... ... @@ -88,7 +88,7 @@
88 88  |(% style="width:171px" %)Contactor feedback error|(% style="width:324px" %)Failure of one of the contactors feedback signal. Which contactor is failed can be found in "Signals -> MOSFETs -> Contactor feedback" section of the BMS Mini device|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %) |(% style="width:56px" %) |(% style="width:126px" %)Cont. feed. er.|(% style="width:54px" %)CFE|(% style="width:265px" %) |(% style="width:306px" %)0x200E-0x200F, bit 12. Off = 0, On = 1.
89 89  |(% style="width:171px" %)Critical error|(% style="width:324px" %)Critical system error, the BMS is damaged|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Critical error|(% style="width:54px" %)CER|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 10. Off = 0, On = 1.
90 90  |(% style="width:171px" %)Crown error|(% style="width:324px" %)Connection with the Crown forklift is lost|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Crown error|(% style="width:54px" %)CRO|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 11. Off = 0, On = 1.
91 -|(% style="width:171px" %)Current limit error|(% style="width:324px" %)Charging or discharging current is more than the limit calculated by Charge map or Discharge map|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %) |(% style="width:56px" %)Yes|(% style="width:126px" %)Cur. limit error|(% style="width:54px" %)CLE|(% style="width:265px" %) |(% style="width:306px" %)
91 +|(% style="width:171px" %)Current limit error|(% style="width:324px" %)Charging or discharging current is more than the limit calculated by Charge map or Discharge map|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %) |(% style="width:56px" %)Yes|(% style="width:126px" %)Cur. limit error|(% style="width:54px" %)CLE|(% style="width:265px" %) |(% style="width:306px" %)0x200E-0x200F, bit 19. Off = 0, On = 1.
92 92  |(% style="width:171px" %)Current sensor error|(% style="width:324px" %)Error in the current sensor circuit|(% style="width:61px" %)Yes|(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Current sensor|(% style="width:54px" %)CSE|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 20. Off = 0, On = 1.
93 93  |(% style="width:171px" %)DCH contactor cycles error|(% style="width:324px" %)Switching frequency of the discharging contactor is too high|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)DCH cont. cycle|(% style="width:54px" %)DCC|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 22. Off = 0, On = 1.
94 94  |(% style="width:171px" %)DCH contactor feedback error|(% style="width:324px" %)The control signal for the discharging contactor and the contactor feedback differ|(% style="width:61px" %)Yes|(% style="width:92px" %) |(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)DCH cont. feed.|(% style="width:54px" %)DCF|(% style="width:265px" %) |(% style="width:306px" %)0x200E-0x200F, bit 7. Off = 0, On = 1.
... ... @@ -115,9 +115,9 @@
115 115  |(% style="width:171px" %)Overcurrent|(% style="width:324px" %)The battery current is too high|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Overcurrent|(% style="width:54px" %)OC|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 0. Off = 0, On = 1.
116 116  |(% style="width:171px" %)Overvoltage|(% style="width:324px" %)Voltage of any cell is too high|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Overvoltage|(% style="width:54px" %)OV|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 2. Off = 0, On = 1.
117 117  |(% style="width:171px" %)PCH contactor feedback error|(% style="width:324px" %)The control signal for the precharging contactor and the contactor feedback differ|(% style="width:61px" %)Yes|(% style="width:92px" %) |(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)PCH cont. feed.|(% style="width:54px" %)PCF|(% style="width:265px" %) |(% style="width:306px" %)0x200E-0x200F, bit 9. Off = 0, On = 1.
118 -|(% style="width:171px" %)Power fault|(% style="width:324px" %)External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|(% style="width:61px" %)Yes|(% style="width:92px" %) |(% style="width:66px" %) |(% style="width:56px" %)Yes|(% style="width:126px" %)Power fault|(% style="width:54px" %)PF|(% style="width:265px" %) |(% style="width:306px" %)
118 +|(% style="width:171px" %)Power fault|(% style="width:324px" %)External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|(% style="width:61px" %)Yes|(% style="width:92px" %) |(% style="width:66px" %) |(% style="width:56px" %)Yes|(% style="width:126px" %)Power fault|(% style="width:54px" %)PF|(% style="width:265px" %) |(% style="width:306px" %)0x200E-0x200F, bit 18. Off = 0, On = 1.
119 119  |(% style="width:171px" %)Power switch error|(% style="width:324px" %)Short circuit in contactor coil control circuit or power switch overheating|(% style="width:61px" %)Yes|(% style="width:92px" %) |(% style="width:66px" %) |(% style="width:56px" %)Yes|(% style="width:126px" %)PSW error|(% style="width:54px" %)PSE|(% style="width:265px" %) |(% style="width:306px" %)0x200E-0x200F, bit 15. Off = 0, On = 1.
120 -|(% style="width:171px" %)Precharge error|(% style="width:324px" %)Capacitive load pre-charge process did not end during the estimated time|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Precharge error|(% style="width:54px" %)PE|(% style="width:265px" %) |(% style="width:306px" %)
120 +|(% style="width:171px" %)Precharge error|(% style="width:324px" %)Capacitive load pre-charge process did not end during the estimated time|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Precharge error|(% style="width:54px" %)PE|(% style="width:265px" %) |(% style="width:306px" %)0x200E-0x200F, bit 17. Off = 0, On = 1.
121 121  |(% style="width:171px" %)Settings error|(% style="width:324px" %)Wrong checksum of the device settings|(% style="width:61px" %) |(% style="width:92px" %) |(% style="width:66px" %)Yes|(% style="width:56px" %) |(% style="width:126px" %)Settings err.|(% style="width:54px" %)SET|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 25. Off = 0, On = 1.
122 122  |(% style="width:171px" %)Short circuit|(% style="width:324px" %)Flowing high battery currents during a long time|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Short circuit|(% style="width:54px" %)SHC|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 16. Off = 0, On = 1.
123 123  |(% style="width:171px" %)Shunt error|(% style="width:324px" %)Internal error of the shunt current sensor|(% style="width:61px" %)Yes|(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Shunt error|(% style="width:54px" %)SHE|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 24. Off = 0, On = 1.