... ... @@ -137,6 +137,12 @@
137 137  
138 138  * the maximum voltage among all cells of the battery is less than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
139 139  
140 +=== Cell imbalance ===
141 +
142 +The BMS Main 3 device implements battery protection from too much cell imbalance. If balancing algorithm is not enough to compensate battery imbalance, then imbalance protection generates an error
143 +
144 +To change the battery protection parameters from low temperature, select the "Protections → Low temperature" section:
145 +
140 140  === Low temperature ===
141 141  
142 142  The BMS Main 3 device implements battery protection from too low temperature.
... ... @@ -321,11 +321,14 @@
321 321  
322 322  To change the protection parameters from loss of communication with BMS Logic devices, select the "Protections → Logic offline" section:
323 323  
324 -[[image:1733328399416-818.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="86" width="800"]]
330 +[[image:1755871522789-489.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="102" width="800"]]
325 325  
332 +
326 326  In this section:
327 327  
328 328  * Enable – a flag to enable the protection;
336 +* Delay before setting the error, second;
337 +* Delay before clearing the error, second;
329 329  * Lock – lock the error until the device is reset.
330 330  
331 331  As a result of the protection from loss of communication with BMS Logic devices, the "Logic offline" error is generated.
... ... @@ -372,6 +372,35 @@
372 372  If there is the "Cell count error", the **“Critical error” **is generated**.**
373 373  )))
374 374  
384 +=== Temperature sensor count ===
385 +
386 +To change the protection parameters from the mismatch of the number of temperature sensors to the set value, select the "Protections → Temperature sensor count" section:
387 +
388 +[[image:1755871582533-550.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="123" width="800"]]
389 +
390 +In this section:
391 +
392 +* Enable – a flag to enable the protection;
393 +* Number of cells – a number of temperature sensors connected to the BMS;
394 +* Delay before setting the error, millisecond;
395 +* Delay before clearing the error, second;
396 +* Lock – a flag to block the error until the device is restarted.
397 +
398 +As a result of the operation of the protection from the mismatch of the number of cells, the "T-sensor count error" is generated.
399 +
400 +Error generation conditions:
401 +
402 +* the number of temperature sensors connected to the BMS is **not equal** to the “Number of temperature sensors” value during the “Delay before setting the error” time.
403 +
404 +Conditions for removing the error:
405 +
406 +* the number of temperature sensors connected to the BMS is **equal** to the “Number of temperature sensors” value during the “Delay before clearing the error” time.
407 +
408 +(% class="box warningmessage" %)
409 +(((
410 +If there is the "T-sensor count error", the **“Critical error” **is generated**.**
411 +)))
412 +
375 375  === Logic count ===
376 376  
377 377  To change the protection parameters from the mismatch of the number of BMS Logic devices to the set value, select the "Protections → Logic count” section:
... ... @@ -763,6 +763,37 @@
763 763  If there is the “HVIL error”, the **“Critical error”** is generated.
764 764  )))
765 765  
804 +=== Battery voltage ===
805 +
806 +The BMS Main 3 allows to control the difference between sum of all cell voltages and voltage measured before the contactors.
807 +
808 +To change the voltage difference check parameters, select the "Protections → Battery voltage" section:
809 +
810 +[[image:1755871661259-633.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="100" width="800"]]
811 +
812 +In this section:
813 +
814 +* Enable – a flag to enable the protection;
815 +* Abnormal voltage difference – a maximum difference between sum of all cell voltages and voltage measured before the contactors (High voltage 1), V;
816 +* Delay before setting the error, second;
817 +* Delay before clearing the error, second;
818 +* Lock – a flag to block the error until the device is restarted.
819 +
820 +If there is a mismatch between voltages, "Battery voltage mismatch" error is generated.
821 +
822 +Error generation conditions:
823 +
824 +* difference between sum of all cell voltages and voltage measured before the contactors is **more **than "Abnormal voltage difference" value during "Delay before setting the error" time.
825 +
826 +Conditions for removing the error:
827 +
828 +* difference between sum of all cell voltages and voltage measured before the contactors is **less **than "Abnormal voltage difference" value during "Delay before clearing the error" time.
829 +
830 +(% class="box warningmessage" %)
831 +(((
832 +If there is the “Battery voltage mismatch” error, the **“Critical error”** is generated.
833 +)))
834 +
766 766  === Critical error ===
767 767  
768 768  Some of the errors are system critical. A separate signal named "Critical error" indicates a BMS fault.
1755871582533-550.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +17.2 KB
Content
1755871661259-633.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +20.5 KB
Content
1760434646517-885.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +21.4 KB
Content
1760436309214-414.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +19.4 KB
Content
1760437465709-702.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +19.4 KB
Content