... ... @@ -1,1 +1,1 @@
1 -Battery management systems.BMS Main 3.3\. Configuration.WebHome
1 +drafts.bms-main-3.3\. Settings.WebHome
Content
... ... @@ -1,5 +1,5 @@
1 1  (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 -= Configuration =
2 += Settings =
3 3  
4 4  (% data-numbered-headings-start="4" style="--numbered-headings-start: 3;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 5  == Protections ==
... ... @@ -42,12 +42,6 @@
42 42  If there is the "Overcurrent" error, the **charging **and **discharging **contactors open.
43 43  )))
44 44  
45 -=== Charge current limit ===
46 -
47 -
48 -=== Discharge current limit ===
49 -
50 -
51 51  === Undervoltage ===
52 52  
53 53  The BMS Main 3 device implements battery protection from too low voltage on the cells.
... ... @@ -300,9 +300,9 @@
300 300  
301 301  * a BMS Logic device temperature is less than the “Tolerant temperature” value.
302 302  
303 -(% class="box infomessage" %)
297 +(% class="box warningmessage" %)
304 304  (((
305 -Cell balancing is disabled on Logic devices with high temperature.
299 +Overheated Logic devices do not balance cells.
306 306  )))
307 307  
308 308  === Logic offline ===
... ... @@ -592,7 +592,7 @@
592 592  
593 593  (% class="box warningmessage" %)
594 594  (((
595 -If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error”** is generated and **all relays open.**
589 +If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error”** is generated and **all relays open.**​​​​​​​
596 596  )))
597 597  
598 598  === WDT reset ===
... ... @@ -618,7 +618,7 @@
618 618  If there is the "WDT reset" error, the **“Critical error” **is generated and **all relays open.**
619 619  )))
620 620  
621 -=== Unallowable charging ===
615 +=== ​​​​​​​Unallowable charging ===
622 622  
623 623  The BMS can detect that the battery is charging through the discharging circuit and protectively open the discharging contactor to prevent unallowable battery operation.
624 624  
... ... @@ -648,7 +648,7 @@
648 648  If there is the "Unallowable charging" error, the **discharging **contactor opens.
649 649  )))
650 650  
651 -=== Stuck contactor ===
645 +=== ​​​​​​​Stuck contactor ===
652 652  
653 653  The BMS Main 3 device protects contactors against sticking.
654 654  
... ... @@ -698,8 +698,30 @@
698 698  If there is the “Contactor feedback” error, the **“Critical error” **is generated and **all relays open.**
699 699  )))
700 700  
701 -=== Insulation ===
695 +=== ​​​​​​​Precharge ===
702 702  
697 +BMS Main 3 device detects errors while pre-charging the load capacity by monitoring the current and voltage difference before and after contactors. To change the pre-charge monitoring parameters, select the "Protections → Precharge" section:
698 +
699 +[[image:1733328487097-648.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="99" width="800"]]
700 +
701 +In this section:
702 +
703 +* Enable – a flag to enable the protection;
704 +* Delay before setting the error, millisecond;
705 +* Delay before clearing the error, second;
706 +* Lock – a flag to block the error until the device is restarted.
707 +
708 +As a result of the protection algorithms the “Precharge error” is generated. Error generation conditions:
709 +
710 +* precharging process cannot be finished (the precharge current does not decrease or voltages before and after contactors are not equal) during the “Delay before setting the error” time.
711 +
712 +(% class="box infomessage" %)
713 +(((
714 +If there is the “Precharge error”, **charging **and **discharging **contactors open.
715 +)))
716 +
717 +=== ​​​​​​​Insulation ===
718 +
703 703  The BMS Main 3 device can detect a physical signal or CAN bus message from an external insulation monitoring device (such as Bender IR155, iso165C, BMD IMD) to monitor the insulation quality.
704 704  
705 705  To change the insulation monitoring parameters, select the "Protections → Insulation" section:
... ... @@ -789,7 +789,7 @@
789 789  If there is the “Critical error”, **all **contactors open.