Last modified by Admin on 2025/03/03 15:20

From version 10.3
edited by Admin
on 2025/01/30 16:16
Change comment: There is no comment for this version
To version 11.2
edited by Admin
on 2025/01/30 16:53
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -11,28 +11,28 @@
11 11  (% style="width:1278px" %)
12 12  |=(% colspan="1" rowspan="2" style="width: 198px;" %)**Name**|=(% rowspan="2" style="width: 60px;" %)**Abbr.**|=(% colspan="1" rowspan="2" style="width: 500px;" %)**Description**|=(% colspan="3" rowspan="1" style="width: 243px;" %)**Compability**|=(% colspan="1" rowspan="2" style="width: 137px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 137px;" %)**Modbus**
13 13  |=(% style="width: 92px;" %)**Mini S / Mini**|=(% style="width: 73px;" %)**Main 2.1**|=(% style="width: 78px;" %)**Main 3**
14 -|Balancing request |BR|(% style="width:500px" %)a request to balance the cells;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
15 -|Battery cover |CVR|(% style="width:500px" %)a signal from the battery cover;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
16 -|CH contactor feedback |CCF|(% style="width:500px" %)a signal from charging contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
17 -|CH/DCH contactor feedback |CDF|(% style="width:500px" %)a signal from charging/discharging contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
18 -|Charge request |CRE|(% style="width:500px" %)a request to close the charging contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
19 -|Charger connected |CON|(% style="width:500px" %)a signal indicating that charger is connected;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
20 -|Circuit breaker status |CBS|(% style="width:500px" %)status of protection disconnector;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
21 -|Close External 1 |CE1|(% style="width:500px" %)a request to close the External 1 discrete output (if assigned).|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
22 -|Close Main contactor |CMC|(% style="width:500px" %)a request to close the main contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
23 -|DCH contactor feedback |DCF|(% style="width:500px" %)a signal from discharging contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
24 -|Discharge request |DRE|(% style="width:500px" %)a request to close the discharging contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
14 +|Balancing request|BR|(% style="width:500px" %)a request to balance the cells;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
15 +|Battery cover|CVR|(% style="width:500px" %)a signal from the battery cover;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
16 +|CH contactor feedback|CCF|(% style="width:500px" %)a signal from charging contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
17 +|CH/DCH contactor feedback|CDF|(% style="width:500px" %)a signal from charging/discharging contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
18 +|Charge request|CRE|(% style="width:500px" %)a request to close the charging contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
19 +|Charger connected|CON|(% style="width:500px" %)a signal indicating that charger is connected;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
20 +|Circuit breaker status|CBS|(% style="width:500px" %)status of protection disconnector;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
21 +|Close External 1|CE1|(% style="width:500px" %)a request to close the External 1 discrete output (if assigned).|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
22 +|Close Main contactor|CMC|(% style="width:500px" %)a request to close the main contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
23 +|DCH contactor feedback|DCF|(% style="width:500px" %)a signal from discharging contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
24 +|Discharge request|DRE|(% style="width:500px" %)a request to close the discharging contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
25 25  |Fuse 1|F1|(% style="width:500px" %)signal from fuse 1;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
26 26  |Fuse 2|F2|(% style="width:500px" %)signal from fuse 2;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
27 -|Fuse 3 |F3|(% style="width:500px" %)signal from fuse 3;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
28 -|Inhibit charging |ICH|(% style="width:500px" %)a command to open the charging contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
29 -|Inhibit discharging |IDC|(% style="width:500px" %)a command to open the discharging contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
30 -|Insulation status |INS|(% style="width:500px" %)a signal from an insulation monitoring device;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
31 -|Interlock | |(% style="width:500px" %)a signal from interlock loop;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
32 -|Main contactor feedback |MCF|(% style="width:500px" %)a signal from main contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
33 -|PCH contactor feedback |PCF|(% style="width:500px" %)a signal from precharging contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
34 -|Power up/down request |PDN|(% style="width:500px" %)a request to power down the device;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
35 -|Precharge request|PRE|(% style="width:500px" %)a request to close the precharging contactor|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %) |(% style="width:137px" %) |(% style="width:137px" %)
27 +|Fuse 3|F3|(% style="width:500px" %)signal from fuse 3;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
28 +|Inhibit charging|ICH|(% style="width:500px" %)a command to open the charging contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
29 +|Inhibit discharging|IDC|(% style="width:500px" %)a command to open the discharging contactor;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
30 +|Insulation status|INS|(% style="width:500px" %)a signal from an insulation monitoring device;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
31 +|Interlock| |(% style="width:500px" %)a signal from interlock loop;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
32 +|Main contactor feedback|MCF|(% style="width:500px" %)a signal from main contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
33 +|PCH contactor feedback|PCF|(% style="width:500px" %)a signal from precharging contactor feedback loop;|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
34 +|Power up/down request|PDN|(% style="width:500px" %)a request to power down the device;|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
35 +|Precharge request|PRE|(% style="width:500px" %)a request to close the precharging contactor|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |(% style="width:137px" %)
36 36  
37 37  (% class="wikigeneratedid" %)
38 38  ~* Contactor feedback signals in BMS Mini / BMS Mini S are connected to [[X1 header>>doc:Battery management systems.BMS Mini S.2\. Installation and connection.WebHome||anchor="HHeaders"]] and configured in "Signals → MOSFETs → Contactors feedback" section.
