Last modified by Admin on 2025/05/28 17:04

From version 13.1
edited by Admin
on 2024/11/13 16:42
Change comment: Deleted image "1731515055585-924.png"
To version 16.1
edited by Admin
on 2024/11/13 17:36
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -Additional modules.BMS Main 2\.1.WebHome
1 +Controllers.BMS Main 2\.1.WebHome
Content
... ... @@ -1,25 +1,57 @@
1 -This document describes configuration procedure of BMS Main 2.x board. Configuring can be done using the web interface available via Ethernet or Wi-Fi.
1 +[[image:https://movicomelectric.com/wa-data/public/site/img/08-BMS-Main-2-1.png||alt="BMS Main 2.1" height="266" width="408"]]
2 2  
3 -Default connection settings for Ethernet are:
3 +The BMS Main 2.1b is a controller of the modular battery management system that has the following features:
4 4  
5 -* IP address – 192.168.0.100
6 -* Network Mask – 255.255.0.0
7 -* Default gateway – 192.168.0.1
5 +* measuring current flowing through the battery;
6 +* communication with BMS Logic that measure voltage and temperature of the battery cells;
7 +* management of charging and discharging the battery;
8 +* management of balancing the battery cells;
9 +* protection of the battery from damage caused by current, voltage, temperature, etc.;
10 +* communication with external equipment (chargers, inverters, indication panels) to provide needed battery operation mode;
11 +* communication with external systems over Ethernet, CAN, RS-485, Wi-Fi;
12 +* collecting and storing battery history data on an SD card.
8 8  
9 -(% class="box infomessage" %)
10 -(((
11 -**Note**
12 -To connect via Ethernet, the computer`s network adapter through which the BMS Main 2.x is configured must be in the same subnet as the target board.
13 -)))
14 +The BMS Main 2.1b is used solely in civil areas. It does not use encryption and cryptography.
14 14  
15 -To connect via Wi-Fi use the IP address which an access point gave to the board (see Wi-Fi for configuring the connection and the “System Overview” section to find out the IP address).
16 +The BMS Main 2.1b is a part of Movicom Electric BMS, a modular battery management system, and controls the following devices:
16 16  
17 -Default credentials for changing board settings using the web interface are:
18 +* //BMS Logic 2.0//;
19 +* //BMS Logic 12//;
20 +* //BMS Logic 18//;
21 +* //BMS Logic RET//.
18 18  
19 -* Login – user
20 -* Password – bms
23 += Specifications =
21 21  
22 -To access the web interface, enter the IP address of the board (192.168.0.100 by default) in the address bar of the browser.
25 +|**Parameter**|**Value**
26 +|Supply voltage, V|9÷30
27 +|Current consumption @12 V, mA (max)|100
28 +|Number of relays|4
29 +|Number of discrete inputs (dry contact)|4
30 +|Number of discrete outputs (+5V)|4
31 +|Relay 1-2 output voltage, V (max)|55
32 +|Relay 1-2 output current, A (max)|2
33 +|Relay 3-4 output voltage, V (max)|55
34 +|Relay 3-4 output current, A (max)|8
35 +|Current sensor type|(((
36 +Hall-Effect sensor,
23 23  
38 +bidirectional,
24 24  
40 +supply voltage 5 V
41 +
42 +(LEM series HASS, HTFS)
43 +)))
44 +|CAN bus speed, kbps|125, 250 (by default), 500, 1000
45 +|RS-485 baud rate, bps|600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200
46 +|Ethernet speed, Mbps|10/100
47 +|RS-485 for communication with BMS Logic baud rate, bps|115200
48 +|Maximum number of the BMS Logic|20
49 +|Dimensions (length × width × height), mm|120 × 120 × 32
50 +|Weight, g|100±5
51 +|(% colspan="2" %)**Operating conditions**
52 +|Operating temperature range, °С|-40÷75
53 +|The degree of protection from external influences|IP00
54 +
55 +
56 +
25 25  
1731519367438-871.1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +5.4 MB