4. Indication

Version 1.1 by Admin on 2024/12/13 15:13

Indication

No connection with BMS

If there are no Heartbeat messages from the BMS controller over the CAN bus the following message will be output on the display:

 1734102803975-599.png 

Sound signals are not emitted in this case.

BMS initialization

If the connection with the BMS controller is established and the BMS is in the initialization mode (during the initialization the current sensor is calibrating and the BMS Logic boards searching is performed), the second line of the display will contain zero values of the voltage, current and temperature:

Sound signals are not emitted in this case.


    1. Battery discharging

If the battery is in the discharging mode (the current is zero or negative) and there are no errors, the first line of the display will contain the charge level and the second line will contain battery parameters: voltage, current and minimum/maximum temperature:

file:///C:/Users/INASIB~1/AppData/Local/Temp/msohtmlclip1/01/clip_image001.emz

Data URI image

Note – Views with the minimum and maximum temperatures are changing every 2 seconds. To change them manually press the button on the device or an external button connected to the P6 header.

If the battery charge level is below the value set in the Low battery level signal (single beep) group, the device will emit a sound signal about the low battery charge level.

If the battery charge level is below the value set in the Battery discharged signal (three beeps) group, the device will emit three sound signals alarming that the battery is empty.


    1. Battery charging

The device emits a sound signal if the charger is connected to the battery. Duration of the signal is set by the Signal duration on charger connected parameter. The following message will be output to the display in this case:

file:///C:/Users/INASIB~1/AppData/Local/Temp/msohtmlclip1/01/clip_image005.emz

The device emits two signals if the charger is disconnected from the battery. Duration of the signals is set by the Signal duration on charger disconnected parameter. The following message will be output to the display in this case:

file:///C:/Users/INASIB~1/AppData/Local/Temp/msohtmlclip1/01/clip_image006.emz

If the battery is charging the following animation will appear on the display:

file:///C:/Users/INASIB~1/AppData/Local/Temp/msohtmlclip1/01/clip_image007.emz

  1.  
    1. Indication of errors

If there are errors selected by the Errors filter (see Display options group), names or codes of errors will be output to the display. In this case a loud sound signal is periodically emitted.

file:///C:/Users/INASIB~1/AppData/Local/Temp/msohtmlclip1/01/clip_image008.emz

file:///C:/Users/INASIB~1/AppData/Local/Temp/msohtmlclip1/01/clip_image009.emz

If the number of errors is greater than three, a list of errors will be output page by page. Turning pages will be performed automatically every 2 seconds.  It is also available changing pages manually using the button on the device or an external button connected to the P6 header.

Errors names and codes are in the table below.

Error nameError codeDescription
OvercurrentOCHigh current
UndervoltageUVLow voltage
OvervoltageOVHigh voltage
Low DCH temp.LDTBattery temperature is too low for discharging
High DCH temp.HDTBattery temperature is too high for discharging
Battery coverBCBattery cover is opened
High humidityHHHigh humidity
WaterWAWater in the battery
Logic hi. temp.LHTTemperature of a BMS Logic board is too high
Logic offlineLOFNo connection with a BMS Logic board
Critical errorCERCritical error
Crown errorCROCrown forklift error
Cell countCELWrong number of cells
HYG offlineHYGNo connection with the HYG forklift
Need ACKACKAcknowledge of errors is needed
Combilift offl.COMNo connection with the Combilift forklift
Short circuitSHCShort circuit
Cont. hi. temp.CHTHight temperature of a contactor
Logic countLOGWrong number of BMS Logic boards
ADC errorADCWrong values from the ADC
Current sensorCSECurrent sensor is shorted or opened
CH cont. cycleCCCCharge contactor switches too frequency
DCH cont. cycleDCCDischarge contactor switches too frequency
Shunt offlineSHONo connection with the shunt sensor
Shunt errorSHEInternal error of the shunt sensor
Settings errorSETChecksum of settings is wrong
WDT resetWDTWatchdog timer reset the BMS
No temp. sens.NTSNo temperature sensors connected to a BMS Logic
Shorted temp.TSSA temperature sensor connected to a BMS Logic is shorted
Spirit offlineSPINo connection with the Spirit truck
Low CH temp.LCTBattery temperature is too low for charging
High CH temp.HCTBattery temperature is too high for charging
Mount errorMNTSD card is not mounted
FS errorFSEFilesystem on an SD card is corrupted
Unallowable CHUCHCharging the battery through the discharging circuit
Stuck contactorSTCContactor is stuck
CH cont. feed.CCFWrong feedback signal from the charging contactor
DCH cont. feed.DCFWrong feedback signal from the discharging contactor