Configuration
General information
List of input signals
Here is the list of input signals that can be assigned to discrete inputs of BMS controller.
Name | Abbr. | Description | Compability | CANopen SDO | Modbus | ||
---|---|---|---|---|---|---|---|
Mini S / Mini | Main 2.1 | Main 3 | |||||
Balancing request | BR | a request to balance the cells; | Yes | Yes | Yes | ||
Battery cover | CVR | a signal from the battery cover; | Yes | Yes | Yes | ||
CH contactor feedback | CCF | a signal from charging contactor feedback loop; | Yes* | Yes | Yes | ||
CH/DCH contactor feedback | CDF | a signal from charging/discharging contactor feedback loop; | Yes* | Yes | Yes | ||
Charge request | CRE | a request to close the charging contactor; | Yes | Yes | Yes | ||
Charger connected | CON | a signal indicating that charger is connected; | Yes | Yes | Yes | ||
Circuit breaker status | CBS | status of protection disconnector; | Yes | Yes | Yes | ||
Close External 1 | CE1 | a request to close the External 1 discrete output (if assigned). | Yes | Yes | Yes | ||
Close Main contactor | CMC | a request to close the main contactor; | Yes | Yes | Yes | ||
DCH contactor feedback | DCF | a signal from discharging contactor feedback loop; | Yes* | Yes | Yes | ||
Discharge request | DRE | a request to close the discharging contactor; | Yes | Yes | Yes | ||
Fuse 1 | F1 | signal from fuse 1; | Yes | Yes | Yes | ||
Fuse 2 | F2 | signal from fuse 2; | Yes | Yes | Yes | ||
Fuse 3 | F3 | signal from fuse 3; | Yes | Yes | Yes | ||
Inhibit charging | ICH | a command to open the charging contactor; | Yes | Yes | Yes | ||
Inhibit discharging | IDC | a command to open the discharging contactor; | Yes | Yes | Yes | ||
Insulation status | INS | a signal from an insulation monitoring device; | Yes | Yes | Yes | ||
Interlock | a signal from interlock loop; | Yes | Yes | Yes | |||
Main contactor feedback | MCF | a signal from main contactor feedback loop; | Yes* | Yes | Yes | ||
PCH contactor feedback | PCF | a signal from precharging contactor feedback loop; | Yes* | Yes | Yes | ||
Power up/down request | PDN | a request to power down the device; | Yes | Yes | Yes | ||
Precharge request | PRE | a request to close the precharging contactor | Yes | Yes |
* Contactor feedback signals in BMS Mini / BMS Mini S are connected to X1 header and configured in "Signals → MOSFETs → Contactors feedback" section.
List of internal states
Name | Abbr. | Description | Compability | CANopen SDO | Modbus | ||
---|---|---|---|---|---|---|---|
Mini S / Mini | Main 2.1 | Main 3 | |||||
Allow charging | ACH | a signal for a charger to start charging; | Yes | Yes | Yes | ||
Balancing 1 | BA1 | balancing the first series of cells; | Yes | Yes | |||
Balancing 2 | BA2 | balancing the second series of cells; | Yes | Yes | |||
Cell analysis | CEA | Yes | Yes | Yes | |||
Charging current present | CCP | the presence of the charging current; | Yes | Yes | Yes | ||
Charging | CH | state of the charging contactor; | Yes | Yes | Yes | ||
Charging/discharging | C/D | state of the charging/discharging contactor; | Yes | Yes | Yes | ||
Cooler | COO | a command to turn on a cooler; | Yes | Yes | Yes | ||
Crown EWS | EWS | Yes | Yes | Yes | |||
Discharging (AUX) | AUX | state of the auxiliary discharging contactor; | Yes | Yes | Yes | ||
Discharging current present | DCP | the presence of the discharging current; | Yes | Yes | Yes | ||
Discharging | DCH | state of the discharging contactor; | Yes | Yes | Yes | ||
External 1 | EX1 | a signal that activates by the remote request. | Yes | Yes | |||
Heater | HEA | a command to turn on a heater; | Yes | Yes | Yes | ||
Heater (AUX) | HA | Yes | Yes | ||||
High charging current | HCC | charging current is high; | Yes | Yes | Yes | ||
Init | INI | Yes | Yes | Yes | |||
Low SOC | LOS | a signal corresponding the low SOC of the battery; | Yes | Yes | Yes | ||
Main contactor | MCO | state of the main contactor; | Yes | Yes | Yes | ||
Power down ACK | PDA | an acknowledgement of BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on power down request; | Yes | Yes | Yes | ||
Power up | PUP | an indication of BMS power status; | Yes | Yes | Yes | ||
Precharging | PRE | state of the precharging contactor; | Yes | Yes | Yes | ||
Ready to charge | RTC | the battery is ready to be charged; | Yes | Yes | Yes | ||
Ready to discharge | RTD | the battery is ready to be discharged; | Yes | Yes | Yes | ||
Service reset | SR | Yes | Yes | ||||
Shutdown request (Combilift) | CSH | Yes | Yes | Yes | |||
Shutdown request (HYG/Spirit) | HSH | Yes | Yes | Yes | |||
Voltage too high for charging | ENV | Yes | Yes | Yes |
