... ... @@ -448,13 +448,11 @@
448 448  
449 449  Error generation conditions:
450 450  
451 -* during the initialization BMS Main 3 have not found required number of BMS Logic devices during the "Delay before setting the error" time;
452 452  * after the initialization the number of BMS Logic devices connected to the BMS Main is **not equal** to the “Logic count” value.
453 453  
454 454  Conditions for removing the error:
455 455  
456 -* during the initialization BMS Main 3 have found required number of BMS Logic devices and the "Delay before setting the error" time has passed;
457 -* after the initialization the number of BMS Logic devices connected to the BMS Main is **equal** to the “Logic count” value.
455 +* the number of BMS Logic devices connected to the BMS Main is **equal** to the “Logic count” value.
458 458  
459 459  (% class="box warningmessage" %)
460 460  (((