... ... @@ -152,15 +152,15 @@
152 152  * Delay before clearing the error, second;
153 153  * Lock – a flag to block the error until the device is restarted.
154 154  
155 -As a result of the operation of the battery protection from cell imbalance, the "Cell im” error are generated.
155 +As a result of the operation of the battery protection from cell imbalance, the "Cell imbalance” error is generated.
156 156  
157 157  Error generation conditions:
158 158  
159 -* the minimum temperature among all cells of the battery is less than the “Minimum charging (discharging) temperature” value for the “Delay before setting the error” time.
159 +* the voltage difference between the most charged cell and the least charged cell is more than the “Maximum cell imbalance” value for the “Delay before setting the error” time.
160 160  
161 161  Conditions for removing the error:
162 162  
163 -* the minimum temperature among all cells of the battery is greater than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
163 +* the voltage difference between the most charged cell and the least charged cell is less than the “Tolerant cell imbalance” value for the “Delay before clearing the error” time.
164 164  
165 165  === Low temperature ===
166 166  
... ... @@ -433,7 +433,7 @@
433 433  
434 434  To change the protection parameters from the mismatch of the number of BMS Logic devices to the set value, select the "Protections → Logic count” section:
435 435  
436 -[[image:1733328415732-163.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="110" width="800"]]
436 +[[image:1762425434368-516.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="125" width="800"]]
437 437  
438 438  In this section:
439 439  
... ... @@ -440,6 +440,8 @@
440 440  * Enable – a flag to enable the protection;
441 441  * Logic count – a number of BMS Logic devices connected to the BMS Main;
442 442  * Scan fast – a flag to scan BMS Logic devices fast (devices with addresses from 1 to “Logic count” are scanned; this mode reduces BMS system startup time);
443 +* Delay before setting the error – a delay before setting the error //during initialization//, millisecond;
444 +* Delay before clearing the error– a delay before clearing the error //during initialization//, second;
443 443  * Lock – lock the error until the device is reset.
444 444  
445 445  As a result of the operation of the protection from the mismatch of the number of BMS Logic devices, the "Logic count error" is generated.
... ... @@ -446,7 +446,7 @@
446 446  
447 447  Error generation conditions:
448 448  
449 -* the number of BMS Logic devices connected to the BMS Main is **not equal** to the “Logic count” value.
451 +* after the initialization the number of BMS Logic devices connected to the BMS Main is **not equal** to the “Logic count” value.
450 450  