... ... @@ -92,12 +92,12 @@
92 92  In this section:
93 93  
94 94  * **Enable **– a flag to enable the protection;
95 -* Minimum cell voltage, V;
96 -* Tolerant cell voltage, V;
97 -* Check the open circuit voltage instead of the actual voltage – a flag to use the U,,ocv,, (corrected due to current and cell resistance) cell voltage;
98 -* Delay before setting the error, millisecond;
99 -* Delay before clearing the error, second;
100 -* Lock – a flag to block the error until the device is restarted.
95 +* **Minimum cell voltage**, V;
96 +* **Tolerant cell voltage**, V;
97 +* **Check the open circuit voltage instead of the actual voltage** – a flag to use the U,,ocv,, (corrected due to current and cell resistance) cell voltage;
98 +* **Delay before setting the error**, millisecond;
99 +* **Delay before clearing the error**, second;
100 +* **Lock **– a flag to block the error until the device is restarted.
101 101  
102 102  As a result of the operation of battery protection from low voltage, the "Undervoltage" error is generated.
103 103  
... ... @@ -119,13 +119,13 @@
119 119  
120 120  In this section:
121 121  
122 -* Enable – a flag to enable the protection;
123 -* Maximum cell voltage, V;
124 -* Tolerant cell voltage, V;
125 -* Check the open circuit voltage instead of the actual voltage – a flag to use the U,,ocv,, (corrected due to current and cell resistance) cell voltage;
126 -* Delay before setting the error, millisecond;
127 -* Delay before clearing the error, second;
128 -* Lock – a flag to block the error until the device is restarted.
122 +* **Enable **– a flag to enable the protection;
123 +* **Maximum cell voltage**, V;
124 +* **Tolerant cell voltage**, V;
125 +* **Check the open circuit voltage instead of the actual voltage** – a flag to use the U,,ocv,, (corrected due to current and cell resistance) cell voltage;
126 +* **Delay before setting the error**, millisecond;
127 +* **Delay before clearing the error**, second;
128 +* **Lock **– a flag to block the error until the device is restarted.
129 129  
130 130  As a result of the operation of the battery protection from high voltage, the "Overvoltage" error is generated.
131 131  
... ... @@ -145,12 +145,12 @@
145 145  
146 146  [[image:1760437465709-702.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="133" width="800"]]In this section:
147 147  
148 -* Enable – a flag to enable the protection;
149 -* Maximum cell imbalance, V;
150 -* Tolerant cell imbalance, V;
151 -* Delay before setting the error, millisecond;
152 -* Delay before clearing the error, second;
153 -* Lock – a flag to block the error until the device is restarted.
148 +* **Enable **– a flag to enable the protection;
149 +* **Maximum cell imbalance**, V;
150 +* **Tolerant cell imbalance**, V;
151 +* **Delay before setting the error**, millisecond;
152 +* **Delay before clearing the error**, second;
153 +* **Lock **– a flag to block the error until the device is restarted.
154 154  
155 155  As a result of the operation of the battery protection from cell imbalance, the "Cell imbalance” error is generated.
156 156  
... ... @@ -172,14 +172,14 @@
172 172  
173 173  In this section:
174 174  
175 -* Enable – a flag to enable the protection;
176 -* Minimum charge temperature, °C;
177 -* Tolerant charge temperature, °C;
178 -* Minimum discharge temperature, °C;
179 -* Tolerant discharge temperature, °C;
180 -* Delay before setting the error, millisecond;
181 -* Delay before clearing the error, second;
182 -* Lock – a flag to block the error until the device is restarted.
175 +* **Enable **– a flag to enable the protection;
176 +* **Minimum charge temperature**, °C;
177 +* **Tolerant charge temperature**, °C;
178 +* **Minimum discharge temperature**, °C;
179 +* **Tolerant discharge temperature**, °C;
180 +* **Delay before setting the error**, millisecond;
181 +* **Delay before clearing the error**, second;
182 +* **Lock **– a flag to block the error until the device is restarted.
183 183  
184 184  As a result of the operation of the battery protection from low temperature, the "Low temperature (CH)" and/or “Low temperature (DCH)” error are generated.
185 185  
... ... @@ -201,14 +201,14 @@
201 201  
202 202  In this section:
203 203  
204 -* Enable – a flag to enable the protection;
205 -* Maximum charge temperature, °C;
206 -* Tolerant charge temperature, °C;
207 -* Maximum discharge temperature, °C;
208 -* Tolerant discharge temperature, °C;
209 -* Delay before setting the error, millisecond;
210 -* Delay before clearing the error, second;
211 -* Lock – a flag to block the error until the device is restarted.
204 +* **Enable **– a flag to enable the protection;
205 +* **Maximum charge temperature**, °C;
206 +* **Tolerant charge temperature**, °C;
207 +* **Maximum discharge temperature**, °C;
208 +* **Tolerant discharge temperature**, °C;
209 +* **Delay before setting the error**, millisecond;
210 +* **Delay before clearing the error**, second;
211 +* **Lock **– a flag to block the error until the device is restarted.
212 212  
213 213  As a result of the operation of the battery protection from high temperature, the "High temperature (CH)" or “High temperature (DCH)” error is generated.
214 214  
... ... @@ -228,10 +228,10 @@
228 228  
229 229  In this section:
230 230  
231 -* Enable – a flag to enable the protection;
232 -* Delay before setting the error, millisecond;
233 -* Delay before clearing the error, second;
234 -* Lock – a flag to block the error until the device is restarted.
231 +* **Enable** – a flag to enable the protection;
232 +* **Delay before setting the error**, millisecond;
233 +* **Delay before clearing the error**, second;
234 +* **Lock **Lock .
235 235  
236 236  As a result of the operation of the protection against opening the battery cover, the “Battery cover error” is generated.
237 237  
... ... @@ -258,12 +258,12 @@
258 258  
259 259  In this section:
260 260  
261 -* Enable – a flag to enable the detection;
262 -* Maximum humidity, RH%;
263 -* Tolerant humidity, RH%;
264 -* Delay before setting the error, second;
265 -* Delay before clearing the error, second;
266 -* Lock the error until the device is reset.
261 +* **Enable **– a flag to enable the detection;
262 +* **Maximum humidity**, RH%;
263 +* **Tolerant humidity**, RH%;
264 +* **Delay before setting the error**, second;
265 +* **Delay before clearing the error**, second;
266 +* **Lock **– lock the error until the device is reset.