Wiki source code of 4.2 Battery

Version 15.2 by Admin on 2025/06/19 11:12

Show last authors
1 (% data-numbered-headings-start="4" style="--numbered-headings-start: 3;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 = Monitoring =
3
4 (% data-numbered-headings-start="2" style="--numbered-headings-start: 1;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 == Battery ==
6
7 Battery parameters are summarized in the "Battery" section:
8
9 [[image:1750331506968-446.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="562" width="800"]]
10
11 In this section:
12
13 * Voltage (sum of cell voltages) – voltage of the battery, defined as sum of all cell voltages, V;
14 * Voltage – voltage of the battery,  V;
15 * Current – current of the battery, A;
16 * Internal resistance – internal resistance of the battery, Ohm;
17 * Main voltage – supply voltage on the BMS, V;
18 * Power switch voltage – supply voltage on the power switches, V;
19 * Board temperature – internal temperature of the BMS, °C;
20 * Board humidity – relative humidity measured by the BMS, %;
21 * Temperature 1, 2 – temperature measured by the external temperature sensors, °C;
22 * Number of Logic devices – number of connected Logic devices;
23 * Logic command rate – number of commands transmitted to Logic devices, com/s;
24 * Minimum Logic temperature – minimum temperature among Logic devices, °C;
25 * Min. Logic temp.: Logic index – number of Logic with minimum temperature;
26 * Maximum Logic temperature – minimum temperature among Logic devices, °C;
27 * Max. Logic temp.: Logic index – number of Logic with maximum temperature;
28 * Number of cells – number of connected cells;
29 * Average cell temperature, °C;
30 * Minimum cell temperature, °C;
31 * Min. cell temp.: Logic index – number of Logic with minimum cell temperature;
32 * Min. cell temp.: cell index – number of cell with minimum temperature;
33 * Maximum cell temperature, °C;
34 * Max. cell temp.: Logic index  – number of Logic with maximum cell temperature;
35 * Max. cell temp.: cell index – number of cell with maximum temperature;
36 * Average cell voltage, V;
37 * Minimum cell voltage, V;
38 * Min. cell volt.: Logic index – number of Logic with minimum voltage;
39 * Min. cell volt.: cell index – number of cell with minimum voltage;
40 * Maximum cell voltage, V;
41 * Max. cell volt.: Logic index – number of Logic with maximum voltage;
42 * Max. cell volt.: cell index – number of cell with maximum voltage;
43 * Minimum cell SOC, %;
44 * Min. cell SOC: Logic index – number of Logic with minimum SOC;
45 * Min. cell SOC: cell index – number of cell with minimum SOC;
46 * Maximum cell SOC, %;
47 * Max. cell SOC: Logic index – number of Logic with maximum SOC;
48 * Max. cell SOC: cell index – number of cell with maximum SOC;
49 * Number of balancing cells;
50 * State:
51 ** Discharging ON;
52 ** Discharging OFF;
53 ** Relaxed (after discharging) – battery is in a state of relaxation after discharging;
54 ** Charing ON;
55 ** Charging OFF;
56 ** Relaxed (after charging) – battery is in a state of relaxation after charging;
57 * Duration – duration of the battery in the "State" state, s;
58 * SOC – state of charge of the battery, %;
59 * DOD – depth of discharge of the battery, A×h;
60 * SOH – state of health of the battery, %;
61 * Balancing efficiency – balancing efficiency of the battery, %;
62 * Effective capacity, А×h;
63 * Instant capacity – instantaneous value of the effective capacity (used to calculate the SOC), А×h;
64 * Coulomb counter + – charge received by the battery from the charger, А×h;
65 * Coulomb counter - – charge transferred to the battery load, А×h;
66 * Charge current limit – maximum allowed charge current of the battery, A;
67 * Discharge current limit – maximum allowed discharge current of the battery, A;
68 * High voltage 1 – voltage before the contactors, V;
69 * High voltage 2 – voltage after the contactors, V;
70 * Work charge+ - amount of charge received from charger (positive direction) since device startup, Ah;
71 * Work charge- - amount of charge transmitted to the load (negative direction) since device startup, Ah;
72 * Work energy+ - amount of energy received from charger (positive direction) since device startup, Wh;
73 * Work energy- - amount of energy transmitted to the load (negative direction) since device startup, Wh;
74 * Work energy regen - amount of regererated energy (positive direction) since device startup, Wh;
75 * Total energy+ - total energy received by the battery modules from the charger, Wh;
76 * Total energy- - total energy spent by the battery modules on the load, Wh;
77 * Total energy regen - total energy received by the battery modules during recuperation, Wh;
78 * Total balanced energy – total energy dissipated by the battery modules on balancing resistors, Wh;
79 * Input signals – a bitfield including input signals (see [[Input signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInputsignals"]]);
80 * Internal signals – a bitfield including device internal signals (see [[Internal signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInternalsignals"]]);
81 * Errors 1, 2 – errors of the battery (see [[Errors>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HErrors"]]).