Changes for page 3.4 Protections
Last modified by Admin on 2026/04/01 08:42
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -231,7 +231,7 @@ 231 231 * **Enable** – a flag to enable the protection; 232 232 * **Delay before setting the error**, millisecond; 233 233 * **Delay before clearing the error**, second; 234 -* **Lock **– Lock .234 +* **Lock **– a flag to block the error until the device is restarted. 235 235 236 236 As a result of the operation of the protection against opening the battery cover, the “Battery cover error” is generated. 237 237 ... ... @@ -263,7 +263,7 @@ 263 263 * **Tolerant humidity**, RH%; 264 264 * **Delay before setting the error**, second; 265 265 * **Delay before clearing the error**, second; 266 -* **Lock **– lock the error until the device is res et.266 +* **Lock **– a flag to block the error until the device is restarted. 267 267 268 268 As a result of the operation of the battery protection from high humidity, the "High humidity" error is generated. 269 269 ... ... @@ -290,12 +290,12 @@ 290 290 291 291 In this section: 292 292 293 -* Enable – a flag to enable the protection;294 -* Maximum humidity, RH%; 295 -* Tolerant humidity, RH%; 296 -* Delay before setting the error, second; 297 -* Delay before clearing the error, second; 298 -* Lock – lock the error until the device is reset. 293 +* **Enable **– a flag to enable the protection; 294 +* **Maximum humidity**, RH%; 295 +* **Tolerant humidity**, RH%; 296 +* **Delay before setting the error**, second; 297 +* **Delay before clearing the error**, second; 298 +* **Lock **– lock the error until the device is reset. 299 299 300 300 As a result of the operation of the battery protection from water, the "Water" error is generated. 301 301 ... ... @@ -320,12 +320,12 @@ 320 320 321 321 In this section: 322 322 323 -* Enable – a flag to enable the protection; 324 -* Maximum temperature, °C; 325 -* Tolerant temperature, °C; 326 -* Delay before setting the error, second; 327 -* Delay before clearing the error, second; 328 -* Lock – lock the error until the device is reset. 323 +* **Enable **– a flag to enable the protection; 324 +* **Maximum temperature**, °C; 325 +* **Tolerant temperature**, °C; 326 +* **Delay before setting the error**, second; 327 +* **Delay before clearing the error**, second; 328 +* **Lock **– lock the error until the device is reset. 329 329 330 330 As a result of the operation of the protection from high temperatures of BMS Logic devices, the "High Logic temperature" is generated. 331 331 ... ... @@ -351,10 +351,10 @@ 351 351 352 352 In this section: 353 353 354 -* Enable – a flag to enable the protection; 355 -* Delay before setting the error, second; 356 -* Delay before clearing the error, second; 357 -* Lock – lock the error until the device is reset. 354 +* **Enable **– a flag to enable the protection; 355 +* **Delay before setting the error**, second; 356 +* **Delay before clearing the error**, second; 357 +* **Lock **– lock the error until the device is reset. 358 358 359 359 As a result of the protection from loss of communication with BMS Logic devices, the "Logic offline" error is generated. 360 360 ... ... @@ -379,11 +379,11 @@ 379 379 380 380 In this section: 381 381 382 -* Enable – a flag to enable the protection; 383 -* Number of cells – a number of cells connected to the BMS; 384 -* Delay before setting the error, millisecond; 385 -* Delay before clearing the error, second; 386 -* Lock – a flag to block the error until the device is restarted. 382 +* **Enable** – a flag to enable the protection; 383 +* **Number of cells** – a number of cells connected to the BMS; 384 +* **Delay before setting the error**, millisecond; 385 +* **Delay before clearing the error**, second; 386 +* **Lock **– a flag to block the error until the device is restarted. 387 387 388 388 As a result of the operation of the protection from the mismatch of the number of cells, the "Cell count error" is generated. 389 389 ... ... @@ -408,11 +408,11 @@ 408 408 409 409 In this section: 410 410 411 -* Enable – a flag to enable the protection; 412 -* Number of cells – a number of temperature sensors connected to the BMS; 413 -* Delay before setting the error, millisecond; 414 -* Delay before clearing the error, second; 415 -* Lock – a flag to block the error until the device is restarted. 411 +* **Enable **– a flag to enable the protection; 412 +* **Number of cells** – a number of temperature sensors connected to the BMS; 413 +* **Delay before setting the error**, millisecond; 414 +* **Delay before clearing the error**, second; 415 +* **Lock **– a flag to block the error until the device is restarted. 416 416 417 417 As a result of the operation of the protection from the mismatch of the number of cells, the "T-sensor count error" is generated. 418 418 ... ... @@ -437,12 +437,12 @@ 437 437 438 438 In this section: 439 439 440 -* Enable – a flag to enable the protection; 441 -* Logic count – a number of BMS Logic devices connected to the BMS Main; 442 -* Scan fast – a flag to scan BMS Logic devices fast (devices with addresses from 1 to “Logic count” are scanned; this mode reduces BMS system startup time); 443 -* Delay before setting the error – a delay before setting the error //during initialization//, millisecond; 444 -* Delay before clearing the error– a delay before clearing the error //during initialization//, second; 445 -* Lock – lock the error until the device is reset. 