inversion" section: | ||
20 | |||
21 | [[image:1734022225583-740.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="137" width="600"]] | ||
22 | |||
23 | The behavior of “KEYRUN” signal can be configured in the "Signals → Input discrete signals → KEYRUN mode" section: | ||
24 | |||
25 | [[image:1734022225584-474.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="87" width="600"]] | ||
26 | |||
27 | The behavior of “CHARGE_ON” signal can be configured in the "Signals → Input discrete signals → CHARGE_ON mode" section: | ||
28 | |||
29 | [[image:1734022225585-775.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="89" width="600"]] | ||
30 | |||
31 | In both “KEYRUN mode” and “CHARGE_ON mode” sections: | ||
32 | |||
33 | * Do nothing – power on device and do nothing; | ||
34 | * Set “Join to discharge” – power on device and set “Join to discharge” signal immediately; | ||
35 | * Set “Join to charge” – power on device and set “Join to charge” signal immediately; | ||
36 | * Set “Discharge request” – power on device and set “Discharge request” signal immediately; | ||
37 | * Set “Charge request” – power on device and set “Charge request” signal immediately. | ||
38 | |||
39 | === Current sensor === | ||
40 | |||
41 | The BMS Main 3X device has an ability to measure battery current by **3 external Hall-Effect current sensors**. | ||
42 | |||
43 | Current sensor settings are configured in the "Signals → Current sensor" section: | ||
44 | |||
45 | [[image:1734022225586-287.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="178" width="600"]] | ||
46 | |||
47 | The device supports the following current sensor settings: | ||
48 | |||
49 | * Calculate the battery current as the sum of battery modules currents – a flag that determines overall current as sum of battery modules currents (if flag is not set, device uses measurements from a physical current sensor); | ||
50 | * Connection – type of multiple sensors connection | ||
51 | ** One sensor (#1) – only first sensor is used to measure the battery current; | ||
52 | ** Two sensors (#1 and #2) in parallel – sensors are connected in parallel (the total battery current equals the sum of two sensors); | ||
53 | ** Two sensors (#1 and #2) in different branches – sensors located in two halves of the battery (used in batteries with a middle point); | ||
54 | * Sensor 2, 3: Enable – a flag to enable the second of third current sensor; | ||
55 | * Sensor 1, 2, 3: Nominal current – rated current I,,nom,, of the sensor according to the datasheet, A; | ||
56 | * Sensor 1, 2, 3: Sensitivity – sensitivity of the current sensor according to the datasheet, V / I,,nom.,,; | ||
57 | * Sensor 1, 2, 3: Invert – invert the sign of the measured value; | ||
58 | * Sensor 1, 2, 3: Multiply charging current (experimental) – an experimental flag for scaling the charging current by given multiplier; | ||
59 | * Sensor 1, 2, 3: Multiplier for charging current – charging current multiplier; | ||
60 | * Sensor 1, 2, 3: REF_IN2 mode – mode of additional analog line: | ||
61 | ** Not connected; | ||
62 | ** Reference line – reference output of the sensor; | ||
63 | ** Low range (for the dual range sensor) - a second output of a dual-range sensor (for example, LEM DHAB series); | ||
64 | * Sensor 1, 2, 3: Low range nominal current - rated current I,,nom,, of the low current line of dual range sensor according to the datasheet, A; | ||
65 | * Sensor 1, 2, 3: Low range sensitivity – sensitivity of the low current line of dual range sensor according to the datasheet, V / I,,nominal.,,; | ||
66 | * Sensor 1, 2, 3: Threshold for low range – a threshold current value at which the device uses the readings of the high current sensor instead of low current, A; | ||
67 | * Calibrate – a flag to calibrate (find a 0A point) the current sensor when the device is started; | ||
68 | * Calibration time – calibration time of the current sensor, millisecond; | ||
69 | * Recalibrate current sensor – a command to calibrate the current sensor manually. | ||
70 | |||
71 | === Temperature sensors === | ||
72 | |||
73 | Temperature sensors settings are configured in the "Signals → Temperature sensors" section: | ||
74 | |||
75 | [[image:1734022225587-758.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="58" width="600"]] | ||
76 | |||
77 | In this section: | ||
78 | |||
79 | * Type – a type of temperature sensors. | ||
80 | |||
81 | === Output discrete signals === | ||
82 | |||
83 | The BMS Main 3X device has **4 open drain outputs**. For each discrete output, its assignment and inversion flag are set. | ||
84 | |||
85 | Assignments of discrete outputs are configured in the "Signals → Output discrete signals → Assignments" section: | ||
86 | |||
87 | [[image:1734022225588-223.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="131" width="600"]] | ||
88 | |||
89 | A list of available discrete output assignments is available in [[Internal signals>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HInternalsignals"]]. | ||
90 | |||
91 | Inversion flags for discrete outputs are configured in the "Signals → Output discrete signals → Inversion" section: | ||
92 | |||
93 | [[image:1734022225589-659.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="118" width="600"]] | ||
94 | |||
95 | |||
96 | === Power switches === | ||
97 | |||
98 | The BMS Main 3X device has **6 power switches to drive contactors**. For each switch, its assignment and inversion flag are set. | ||
99 | |||
100 | Assignments of power switches are configured in the "Signals → Power switches → Assignments" section: | ||
101 | |||
102 | [[image:1734022225590-811.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="145" width="600"]] | ||
103 | |||
104 | The device supports the same switch assignments as discrete outputs. | ||
105 | |||
106 | Inversion flags for switches are configured in the “Signals → Power switches → Inversion” section: | ||
107 | |||