Wiki source code of 1. General information
Show last authors
author | version | line-number | content |
---|---|---|---|
1 | [[image:https://movicomelectric.com/wa-data/public/site/img/08-BMS-Main-2-1.png||alt="BMS Main 2.1" data-xwiki-image-style-alignment="center" height="266" width="408"]] | ||
2 | |||
3 | The BMS Main 2.1 is a controller of the modular battery management system that has the following features: | ||
4 | |||
5 | * measuring current flowing through the battery; | ||
6 | * communication with BMS Logic that measure voltage and temperature of the battery cells; | ||
7 | * management of charging and discharging the battery; | ||
8 | * management of balancing the battery cells; | ||
9 | * protection of the battery from damage caused by current, voltage, temperature, etc.; | ||
10 | * communication with external equipment (chargers, inverters, indication panels) to provide needed battery operation mode; | ||
11 | * communication with external systems over Ethernet, CAN, RS-485, Wi-Fi; | ||
12 | * collecting and storing battery history data on an SD card. | ||
13 | |||
14 | The BMS Main 2.1 is used solely in civil areas. It does not use encryption and cryptography. | ||
15 | |||
16 | The BMS Main 2.1 is a part of Movicom Electric BMS, a modular battery management system, and controls the following devices: | ||
17 | |||
18 | * //BMS Logic 2.0//; | ||
19 | * //BMS Logic 12//; | ||
20 | * //BMS Logic 18//; | ||
21 | * //BMS Logic RET//. | ||
22 | |||
23 | = 1.1 Specifications = | ||
24 | |||
25 | (% style="width:705px" %) | ||
26 | |(% style="width:434px" %)**Parameter**|(% style="width:267px" %)**Value** | ||
27 | |(% style="width:434px" %)Supply voltage, V|(% style="width:267px" %)9÷30 | ||
28 | |(% style="width:434px" %)Current consumption @12 V, mA (max)|(% style="width:267px" %)100 | ||
29 | |Number of BMS Logic devices|1 to 23 | ||
30 | |Number of cells (maximum)|414 | ||
31 | |(% style="width:434px" %)Number of programmable solid-state relays for contactors (55V, 3A)|(% style="width:267px" %)4 | ||
32 | |(% style="width:434px" %)Number of programmable discrete inputs (dry contact)|(% style="width:267px" %)4 | ||
33 | |(% style="width:434px" %)Number of programmable discrete outputs (+5V)|(% style="width:267px" %)4 | ||
34 | |(% style="width:434px" %)Current sensor type|(% style="width:267px" %)((( | ||
35 | Hall-Effect sensor, bidirectional, supply voltage 5 V (LEM series HASS, HTFS) | ||
36 | ))) | ||
37 | |(% style="width:434px" %)Current sensor signal measurement error, V (maximum)|(% style="width:267px" %)0.001 | ||
38 | |(% style="width:434px" %)Number of CAN interfaces|(% style="width:267px" %)1 | ||
39 | |(% style="width:434px" %)CAN bus speed, kbps|(% style="width:267px" %)125, 250 (by default), 500, 1000 | ||
40 | |(% style="width:434px" %)Number of RS-485 interfaces|(% style="width:267px" %)2 | ||
41 | |(% style="width:434px" %)RS-485 baud rate, bps|(% style="width:267px" %)600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200 | ||
42 | |(% style="width:434px" %)**CAN output voltage, V**|(% style="width:267px" %)**5.0 ± 0.5** | ||
43 | |(% style="width:434px" %)**CAN output current, mA (maximum)**|(% style="width:267px" %)400 | ||
44 | |(% style="width:434px" %)**Number of Ethernet interfaces**|(% style="width:267px" %)1 | ||
45 | |(% style="width:434px" %)Ethernet speed, Mbps|(% style="width:267px" %)10/100 | ||
46 | |(% style="width:434px" %)Dimensions (length × width × height), mm|(% style="width:267px" %)120 × 120 × 32 | ||
47 | |(% style="width:434px" %)Weight, g|(% style="width:267px" %)100±5 | ||
48 | |(% colspan="2" style="width:702px" %)**Operating conditions** | ||
49 | |(% style="width:434px" %)Operating temperature range, °С|(% style="width:267px" %)-40÷75 | ||
50 | |(% style="width:434px" %)The degree of protection from external influences|(% style="width:267px" %)IP00 | ||
51 | |||
52 | == 1.2 Overall and mounting dimensions == | ||
53 | |||
54 | [[image:1733138859908-160.png]] | ||
55 | |||