Changes for page 3.4 Protections

Last modified by Admin on 2025/11/06 10:39

From version 47.1
edited by Admin
on 2025/11/06 10:39
Change comment: There is no comment for this version
To version 45.1
edited by Admin
on 2025/11/06 10:36
Change comment: Загрузить новое вложение 1762425390154-843.png

Summary

Details

Page properties
Content
... ... @@ -433,7 +433,7 @@
433 433  
434 434  To change the protection parameters from the mismatch of the number of BMS Logic devices to the set value, select the "Protections → Logic count” section:
435 435  
436 -[[image:1762425434368-516.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="125" width="800"]]
436 +[[image:1733328415732-163.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="110" width="800"]]
437 437  
438 438  In this section:
439 439  
... ... @@ -440,8 +440,6 @@
440 440  * Enable – a flag to enable the protection;
441 441  * Logic count – a number of BMS Logic devices connected to the BMS Main;
442 442  * Scan fast – a flag to scan BMS Logic devices fast (devices with addresses from 1 to “Logic count” are scanned; this mode reduces BMS system startup time);
443 -* Delay before setting the error – a delay before setting the error //during initialization//, millisecond;
444 -* Delay before clearing the error– a delay before clearing the error //during initialization//, second;
445 445  * Lock – lock the error until the device is reset.
446 446  
447 447  As a result of the operation of the protection from the mismatch of the number of BMS Logic devices, the "Logic count error" is generated.
... ... @@ -448,13 +448,11 @@
448 448  
449 449  Error generation conditions:
450 450  
451 -* during the initialization BMS Main 3 have not found required number of BMS Logic devices during the "Delay before setting the error" time;
452 -* after the initialization the number of BMS Logic devices connected to the BMS Main is **not equal** to the “Logic count” value.
449 +* the number of BMS Logic devices connected to the BMS Main is **not equal** to the “Logic count” value.
453 453  
454 454  Conditions for removing the error:
455 455  
456 -* during the initialization BMS Main 3 have found required number of BMS Logic devices and the "Delay before setting the error" time has passed;
457 -* after the initialization the number of BMS Logic devices connected to the BMS Main is **equal** to the “Logic count” value.
453 +* the number of BMS Logic devices connected to the BMS Main is **equal** to the “Logic count” value.
458 458  
459 459  (% class="box warningmessage" %)
460 460  (((
1762425434368-516.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -19.8 KB
Content