... ... @@ -44,30 +44,30 @@
44 44  (% style="width:1277px" %)
45 45  |=(% colspan="1" rowspan="2" style="width: 201px;" %)**Name**|=(% rowspan="2" style="width: 55px;" %)**Abbr.**|=(% colspan="1" rowspan="2" style="width: 531px;" %)**Description**|=(% colspan="3" rowspan="1" style="width: 255px;" %)**Compability**|=(% colspan="1" rowspan="2" style="width: 140px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 142px;" %)**Modbus**
46 46  |=(% style="width: 94px;" %)**Mini S / Mini**|=(% style="width: 75px;" %)**Main 2.1**|=(% style="width: 84px;" %)**Main 3**
47 -|Allow charging |ACH|a signal for a charger to start charging;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
48 -|Balancing 1 |BA1|balancing the first series of cells;| |Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
49 -|Balancing 2 |BA2|balancing the second series of cells;| |Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
47 +|Allow charging|ACH|a signal for a charger to start charging;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
48 +|Balancing 1|BA1|balancing the first series of cells;| |Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
49 +|Balancing 2|BA2|balancing the second series of cells;| |Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
50 50  |Cell analysis|CEA| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
51 -|Charging current present |CCP|the presence of the charging current;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
52 -|Charging |CH|state of the charging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
51 +|Charging current present|CCP|the presence of the charging current;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
52 +|Charging|CH|state of the charging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
53 53  |Charging/discharging|C/D|state of the charging/discharging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
54 -|Cooler |COO|a command to turn on a cooler;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
54 +|Cooler|COO|a command to turn on a cooler;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
55 55  |Crown EWS|EWS| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
56 -|Discharging (AUX) |AUX|state of the auxiliary discharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
57 -|Discharging current present |DCP|the presence of the discharging current;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
58 -|Discharging |DCH|state of the discharging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
59 -|External 1 |EX1|a signal that activates by the remote request.|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
56 +|Discharging (AUX)|AUX|state of the auxiliary discharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
57 +|Discharging current present|DCP|the presence of the discharging current;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
58 +|Discharging|DCH|state of the discharging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
59 +|External 1|EX1|a signal that activates by the remote request.|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
60 60  |Heater (AUX)|HA| | |Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
61 -|Heater |HEA|a command to turn on a heater;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
62 -|High charging current |HCC|charging current is high;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
61 +|Heater|HEA|a command to turn on a heater;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
62 +|High charging current|HCC|charging current is high;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
63 63  |Init|INI| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
64 -|Low SOC |LOS|a signal corresponding the low SOC of the battery;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
65 -|Main contactor |MCO|state of the main contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
66 -|Power down ACK |PDA|an acknowledgement of BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on power down request;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
67 -|Power up |PUP|an indication of BMS power status;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
68 -|Precharging |PRE|state of the precharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
69 -|Ready to charge |RTC|the battery is ready to be charged;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
70 -|Ready to discharge |RTD|the battery is ready to be discharged;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
64 +|Low SOC|LOS|a signal corresponding the low SOC of the battery;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
65 +|Main contactor|MCO|state of the main contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
66 +|Power down ACK|PDA|an acknowledgement of BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on power down request;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
67 +|Power up|PUP|an indication of BMS power status;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
68 +|Precharging|PRE|state of the precharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
69 +|Ready to charge|RTC|the battery is ready to be charged;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
70 +|Ready to discharge|RTD|the battery is ready to be discharged;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
71 71  |Service reset|SR| |Yes~*~**| |Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
72 72  |Shutdown request (Combilift)|CSH| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
73 73  |Shutdown request (HYG/Spirit)|HSH| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
... ... @@ -87,55 +87,55 @@
87 87  (% style="width:1279px" %)
88 88  |(% colspan="1" rowspan="2" style="width:196px" %)**Name **|(% colspan="1" rowspan="2" style="width:58px" %)**Abbr.**|(% colspan="1" rowspan="2" style="width:443px" %)**Description**|(% colspan="1" rowspan="2" style="width:67px" %)**Is a Critical error?**|(% colspan="3" rowspan="1" style="width:248px" %)**Compability**|(% colspan="1" rowspan="2" style="width:142px" %)**CANopen SDO**|(% colspan="1" rowspan="2" style="width:134px" %)**Modbus**
89 89  |=(% style="width: 93px;" %)**Mini S / Mini**|=(% style="width: 76px;" %)**Main 2.1**|=(% style="width: 80px;" %)**Main 3**