440 +* **Enable **– a flag to enable the protection; 441 +* **Logic count** – a number of BMS Logic devices connected to the BMS Main; 442 +* **Scan fast** – a flag to scan BMS Logic devices fast (devices with addresses from 1 to “Logic count” are scanned; this mode reduces BMS system startup time); 443 +* **Delay before setting the error** – a delay before setting the error //during initialization//, millisecond; 444 +* **Delay before clearing the error **– a delay before clearing the error //during initialization//, second; 445 +* **Lock** – lock the error until the device is reset. 446 446 447 447 As a result of the operation of the protection from the mismatch of the number of BMS Logic devices, the "Logic count error" is generated. 448 448 ... ... @@ -471,12 +471,12 @@ 471 471 472 472 In this section: 473 473 474 -* Level 1, 2, 3 – three protection levels. The following parameters are configured at each level: 475 -** Enable – a flag to enable the protection; 476 -** Maximum current, A; 477 -** Delay before setting the error, second; 478 -* Delay before clearing the error, second; 479 -* Lock – a flag to block the error until the device is restarted. 474 +* **Level 1, 2, 3** – three protection levels. The following parameters are configured at each level: 475 +** **Enable **– a flag to enable the protection; 476 +** **Maximum current**, A; 477 +** **Delay before setting the error**, second; 478 +* **Delay before clearing the error**, second; 479 +* **Lock **– a flag to block the error until the device is restarted. 480 480 481 481 If there is a short circuit, the "Short circuit" error is generated. 482 482 ... ... @@ -498,13 +498,13 @@ 498 498 499 499 In this section: 500 500 501 -* Enable – a flag to enable the protection; 502 -* Thermistor – a selection of which cell thermistor will be used as contactor temperature sensor; 503 -* Maximum contactor temperature, °C; 504 -* Tolerant contactor temperature, °C; 505 -* Delay before setting the error, second; 506 -* Delay before clearing the error, second; 507 -* Lock – a flag to block the error until the device is restarted. 501 +* **Enable** – a flag to enable the protection; 502 +* **Thermistor **– a selection of which cell thermistor will be used as contactor temperature sensor; 503 +* **Maximum contactor temperature**, °C; 504 +* **Tolerant contactor temperature**, °C; 505 +* **Delay before setting the error**, second; 506 +* **Delay before clearing the error**, second; 507 +* **Lock **– a flag to block the error until the device is restarted. 508 508 509 509 If there is a contactor overheat, the "High contactor temperature" error is generated. 510 510 ... ... @@ -526,13 +526,13 @@ 526 526 527 527 In this section: 528 528 529 -* Enable – a flag to enable the protection; 530 -* Maximum voltage, V; 531 -* Minimum voltage, V; 532 -* Voltage hysteresis – a hysteresis value to clear the error, V; 533 -* Delay before setting the error, second; 534 -* Delay before clearing the error, second; 535 -* Lock – a flag to block the error until the device is restarted. 529 +* **Enable **– a flag to enable the protection; 530 +* **Maximum voltage**, V; 531 +* **Minimum voltage**, V; 532 +* **Voltage hysteresis** – a hysteresis value to clear the error, V; 533 +* **Delay before setting the error**, second; 534 +* **Delay before clearing the error**, second; 535 +* **Lock **– a flag to block the error until the device is restarted. 536 536 537 537 If there is an open or short circuit connection of a current sensor, the "Current sensor error" is generated. 538 538 ... ... @@ -552,13 +552,18 @@ 552 552 553 553 === Power switch === 554 554 555 -BMS Main 3 / BMS Main 2R device checks the status of power switches that are used to control the contactors. To change the parameters of the power switch protection, select the "Protections → Power switch" section: 555 +(% class="box warningmessage" %) 556 +((( 557 +This section is not available on BMS Main 2R. 558 +))) 556 556 560 +BMS Main 3 device checks the status of power switches that are used to control the contactors. To change the parameters of the power switch protection, select the "Protections → Power switch" section: 561 + 557 557 [[image:1733328461554-241.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="99" width="800"]] 558 558 559 559 In this section: 560 560 561 -* Delay before clearing the error, second; 566 +* **Delay before clearing the error**, second; 562 562 * Lock – a flag to block the error until the device is restarted. 563 563 564 564 The “Power switch error” occurs when the device detects a shortage in contactor coil control circuit or an overheating of the power switch. Error is removed when the temperature of power switch is normal during “Delay before clearing the error” time. ... ... @@ -570,8 +570,13 @@ 570 570 571 571 === Power fault === 572 572 573 -BMS Main 3 / BMS Main 2R device checks the status of CAN2, CAN3, RS-485-2 and Current sensors power supply. 578 +(% class="box warningmessage" %) 579 +((( 580 +This section is not available on BMS Main 2R. 581 +))) 574 574 583 +BMS Main 3 device checks the status of CAN2, CAN3, RS-485-2 and Current sensors power supply. 584 + 575 575 (% class="box infomessage" %) 576 576 ((( 577 577 **Note:** this error can be configured only under** "Service" account**.