Last modified by Admin on 2025/05/28 17:04

From version 13.1
edited by Admin
on 2024/11/13 16:42
Change comment: Deleted image "1731515055585-924.png"
To version 17.1
edited by Admin
on 2024/11/13 17:41
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -Additional modules.BMS Main 2\.1.WebHome
1 +Controllers.BMS Main 2\.1.WebHome
Content
... ... @@ -1,25 +1,50 @@
1 -This document describes configuration procedure of BMS Main 2.x board. Configuring can be done using the web interface available via Ethernet or Wi-Fi.
1 +[[image:https://movicomelectric.com/wa-data/public/site/img/08-BMS-Main-2-1.png||alt="BMS Main 2.1" height="266" width="408"]]
2 2  
3 -Default connection settings for Ethernet are:
3 +The BMS Main 2.1b is a controller of the modular battery management system that has the following features:
4 4  
5 -* IP address – 192.168.0.100
6 -* Network Mask – 255.255.0.0
7 -* Default gateway – 192.168.0.1
5 +* measuring current flowing through the battery;
6 +* communication with BMS Logic that measure voltage and temperature of the battery cells;
7 +* management of charging and discharging the battery;
8 +* management of balancing the battery cells;
9 +* protection of the battery from damage caused by current, voltage, temperature, etc.;
10 +* communication with external equipment (chargers, inverters, indication panels) to provide needed battery operation mode;
11 +* communication with external systems over Ethernet, CAN, RS-485, Wi-Fi;
12 +* collecting and storing battery history data on an SD card.
8 8  
9 -(% class="box infomessage" %)
10 -(((
11 -**Note**
12 -To connect via Ethernet, the computer`s network adapter through which the BMS Main 2.x is configured must be in the same subnet as the target board.
13 -)))
14 +The BMS Main 2.1b is used solely in civil areas. It does not use encryption and cryptography.
14 14  
15 -To connect via Wi-Fi use the IP address which an access point gave to the board (see Wi-Fi for configuring the connection and the “System Overview” section to find out the IP address).
16 +The BMS Main 2.1b is a part of Movicom Electric BMS, a modular battery management system, and controls the following devices:
16 16  
17 -Default credentials for changing board settings using the web interface are:
18 +* //BMS Logic 2.0//;
19 +* //BMS Logic 12//;
20 +* //BMS Logic 18//;
21 +* //BMS Logic RET//.
18 18  
19 -* Login – user
20 -* Password – bms
23 += Specifications =
21 21  
22 -To access the web interface, enter the IP address of the board (192.168.0.100 by default) in the address bar of the browser.
25 +|(% style="width:429px" %)**Parameter**|(% style="width:1092px" %)**Value**
26 +|(% style="width:429px" %)Supply voltage, V|(% style="width:1092px" %)9÷30
27 +|(% style="width:429px" %)Current consumption @12 V, mA (max)|(% style="width:1092px" %)100
28 +|(% style="width:429px" %)Number of relays|(% style="width:1092px" %)4
29 +|(% style="width:429px" %)Number of discrete inputs (dry contact)|(% style="width:1092px" %)4
30 +|(% style="width:429px" %)Number of discrete outputs (+5V)|(% style="width:1092px" %)4
31 +|(% style="width:429px" %)Relay 1-2 output voltage, V (max)|(% style="width:1092px" %)55
32 +|(% style="width:429px" %)Relay 1-2 output current, A (max)|(% style="width:1092px" %)2
33 +|(% style="width:429px" %)Relay 3-4 output voltage, V (max)|(% style="width:1092px" %)55
34 +|(% style="width:429px" %)Relay 3-4 output current, A (max)|(% style="width:1092px" %)8
35 +|(% style="width:429px" %)Current sensor type|(% style="width:1092px" %)(((
36 +Hall-Effect sensor, bidirectional, supply voltage 5 V (LEM series HASS, HTFS)
37 +)))
38 +|(% style="width:429px" %)CAN bus speed, kbps|(% style="width:1092px" %)125, 250 (by default), 500, 1000
39 +|(% style="width:429px" %)RS-485 baud rate, bps|(% style="width:1092px" %)600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200
40 +|(% style="width:429px" %)Ethernet speed, Mbps|(% style="width:1092px" %)10/100
41 +|(% style="width:429px" %)RS-485 for communication with BMS Logic baud rate, bps|(% style="width:1092px" %)115200
42 +|(% style="width:429px" %)Maximum number of the BMS Logic|(% style="width:1092px" %)20
43 +|(% style="width:429px" %)Dimensions (length × width × height), mm|(% style="width:1092px" %)120 × 120 × 32
44 +|(% style="width:429px" %)Weight, g|(% style="width:1092px" %)100±5
45 +|(% colspan="2" %)**Operating conditions**
46 +|(% style="width:429px" %)Operating temperature range, °С|(% style="width:1092px" %)-40÷75
47 +|(% style="width:429px" %)The degree of protection from external influences|(% style="width:1092px" %)IP00
23 23  
24 24  
25 25  
1731519367438-871.1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +5.4 MB
Content