... ... @@ -44,9 +44,9 @@
44 44  
45 45  === Charge current limit ===
46 46  
47 -The BMS Main 3 device can check if the charging current exceeds the estimated limit based on the [[Charge map>>doc:Battery management systems.BMS Main 3.3\. Configuration.3\.3 Control.WebHome||anchor="HChargemap"]].  If current exceeds the calculated limit more than configured difference, "Current limit" error is generated.
47 +The BMS Main 3 device can check if the charging current exceeds the estimated limit based on the [[Charge map>>doc:Battery management systems.BMS Main 3.3\. Configuration.3\.3 Control.WebHome||anchor="HChargemap"]]. If current exceeds the calculated limit more than configured difference, "Current limit" error is generated.
48 48  
49 -Current difference is configured by two regions separated by the threshold value. Maximum current in Region 1 is calculated by the absolute difference, in Region 2 – by the relative difference.
49 +Current difference is separated to two regions by the threshold value. Maximum current in Region 1 is calculated by the absolute difference, in Region 2 – by the relative difference.
50 50  
51 51  To change the overcurrent protection of the battery, select the "Protections → Charge current limit" section:
52 52  
... ... @@ -53,18 +53,25 @@
53 53  [[image:1735225207687-430.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="113" width="800"]]In this section:
54 54  
55 55  * Enable – a flag to enable the protection;
56 -* Threshold to switch from Region 1 to Region 2
56 +* Threshold to switch from Region 1 to Region 2 – a current value at which
57 57  *
58 58  
59 59  
60 60  === Discharge current limit ===
61 61  
62 -The BMS Main 3 device can check if the charging current exceeds the estimated limit based on the [[Charge map>>doc:Battery management systems.BMS Main 3.3\. Configuration.3\.3 Control.WebHome||anchor="HChargemap"]].  If current exceeds the calculated limit more than configured difference, "Current limit" error is generated.
62 +The BMS Main 3 device can check if the discharging current exceeds the estimated limit based on the [[Discharge map>>doc:Battery management systems.BMS Main 3.3\. Configuration.3\.3 Control.WebHome||anchor="HDischargemap"]]. If current exceeds the calculated limit more than configured difference, "Current limit" error is generated.
63 63  
64 -Current difference is configured by two regions separated by the threshold value. Maximum current in Region 1 is calculated by the absolute difference, in Region 2 – by the relative difference.
64 +Current difference is separated to two regions by the threshold value. Maximum current in Region 1 is calculated by the absolute difference, in Region 2 – by the relative difference.
65 65  
66 -To change the overcurrent protection of the battery, select the "Protections → Charge current limit" section:
66 +To change the overcurrent protection of the battery, select the "Protections → Discharge current limit" section:
67 67  
68 +[[image:1735225942893-869.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="113" width="800"]]
69 +
70 +In this section:
71 +
72 +* Enable – a flag to enable the protection;
73 +* Threshold to switch from Region 1 to Region 2
74 +
68 68  === Undervoltage ===
69 69  
70 70  The BMS Main 3 device implements battery protection from too low voltage on the cells.