Admin 21.1 1 [[image:https://movicomelectric.com/wa-data/public/site/img/08-BMS-Main-2-1.png||alt="BMS Main 2.1" data-xwiki-image-style-alignment="center" height="266" width="408"]]
Admin 13.1 2
Admin 23.1 3 The BMS Main 2.1 is a controller of the modular battery management system that has the following features:
Admin 13.1 4
Admin 15.2 5 * measuring current flowing through the battery;
6 * communication with BMS Logic that measure voltage and temperature of the battery cells;
7 * management of charging and discharging the battery;
8 * management of balancing the battery cells;
9 * protection of the battery from damage caused by current, voltage, temperature, etc.;
10 * communication with external equipment (chargers, inverters, indication panels) to provide needed battery operation mode;
11 * communication with external systems over Ethernet, CAN, RS-485, Wi-Fi;
12 * collecting and storing battery history data on an SD card.
Admin 13.1 13
Admin 23.1 14 The BMS Main 2.1 is used solely in civil areas. It does not use encryption and cryptography.
Admin 13.1 15
Admin 23.1 16 The BMS Main 2.1 is a part of Movicom Electric BMS, a modular battery management system, and controls the following devices:
Admin 15.2 17
18 * //BMS Logic 2.0//;
19 * //BMS Logic 12//;
20 * //BMS Logic 18//;
21 * //BMS Logic RET//.
22
Admin 20.1 23 = 1.1 Specifications =
Admin 15.2 24
Admin 23.1 25 (% style="width:705px" %)
26 |(% style="width:434px" %)**Parameter**|(% style="width:267px" %)**Value**
27 |(% style="width:434px" %)Supply voltage, V|(% style="width:267px" %)9÷30
28 |(% style="width:434px" %)Current consumption @12 V, mA (max)|(% style="width:267px" %)100
29 |Number of BMS Logic devices|1 to 23
30 |Number of cells (maximum)|414
31 |(% style="width:434px" %)Number of programmable solid-state relays for contactors (55V, 3A)|(% style="width:267px" %)4
32 |(% style="width:434px" %)Number of programmable discrete inputs (dry contact)|(% style="width:267px" %)4
33 |(% style="width:434px" %)Number of programmable discrete outputs (+5V)|(% style="width:267px" %)4
34 |(% style="width:434px" %)Current sensor type|(% style="width:267px" %)(((
Admin 17.1 35 Hall-Effect sensor, bidirectional, supply voltage 5 V (LEM series HASS, HTFS)
Admin 15.2 36 )))
Admin 23.1 37 |(% style="width:434px" %)Current sensor signal measurement error, V (maximum)|(% style="width:267px" %)0.001
38 |(% style="width:434px" %)Number of CAN interfaces|(% style="width:267px" %)1
39 |(% style="width:434px" %)CAN bus speed, kbps|(% style="width:267px" %)125, 250 (by default), 500, 1000
40 |(% style="width:434px" %)Number of RS-485 interfaces|(% style="width:267px" %)2
41 |(% style="width:434px" %)RS-485 baud rate, bps|(% style="width:267px" %)600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200
42 |(% style="width:434px" %)**CAN output voltage, V**|(% style="width:267px" %)**5.0 ± 0.5**
43 |(% style="width:434px" %)**CAN output current, mA (maximum)**|(% style="width:267px" %)400
44 |(% style="width:434px" %)**Number of Ethernet interfaces**|(% style="width:267px" %)1
45 |(% style="width:434px" %)Ethernet speed, Mbps|(% style="width:267px" %)10/100
46 |(% style="width:434px" %)Dimensions (length × width × height), mm|(% style="width:267px" %)120 × 120 × 32
47 |(% style="width:434px" %)Weight, g|(% style="width:267px" %)100±5
48 |(% colspan="2" style="width:702px" %)**Operating conditions**
49 |(% style="width:434px" %)Operating temperature range, °С|(% style="width:267px" %)-40÷75
50 |(% style="width:434px" %)The degree of protection from external influences|(% style="width:267px" %)IP00
Admin 15.2 51
Admin 23.1 52 == 1.2 Overall and mounting dimensions ==
53
54 [[image:1733138859908-160.png]]
55
56 [[image:1733138864828-321.png]]