* States
List of errors
Name | Abbr. | Description | Is a Critical error? | Compability | CANopen SDO | Modbus | ||
Mini S / Mini | Main 2.1 | Main 3 | ||||||
---|---|---|---|---|---|---|---|---|
ADC error | ADC | current cannot be measured; | • | Yes | Yes | Yes | ||
Battery cover error | BC | battery cover is open; | • | Yes | Yes | Yes | ||
Cell count error | CEL | number of cells does not match the specified value; | • | Yes | Yes | Yes | ||
CH contactor cycles error | CCC | switching frequency of the charging contactor is too high; | Yes | Yes | Yes | |||
CH contactor feedback error | CCF | the control signals for the charging contactor and the contactor feedback differ; | • | Yes | ||||
CH/DCH contactor feedback error | CDF | the control signals for the charging/discharging contactor and the contactor feedback differ; | • | Yes | ||||
Combilift offline | COM | connection with a Combilift forklift is lost; | Yes | Yes | Yes | |||
Contactor feedback error | CFE | Failure of one of the contactors feedback signal. Which contactor is failed can be | Yes | Yes | ||||
Critical error | CER | Yes | Yes | Yes | ||||
Crown error | CRO | connection with a Crown forklift is lost; | Yes | Yes | Yes | |||
Current limit error | CLE | charging or discharging current is more than limit calculated by Charge map or Discharge map. | Yes | Yes | ||||
Current sensor error | CSE | error in the current sensor circuit; | • | Yes | Yes | Yes | ||
DCH contactor cycles error | DCC | switching frequency of the discharging contactor is too high; | Yes | Yes | Yes | |||
DCH contactor feedback error | DCF | the control signals for the discharging contactor and the contactor feedback differ; | • | Yes | ||||
FS error | FSE | Yes | Yes | Yes | ||||
General error | GE | Yes | Yes | Yes | ||||
High contactor temperature | CHT | Yes | Yes | Yes | ||||
High humidity | HH | humidity of the battery is increased; | Yes | Yes | Yes | |||
High Logic temperature | LHT | at least one of the Logic devices is overheated; | Yes | Yes | Yes | |||
High temperature (CH) | HCT | temperature is too high for charging; | Yes | Yes | Yes | |||
High temperature (DCH) | HDT | temperature is too high for discharging; | Yes | Yes | Yes | |||
High voltage fault | HVF | failure of high voltage measuring circuits; | • | Yes | ||||
HVIL error | HE | breakage of high-voltage interlock current loop; | • | Yes | ||||
HYG offline | HYG | connection with a HYG forklift is lost; | Yes | Yes | Yes | |||
Insulation fault; | INF | • | Yes | Yes | Yes | |||
Logic count error | LOG | |||||||
Logic offline | LOF | at least one of the Logic devices is offline; | • | Yes | Yes | Yes | ||
Low temperature (CH) | LCT | temperature is too low for charging; | Yes | Yes | Yes | |||
Low temperature (DCH) | LDT | temperature is too low for discharging; | Yes | Yes | Yes | |||
Main contactor feedback error | MCF | the control signals for the main contactor and the contactor feedback differ; | • | Yes | ||||
Mount error | MNT | Yes | Yes | Yes | ||||
Need acknowledge | ACK | there is an unacknowledged error in Error journal; | Yes | Yes | Yes | |||
No temperature sensors | NTS | the device has no temperature sensors connected; | • | Yes | Yes | Yes | ||
Overcurrent | OC | Yes | Yes | Yes | ||||
Overvoltage | OV | Yes | Yes | Yes | ||||
PCH contactor feedback error | PCF | the control signals for the precharging contactor and the contactor feedback differ; | • | Yes | ||||
Power fault | PF | external devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices; | • | Yes | ||||
Power switch error | PSE | short circuit in contactor coil control circuit or power switch overheating; | • | Yes | ||||
Precharge error | PE | capacitive load pre-charge process did not end during the estimated time; | Yes | Yes | Yes | |||
Settings error | SET | |||||||
Short circuit | SHC | Yes | Yes | Yes | ||||
Shunt error | SHE | internal error of the shunt current sensor; | • | Yes | Yes | Yes | ||
Shunt offline | SHO | connection with the shunt current sensor is lost; | • | Yes | Yes | Yes | ||
Spirit offline | SPI | connection with a Spirit forklift is lost; | Yes | Yes | Yes | |||
Stuck contactor | STC | • | Yes | Yes | Yes | |||
Temperature sensor is shorted | TSS | some temperature sensors are shorted; | • | Yes | Yes | Yes | ||
Unallowable charging | UCH | charging the battery through the discharging contactor; | Yes | Yes | Yes | |||
Undervoltage | UV | Yes | Yes | Yes | ||||
Water | WA | there is water in the battery enclosure; | • | Yes | Yes | Yes | ||
WDT reset | WDT | watchdog timer reset the device; | • | Yes | Yes | Yes |