Changes for page 3. Configuration

Last modified by Admin on 2025/01/09 15:17

From version 4.1
edited by Admin
on 2024/12/02 16:37
Change comment: There is no comment for this version
To version 1.1
edited by Admin
on 2024/12/02 15:02
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -10,20 +10,19 @@
10 10  
11 11  === 3.1.1 Communication and power cable ===
12 12  
13 -[[image:1733151480872-233.png||data-xwiki-image-style-alignment="center" height="239" width="435"]]
13 +[[image:1733151480872-233.png||data-xwiki-image-style-alignment="center" height="255" width="465"]]
14 14  
15 15  The wires of the communication and power cable must be connected according to the following table:
16 16  
17 -(% style="width:393px" %)
18 -|**Circuit name**|(% style="width:148px" %)**Pin of the connector to BMS USB-RS485**|(% style="width:149px" %)**Pin of the connector to BMS Logic 18**
19 -|**RS485_A**|(% style="width:148px" %)1|(% style="width:149px" %)1
20 -|**RS485_B**|(% style="width:148px" %)2|(% style="width:149px" %)2
21 -|**+5V**|(% style="width:148px" %)3|(% style="width:149px" %)3
22 -|**GND**|(% style="width:148px" %)4|(% style="width:149px" %)4
17 +|**Circuit name**|(% style="width:148px" %)**Pin of the connector to BMS USB-RS485**|(% style="width:386px" %)**Pin of the connector to BMS Logic 18**
18 +|**RS485_A**|(% style="width:148px" %)1|(% style="width:386px" %)1
19 +|**RS485_B**|(% style="width:148px" %)2|(% style="width:386px" %)2
20 +|**+5V**|(% style="width:148px" %)3|(% style="width:386px" %)3
21 +|**GND**|(% style="width:148px" %)4|(% style="width:386px" %)4
23 23  
24 24  === 3.1.2 Cells cable ===
25 25  
26 -[[image:1733151480875-350.png||data-xwiki-image-style-alignment="center" height="137" width="713"]]
25 +[[image:1733151480875-350.png||data-xwiki-image-style-alignment="center" height="126" width="656"]]
27 27  
28 28  [[image:1733151480876-978.png||data-xwiki-image-style-alignment="center" height="224" width="441"]]
29 29  
... ... @@ -51,20 +51,20 @@
51 51  |**C17**|(% style="width:151px" %)21|(% style="width:152px" %)20
52 52  |**C18**|(% style="width:151px" %)10|(% style="width:152px" %)10
53 53  
54 -== 3.2 Setting device address ==
53 +3.2 Setting device address
55 55  
56 56  Launch the ElectricDeviceMonitor, then select the “BMS Logic 12/18 3.x” monitor:
57 57  
58 -[[image:1733151480877-266.png||data-xwiki-image-style-alignment="center" height="351" width="321"]]
57 +[[image:1733151480877-266.png||data-xwiki-image-style-alignment="center" height="267" width="244"]]
59 59  
60 60  Select the following settings to connect to the BMS Logic 18: 115200 bps, 8 bits, no parity, 1 stop bit, device address 247. The address 247 is a service address that the device will always answer.
61 61  
62 -[[image:1733151480878-434.png||data-xwiki-image-style-alignment="center" height="263" width="477"]]
61 +[[image:1733151480878-434.png||data-xwiki-image-style-alignment="center" height="248" width="450"]]
63 63  
64 64  Check the connection with the BMS Logic 18 is established.
65 65  
66 66  Set the needed device address and click the “Save” button:
67 67  
68 -[[image:1733151480878-552.png||data-xwiki-image-style-alignment="center" height="461" width="707"]]
67 +[[image:1733151480878-552.png||data-xwiki-image-style-alignment="center" height="432" width="663"]]
69 69  
70 70