Changes for page 3.4 Protections

Last modified by Admin on 2025/04/09 12:19

From version 6.1
edited by Admin
on 2024/12/24 18:36
Change comment: There is no comment for this version
To version 15.1
edited by Admin
on 2024/12/26 14:56
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -12,7 +12,7 @@
12 12  
13 13  To change the overcurrent protection of the battery, select the "Protections → Overcurrent" section:
14 14  
15 -[[image:1733328382376-958.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
15 +[[image:1735224601506-488.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="123" width="800"]]
16 16  
17 17  In this section:
18 18  
... ... @@ -42,6 +42,14 @@
42 42  If there is the "Overcurrent" error, the **charging **and **discharging **contactors open.
43 43  )))
44 44  
45 +=== Charge current limit ===
46 +
47 +TBA
48 +
49 +=== Discharge current limit ===
50 +
51 +TBA
52 +
45 45  === Undervoltage ===
46 46  
47 47  The BMS Main 3 device implements battery protection from too low voltage on the cells.
... ... @@ -48,7 +48,7 @@
48 48  
49 49  To change the battery protection parameters from low voltage on the cells, select the "Protections → Undervoltage" section:
50 50  
51 -[[image:1733328382380-760.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="127" width="800"]]
59 +[[image:1735224224155-829.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="112" width="800"]]
52 52  
53 53  In this section:
54 54  
... ... @@ -55,6 +55,7 @@
55 55  * Enable – a flag to enable the protection;
56 56  * Minimum cell voltage, V;
57 57  * Tolerant cell voltage, V;
66 +* Check the open circuit voltage instead of the actual voltage – a flag to enable the check of voltage correction due to current and cell resistance;
58 58  * Delay before setting the error, millisecond;
59 59  * Delay before clearing the error, second;
60 60  * Lock – a flag to block the error until the device is restarted.
... ... @@ -80,7 +80,7 @@
80 80  
81 81  To change the battery protection parameters from high voltage on the cells, select the "Protections → Overvoltage" section:
82 82  
83 -[[image:1733328382382-607.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
92 +[[image:1735224377252-473.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="114" width="800"]]
84 84  
85 85  In this section:
86 86  
... ... @@ -87,9 +87,9 @@
87 87  * Enable – a flag to enable the protection;
88 88  * Maximum cell voltage, V;
89 89  * Tolerant cell voltage, V;
99 +* Check the open circuit voltage instead of the actual voltage – a flag to enable the check of voltage correction due to current and cell resistance;
90 90  * Delay before setting the error, millisecond;
91 91  * Delay before clearing the error, second;
92 -* Switch off the discharging contactor on error – a flag to open the discharging contactor when the "Overvoltage" error is generated;
93 93  * Lock – a flag to block the error until the device is restarted.
94 94  
95 95  As a result of the operation of the battery protection from high voltage, the "Overvoltage" error is generated.
... ... @@ -269,7 +269,7 @@
269 269  If there is the “Water” error, the **“Critical error”** is generated and **all relays open**.
270 270  )))
271 271  
272 -=== High Logic temperature ===
281 +=== Logic high temperature ===
273 273  
274 274  To change the overheating protection parameters of BMS Logic devices, select the "Protections → High Logic temperature" section:
275 275  
... ... @@ -388,7 +388,7 @@
388 388  
389 389  To change the protection parameters from short circuit, select the "Protections → Short circuit" section:
390 390  
391 -[[image:1733328415733-309.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="210" width="800"]]
400 +[[image:1735224667621-969.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="153" width="800"]]
392 392  
393 393  In this section:
394 394  
... ... @@ -396,8 +396,6 @@
396 396  ** Enable – a flag to enable the protection;
397 397  ** Maximum current, A;
398 398  ** Delay before setting the error, second;
399 -* Switch off the charging contactor on error – a flag to open the charging contactor when the "Short circuit" error occurs;
400 -* Switch off the discharging contactor on error – a flag to open the discharging contactor when the "Short circuit" error occurs;
401 401  * Delay before clearing the error, second;
402 402  * Lock – a flag to block the error until the device is restarted.
403 403  
... ... @@ -422,7 +422,7 @@
422 422  
423 423  To change the overheating protection parameters of power contactors, select the "Protections → High contactor temperature" section:
424 424  
425 -[[image:1733328415734-986.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
432 +[[image:1735224706573-347.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="112" width="800"]]
426 426  
427 427  In this section:
428 428  
... ... @@ -431,8 +431,6 @@
431 431  * Maximum contactor temperature, °C;
432 432  * Tolerant contactor temperature, °C;
433 433  * Delay before setting the error, second;
434 -* Switch off the charging contactor on error – a flag to open the charging contactor when the "High contactor temperature" error occurs;
435 -* Switch off the discharging contactor on error – a flag to open the discharging contactor when the "High contactor temperature" error occurs;
436 436  * Delay before clearing the error, second;
437 437  * Lock – a flag to block the error until the device is restarted.
438 438  
... ... @@ -503,6 +503,10 @@
503 503  If there is the "Power switch error", the **“Critical error” **is generated and **all relays open.**
504 504  )))
505 505  
511 +=== Power fault ===
512 +
513 +TBA
514 +
506 506  === Charge contactor cycles ===
507 507  
508 508  The BMS Main 3 device protects the charging contactor against frequent switching.
... ... @@ -724,14 +724,18 @@
724 724  
725 725  To change the HVIL measurement parameters, select the "Protections → HVIL" section:
726 726  
727 -[[image:1733328487099-371.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="85" width="800"]]
736 +[[image:1735224839441-185.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="102" width="800"]]
728 728  
729 729  In this section:
730 730  
731 731  * Enable – a flag to enable the protection;
741 +* Source is OFF: Lower current limit, A;
742 +* Source is OFF: Upper current limit, A;
743 +* Source is ON: Lower current limit, A;
744 +* Source is ON: Upper current limit, A;
732 732  * Lock – a flag to block the error until the device is restarted.
733 733  
734 -If interlock loop breaks, the “HVIL error” is generated. Error clears if interlock loop is being restored.
747 +If interlock loop breaks and its current is out of the configured ranges, the “HVIL error” is generated. Error clears if interlock loop is being restored.
735 735  
736 736  (% class="box warningmessage" %)
737 737  (((
... ... @@ -787,7 +787,7 @@
787 787  
788 788  To change the general error parameters, select the "Protections → Critical error" section:
789 789  
790 -[[image:1733328487101-216.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="262" width="800"]]
803 +[[image:1735224942262-497.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="102" width="800"]]
791 791  
792 792  In this section:
793 793  
... ... @@ -795,7 +795,7 @@
795 795  * Delay before setting the error, millisecond;
796 796  * Delay before clearing the error, second;
797 797  * Lock – a flag to block the error until the device is restarted;
798 -* Check: <error> a flags to enable check of corresponding errors.
811 +* Errors 1, 2 to set the "Critical errorbitfields to enable check of corresponding errors.
799 799  
800 800  The general error flag is generated if at least one of the enabled errors is generated during the “Delay before setting the error” time.
801 801  
1735224224155-829.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +23.4 KB
Content
1735224377252-473.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +23.4 KB
Content
1735224601506-488.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +24.6 KB
Content
1735224667621-969.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +32.8 KB
Content
1735224706573-347.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +22.1 KB
Content
1735224839441-185.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +20.1 KB
Content
1735224942262-497.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +19.9 KB
Content