... ... @@ -105,7 +105,7 @@
105 105  |(% style="width:171px" %)Insulation fault|(% style="width:324px" %)Insulation resistance is too low|(% style="width:61px" %)Yes|(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Insulation fault|(% style="width:54px" %)INF|(% style="width:265px" %) |(% style="width:306px" %)
106 106  |(% style="width:171px" %)Logic count error|(% style="width:324px" %)The number of BMS Logic devices differs from the required value|(% style="width:61px" %) |(% style="width:92px" %) |(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Logic count|(% style="width:54px" %)LOG|(% style="width:265px" %) |(% style="width:306px" %)
107 107  |(% style="width:171px" %)Logic offline (Cell monitor offline)|(% style="width:324px" %)BMS Main devices: at least one of the Logic devices is offline.
108 -BMS Mini devices: connection with cell monitor is lost.|(% style="width:61px" %)Yes|(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Logic offline|(% style="width:54px" %)LOF|(% style="width:265px" %) |(% style="width:306px" %)
108 +BMS Mini devices: connection with cell monitor is lost.|(% style="width:61px" %)Yes|(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Logic offline|(% style="width:54px" %)LOF|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 5. Off = 0, On = 1.
109 109  |(% style="width:171px" %)Low temperature (CH)|(% style="width:324px" %)Temperature is too low for charging;|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Low temp. CH|(% style="width:54px" %)LTC|(% style="width:265px" %) |(% style="width:306px" %)
110 110  |(% style="width:171px" %)Low temperature (DCH)|(% style="width:324px" %)Temperature is too low for discharging;|(% style="width:61px" %) |(% style="width:92px" %)Yes|(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Low temp. DCH|(% style="width:54px" %)LTD|(% style="width:265px" %) |(% style="width:306px" %)0x2007-0x2008, bit 3. Off = 0, On = 1.
111 111  |(% style="width:171px" %)Main contactor feedback error|(% style="width:324px" %)The control signal for the main contactor and the contactor feedback differ|(% style="width:61px" %)Yes|(% style="width:92px" %) |(% style="width:66px" %)Yes|(% style="width:56px" %)Yes|(% style="width:126px" %)Main cont. feed.|(% style="width:54px" %)MCF|(% style="width:265px" %) |(% style="width:306px" %)