Last modified by Admin on 2025/05/28 17:04

From version 15.1
edited by Admin
on 2024/11/13 17:36
Change comment: Uploaded new attachment "1731519367438-871.1.png", version {1}
To version 15.2
edited by Admin
on 2024/11/13 17:36
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,6 +1,57 @@
1 -This document describes configuration procedure of BMS Main 2.x board. Configuring can be done using the web interface available via Ethernet or Wi-Fi.
1 +[[image:1731519367438-871.1.png]]
2 2  
3 +The BMS Main 2.1b is a controller of the modular battery management system that has the following features:
3 3  
5 +* measuring current flowing through the battery;
6 +* communication with BMS Logic that measure voltage and temperature of the battery cells;
7 +* management of charging and discharging the battery;
8 +* management of balancing the battery cells;
9 +* protection of the battery from damage caused by current, voltage, temperature, etc.;
10 +* communication with external equipment (chargers, inverters, indication panels) to provide needed battery operation mode;
11 +* communication with external systems over Ethernet, CAN, RS-485, Wi-Fi;
12 +* collecting and storing battery history data on an SD card.
4 4  
14 +The BMS Main 2.1b is used solely in civil areas. It does not use encryption and cryptography.
5 5  
16 +The BMS Main 2.1b is a part of Movicom Electric BMS, a modular battery management system, and controls the following devices:
17 +
18 +* //BMS Logic 2.0//;
19 +* //BMS Logic 12//;
20 +* //BMS Logic 18//;
21 +* //BMS Logic RET//.
22 +
23 += Specifications =
24 +
25 +|**Parameter**|**Value**
26 +|Supply voltage, V|9÷30
27 +|Current consumption @12 V, mA (max)|100
28 +|Number of relays|4
29 +|Number of discrete inputs (dry contact)|4
30 +|Number of discrete outputs (+5V)|4
31 +|Relay 1-2 output voltage, V (max)|55
32 +|Relay 1-2 output current, A (max)|2
33 +|Relay 3-4 output voltage, V (max)|55
34 +|Relay 3-4 output current, A (max)|8
35 +|Current sensor type|(((
36 +Hall-Effect sensor,
37 +
38 +bidirectional,
39 +
40 +supply voltage 5 V
41 +
42 +(LEM series HASS, HTFS)
43 +)))
44 +|CAN bus speed, kbps|125, 250 (by default), 500, 1000
45 +|RS-485 baud rate, bps|600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200
46 +|Ethernet speed, Mbps|10/100
47 +|RS-485 for communication with BMS Logic baud rate, bps|115200
48 +|Maximum number of the BMS Logic|20
49 +|Dimensions (length × width × height), mm|120 × 120 × 32
50 +|Weight, g|100±5
51 +|(% colspan="2" %)**Operating conditions**
52 +|Operating temperature range, °С|-40÷75
53 +|The degree of protection from external influences|IP00
54 +
55 +
56 +
6 6