Last modified by Admin on 2025/05/28 17:04

From version 15.2
edited by Admin
on 2024/11/13 17:36
Change comment: There is no comment for this version
To version 24.1
edited by Admin
on 2024/12/02 11:29
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -Controllers.BMS Main 2\.1.WebHome
1 +drafts.BMS Main 2\.1.WebHome
Content
... ... @@ -1,57 +1,40 @@
1 -[[image:1731519367438-871.1.png]]
1 +[[image:https://movicomelectric.com/wa-data/public/site/img/08-BMS-Main-2-1.png||alt="BMS Main 2.1" data-xwiki-image-style-alignment="center" height="266" width="408"]]
2 2  
3 -The BMS Main 2.1b is a controller of the modular battery management system that has the following features:
3 +BMS Main 2.1 is a modular BMS controller for 24-1200V batteries. It interacts with measuring modules, calculates the battery state, and protects the battery from damage.
4 4  
5 -* measuring current flowing through the battery;
6 -* communication with BMS Logic that measure voltage and temperature of the battery cells;
7 -* management of charging and discharging the battery;
8 -* management of balancing the battery cells;
9 -* protection of the battery from damage caused by current, voltage, temperature, etc.;
10 -* communication with external equipment (chargers, inverters, indication panels) to provide needed battery operation mode;
11 -* communication with external systems over Ethernet, CAN, RS-485, Wi-Fi;
12 -* collecting and storing battery history data on an SD card.
5 +BMS based on the Main 2.1 can control up to 23 measuring modules and manage a battery consisting of 414 cells.
13 13  
14 -The BMS Main 2.1b is used solely in civil areas. It does not use encryption and cryptography.
7 += 1.1 Specifications =
15 15  
16 -The BMS Main 2.1b is a part of Movicom Electric BMS, a modular battery management system, and controls the following devices:
17 -
18 -* //BMS Logic 2.0//;
19 -* //BMS Logic 12//;
20 -* //BMS Logic 18//;
21 -* //BMS Logic RET//.
22 -
23 -= Specifications =
24 -
25 -|**Parameter**|**Value**
26 -|Supply voltage, V|9÷30
27 -|Current consumption @12 V, mA (max)|100
28 -|Number of relays|4
29 -|Number of discrete inputs (dry contact)|4
30 -|Number of discrete outputs (+5V)|4
31 -|Relay 1-2 output voltage, V (max)|55
32 -|Relay 1-2 output current, A (max)|2
33 -|Relay 3-4 output voltage, V (max)|55
34 -|Relay 3-4 output current, A (max)|8
35 -|Current sensor type|(((
36 -Hall-Effect sensor,
37 -
38 -bidirectional,
39 -
40 -supply voltage 5 V
41 -
42 -(LEM series HASS, HTFS)
9 +(% style="width:705px" %)
10 +|(% style="width:434px" %)**Parameter**|(% style="width:267px" %)**Value**
11 +|(% style="width:434px" %)Supply voltage, V|(% style="width:267px" %)9÷30
12 +|(% style="width:434px" %)Current consumption @12 V, mA (max)|(% style="width:267px" %)100
13 +|Number of BMS Logic devices|1 to 23
14 +|Number of cells (maximum)|414
15 +|(% style="width:434px" %)Number of programmable solid-state relays for contactors (55V, 3A)|(% style="width:267px" %)4
16 +|(% style="width:434px" %)Number of programmable discrete inputs (dry contact)|(% style="width:267px" %)4
17 +|(% style="width:434px" %)Number of programmable discrete outputs (+5V)|(% style="width:267px" %)4
18 +|(% style="width:434px" %)Current sensor type|(% style="width:267px" %)(((
19 +Hall-Effect sensor, bidirectional, supply voltage 5 V (LEM series HASS, HTFS)
43 43  )))
44 -|CAN bus speed, kbps|125, 250 (by default), 500, 1000
45 -|RS-485 baud rate, bps|600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200
46 -|Ethernet speed, Mbps|10/100
47 -|RS-485 for communication with BMS Logic baud rate, bps|115200
48 -|Maximum number of the BMS Logic|20
49 -|Dimensions (length × width × height), mm|120 × 120 × 32
50 -|Weight, g|100±5
51 -|(% colspan="2" %)**Operating conditions**
52 -|Operating temperature range, °С|-40÷75
53 -|The degree of protection from external influences|IP00
21 +|(% style="width:434px" %)Current sensor signal measurement error, V (maximum)|(% style="width:267px" %)0.001
22 +|(% style="width:434px" %)Number of CAN interfaces|(% style="width:267px" %)1
23 +|(% style="width:434px" %)CAN bus speed, kbps|(% style="width:267px" %)125, 250 (by default), 500, 1000
24 +|(% style="width:434px" %)Number of RS-485 interfaces|(% style="width:267px" %)2
25 +|(% style="width:434px" %)RS-485 baud rate, bps|(% style="width:267px" %)600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200
26 +|(% style="width:434px" %)**CAN output voltage, V**|(% style="width:267px" %)**5.0 ± 0.5**
27 +|(% style="width:434px" %)**CAN output current, mA (maximum)**|(% style="width:267px" %)400
28 +|(% style="width:434px" %)**Number of Ethernet interfaces**|(% style="width:267px" %)1
29 +|(% style="width:434px" %)Ethernet speed, Mbps|(% style="width:267px" %)10/100
30 +|(% style="width:434px" %)Dimensions (length × width × height), mm|(% style="width:267px" %)120 × 120 × 32
31 +|(% style="width:434px" %)Weight, g|(% style="width:267px" %)100±5
32 +|(% colspan="2" style="width:702px" %)**Operating conditions**
33 +|(% style="width:434px" %)Operating temperature range, °С|(% style="width:267px" %)-40÷75
34 +|(% style="width:434px" %)The degree of protection from external influences|(% style="width:267px" %)IP00
54 54  
36 +== 1.2 Overall and mounting dimensions ==
55 55  
38 +[[image:1733138859908-160.png]]
56 56  
57 -
40 +[[image:1733138864828-321.png]]
1733138859908-160.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +74.1 KB
Content
1733138864828-321.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +19.5 KB
Content