Strings controllers: signals, states and errors

Version 29.1 by Admin on 2025/02/04 08:28

Signals, states and errors

Input signals

Below is the list of input signals that can be assigned to discrete inputs of the battery strings controller.

NameDescriptionCompabilityBMS DIsplayCANopen SDOModbus
Main XMain 3XShort nameAbbreviation
Battery coverSignal from the battery coverYesYesBattery coverCVR  
CH contactor feedbackSignal from the charging contactor feedback loopYesYesCH cont. feed.CCF  
CH/DCH contactor feedbackSignal from the charging/discharging contactor feedback loopYesYesC/D cont. feed.CDF  
Charge requestRequest to close the charging contactorYesYesCharge requestCRE  
DCH contactor feedbackSignal from the discharging contactor feedback loopYesYesDCH cont. feed.DCF  
Discharge requestRequest to close the discharging contactorYesYesDischarge req.DRE  
Insulation statusSignal from an insulation monitoring deviceYesYesInsul. statusINS  
InterlockSignal from the interlock loop YesInterlockINT  
Join to chargeRequest to join the battery modules for chargingYesYesJoin to chargeJTC  
Join to dischargeRequest to join the battery modules for dischargingYesYesJoin to dischar.JTD  
Main contactor feedbackSignal from the main contactor feedback loopYesYesMain cont. feed.MCF  
PCH contactor feedbackSignal from the precharging contactor feedback loopYesYesPCH cont. feed.PCF  
Power down requestRequest to power down the device YesPower down req.PDN  
Precharge requestRequest to close the precharging contactorYesYesPrecharge req.PRE  

Internal signals

Below is the list of internal BMS signals. The signals marked with bold text can be assigned to discrete outputs and relays.

NameDescriptionCompabilityBMS DisplayCANopen SDOModbus
Main XMain 3XShort nameAbbreviation
Charging current presentSignal showing the presence of the charging currentYes*Yes*CH curr. presentCCP  
ChargingCommand to control the charging contactorYesYesChargingCH  
Charging/DischargingCommand to control the charging/discharging contactorYesYesCharg./Discharg.C/D  
Coolant pumpCommand to control the coolant pumpYesYesCoolant pumpCP  
CoolerCommand to control the coolerYesYesCoolerCOO  
Discharging current presentSignal showing the presence of the discharging currentYes*Yes*DCH cur. presentDCP  
DischargingCommand to control the discharging contactorYesYesDischargingDCH  
Fuse 1 (modules)ORed internal signals "Fuse 1" from all battery modulesYes*Yes*Fuse 1 (mod.)F1M  
Fuse 2 (modules)ORed internal signals "Fuse 2" from all battery modulesYes*Yes*Fuse 2 (mod.)F2M  
Fuse 3 (modules)ORed internal signals "Fuse 3" from all battery modulesYes*Yes*Fuse 3 (mod.)F3M  
General error (modules)ORed internal signals "General error" from all battery modulesYesYesGen.error (mod.)GEM  
HeaterCommand to control the heaterYesYesHeaterHEA  
InitSignal showing that the device is in the initialization phaseYes*Yes*InitINI  
Interlock (modules)ORed internal signals "Interlock" from all battery modulesYes*Yes*Interlock (mod.)INM  
Main contactorCommand to control the main contactorYesYesMain contactorMCO  
PrechargingCommand to control the precharging contactorYesYesPrechargingPCH  
Service resetCommand to restart the deviceYes*Yes*Service resetSR  

* Cannot be assigned to discrete outputs and relays.

Errors

Name DescriptionIs a critical error?CompabilityBMS DisplayCANopen SDOModbus
Main XMain 3XShort nameAbbreviation
ADC errorError of the ADC that measures the battery currentYes YesADC errorADC  
Battery cover errorBattery cover is openYesYesYesBattery coverBCE  
CH contactor feedback errorThe control signal for the charging contactor and the contactor feedback differYesYesYesCH cont. feed.CCF  
CH/DCH contactor feedback errorThe control signal for the charging/discharging contactor and the contactor feedback differYesYesYesC/D cont. feed.CDF  
Charging current unbalance  YesYesCH current unb.CCU  
Critical errorCritical system error, the BMS is damaged YesYesCritical errorCER  
Current limit errorCharging or discharging current is more than the limit calculated by Charge map or Discharge map YesYesCur. limit errorCLE  
Current sensor errorError in the current sensor circuitYes YesCurrent sensorCSE  
Current unbalance (CH)  YesYesCurrent unb. CHCUC  
Current unbalance (DCH)  YesYesCurrent unb. DCHCUD  
DCH contactor feedback errorThe control signal for the discharging contactor and the contactor feedback differYes YesDCH cont. feed.DCF  
Discharging current unbalance  YesYesDCH current unb.DCU  
FS errorSD card read/write error YesYesFS errorFSE  
High contactor temperatureTemperature of a contactor is too high YesYesHi. cont. temp.HCT  
High humidityIncreased humidity inside the battery  YesHigh humidityHHU  
High voltage faultFailure of high voltage measuring circuitsYes YesHV faultHVF  
HVIL errorBreakage of high-voltage interlock current loopYes YesHVIL errorHE  
Insulation faultInsulation resistance is too lowYesYesYesInsulation faultINF  
Module offlineSome of battery modules is offlineYesYesYesModule offlineMOF  
Main contactor feedback errorThe control signal for the main contactor and the contactor feedback differYesYesYesMain cont. feed.MCF  
Mount errorSD card cannot be mounted YesYesMount errorMNT  
Need acknowledgeThere is an unacknowledged error in error journal YesYesNeed ACKACK  
OvercurrentThe battery current is too high YesYesOvercurrentOC  
PCH contactor feedback errorThe control signal for the precharging contactor and the contactor feedback differYesYesYesPCH cont. feed.PCF  
Power faultExternal devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devicesYes YesPower faultPF  
Power switch errorShort circuit in contactor coil control circuit or power switch overheatingYes YesPSW errorPSE  
Precharge errorCapacitive load pre-charge process did not end during the estimated time YesYesPrecharge errorPE  
Short circuitFlowing high battery currents during a long time YesYesShort circuitSHC  
Stuck contactorSome contactor got stuckYesYesYesStuck contactorSTC  
Voltage unbalance (CH)  YesYesVoltage unb. CHVUC  
Voltage unbalance (DCH)  YesYesVoltage unb. DCHVUD  
WaterThere is water in the battery enclosureYes YesWaterWHU  
WDT resetWatchdog timer reset the deviceYesYesYesWDT resetWDT