Changes for page 3.4 Protections

Last modified by Admin on 2025/04/09 12:19

From version 16.18
edited by Admin
on 2024/12/26 15:05
Change comment: There is no comment for this version
To version 16.20
edited by Admin
on 2024/12/26 15:07
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -44,8 +44,9 @@
44 44  
45 45  === Charge current limit ===
46 46  
47 -The BMS Main 3 device can check if the charging current exceeds the estimated limit based on the Charge map . If current is more than calculated maximum, "Current limit" error is generated.
47 +The BMS Main 3 device can check if the charging current exceeds the estimated limit based on the [[Charge map>>doc:Battery management systems.BMS Main 3.3\. Configuration.3\.3 Control.WebHome||anchor="HChargemap"]].  If current exeeds than calculated limit , "Current limit" error is generated.
48 48  
49 +Two regions of current
49 49  
50 50  To change the overcurrent protection of the battery, select the "Protections → Charge current limit" section:
51 51