Wiki source code of 1. Technical specifications
Last modified by Admin on 2025/05/28 17:04
Show last authors
author | version | line-number | content |
---|---|---|---|
1 | (% data-numbered-headings-start="1" style="--numbered-headings-start: 0;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %) | ||
2 | = Technical specifications = | ||
3 | |||
4 | [[image:https://movicomelectric.com/wa-data/public/site/img/08-BMS-Main-2-1.png||alt="BMS Main 2.1" data-xwiki-image-style-alignment="center" height="266" width="408"]] | ||
5 | |||
6 | BMS Main 2.1 is a modular BMS controller for 24-1200V batteries. It interacts with measuring modules, calculates the battery state, and protects the battery from damage. | ||
7 | |||
8 | BMS based on the Main 2.1 can control up to 23 measuring modules and manage a battery consisting of 414 cells. | ||
9 | |||
10 | == Specifications == | ||
11 | |||
12 | (% style="width:705px" %) | ||
13 | |(% style="width:434px" %)**Parameter**|(% style="width:267px" %)**Value** | ||
14 | |(% style="width:434px" %)Supply voltage, V|(% style="width:267px" %)9 to 30 | ||
15 | |(% style="width:434px" %)Current consumption @12 V, mA (max)|(% style="width:267px" %)100 | ||
16 | |Number of BMS Logic devices|1 to 23 | ||
17 | |Number of cells (maximum)|414 | ||
18 | |(% style="width:434px" %)Number of programmable solid-state relays for contactors (55V, 3A)|(% style="width:267px" %)4 | ||
19 | |(% style="width:434px" %)Number of programmable discrete inputs (dry contact)|(% style="width:267px" %)4 | ||
20 | |(% style="width:434px" %)Number of programmable discrete outputs (+5V, total 200mA)|(% style="width:267px" %)4 | ||
21 | |(% style="width:434px" %)Current sensor type|(% style="width:267px" %)((( | ||
22 | Hall-Effect sensor, bidirectional, supply voltage 5 V (LEM series HASS, HTFS) | ||
23 | ))) | ||
24 | |(% style="width:434px" %)Current sensor signal measurement error, V (maximum)|(% style="width:267px" %)± 0.001 | ||
25 | |(% style="width:434px" %)Number of CAN interfaces|(% style="width:267px" %)1 | ||
26 | |(% style="width:434px" %)CAN bus speed, kbps|(% style="width:267px" %)125, 250 (by default), 500, 1000 | ||
27 | |(% style="width:434px" %)Number of RS-485 interfaces|(% style="width:267px" %)2 | ||
28 | |(% style="width:434px" %)RS-485 baud rate, bps|(% style="width:267px" %)600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200 | ||
29 | |(% style="width:434px" %)CAN output voltage, V|(% style="width:267px" %)5.0 ± 0.5 | ||
30 | |(% style="width:434px" %)CAN output current, mA (maximum)|(% style="width:267px" %)400 | ||
31 | |(% style="width:434px" %)Number of Ethernet interfaces|(% style="width:267px" %)1 | ||
32 | |(% style="width:434px" %)Ethernet speed, Mbps|(% style="width:267px" %)10/100 | ||
33 | |(% style="width:434px" %)Dimensions (length × width × height), mm|(% style="width:267px" %)120 × 120 × 17 | ||
34 | |(% style="width:434px" %)Weight, g|(% style="width:267px" %)100 ± 10 | ||
35 | |(% style="width:434px" %)Operating temperature range, °С|(% style="width:267px" %)-40 to +85 | ||
36 | |(% style="width:434px" %)The degree of protection from external influences|(% style="width:267px" %)IP00 | ||
37 | |Headers P1, P6-P9 type |Molex series Mini-Fit | ||
38 | |Headers P11-P15 type |Molex series Micro-Fit | ||
39 | |||
40 | == Overall and mounting dimensions == | ||
41 | |||
42 | |||
43 | [[image:1747230403731-923.png||data-xwiki-image-style-alignment="center" height="546" width="450"]] | ||
44 | |||
45 |