90 -|ADC error |ADC|current cannot be measured;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
91 -|Battery cover error |BC|battery cover is open;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
92 -|Cell count error |CEL|number of cells does not match the specified value;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
93 -|CH contactor cycles error |CCC|switching frequency of the charging contactor is too high;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
94 -|CH contactor feedback error |CCF|the control signals for the charging contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
95 -|CH/DCH contactor feedback error |CDF|the control signals for the charging/discharging contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
96 -|Combilift offline |COM|connection with a Combilift forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
90 +|ADC error|ADC|current cannot be measured;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
91 +|Battery cover error|BC|battery cover is open;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
92 +|Cell count error|CEL|number of cells does not match the specified value;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
93 +|CH contactor cycles error|CCC|switching frequency of the charging contactor is too high;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
94 +|CH contactor feedback error|CCF|the control signals for the charging contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
95 +|CH/DCH contactor feedback error|CDF|the control signals for the charging/discharging contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
96 +|Combilift offline|COM|connection with a Combilift forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
97 97  |Contactor feedback error|CFE|Failure of one of the contactors feedback signal. Which contactor is failed can be | |Yes| |Yes|(% style="width:142px" %) |(% style="width:134px" %)
98 98  |Critical error|CER| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
99 -|Crown error |CRO|connection with a Crown forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
100 -|Current limit error |CLE|charging or discharging current is more than limit calculated by Charge map or Discharge map.| |Yes| |Yes|(% style="width:142px" %) |(% style="width:134px" %)
101 -|Current sensor error |CSE|error in the current sensor circuit;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
102 -|DCH contactor cycles error |DCC|switching frequency of the discharging contactor is too high;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
103 -|DCH contactor feedback error |DCF|the control signals for the discharging contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
99 +|Crown error|CRO|connection with a Crown forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
100 +|Current limit error|CLE|charging or discharging current is more than limit calculated by Charge map or Discharge map.| |Yes| |Yes|(% style="width:142px" %) |(% style="width:134px" %)
101 +|Current sensor error|CSE|error in the current sensor circuit;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
102 +|DCH contactor cycles error|DCC|switching frequency of the discharging contactor is too high;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
103 +|DCH contactor feedback error|DCF|the control signals for the discharging contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
104 104  |FS error|FSE| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
105 105  |General error|GE| | |Yes*|Yes*|Yes|(% style="width:142px" %) |(% style="width:134px" %)
106 106  |High contactor temperature|CHT| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
107 -|High humidity |HH|humidity of the battery is increased;| | |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
108 -|High Logic temperature |LHT|at least one of the Logic devices is overheated;| | |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
109 -|High temperature (CH) |HCT|temperature is too high for charging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
110 -|High temperature (DCH) |HDT|temperature is too high for discharging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
111 -|High voltage fault |HVF|failure of high voltage measuring circuits;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
112 -|HVIL error |HE|breakage of high-voltage interlock current loop;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
113 -|HYG offline |HYG|connection with a HYG forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
107 +|High humidity|HH|humidity of the battery is increased;| | |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
108 +|High Logic temperature|LHT|at least one of the Logic devices is overheated;| | |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
109 +|High temperature (CH)|HCT|temperature is too high for charging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
110 +|High temperature (DCH)|HDT|temperature is too high for discharging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
111 +|High voltage fault|HVF|failure of high voltage measuring circuits;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
112 +|HVIL error|HE|breakage of high-voltage interlock current loop;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
113 +|HYG offline|HYG|connection with a HYG forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
114 114  |Insulation fault|INF| |•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
115 -|Logic count error|LOG| | | | | |(% style="width:142px" %) |(% style="width:134px" %)
116 -|Logic offline |LOF|at least one of the Logic devices is offline;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
117 -|Low temperature (CH) |LCT|temperature is too low for charging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
118 -|Low temperature (DCH) |LDT|temperature is too low for discharging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
119 -|Main contactor feedback error |MCF|the control signals for the main contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
115 +|Logic count error|LOG| | | |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
116 +|Logic offline|LOF|at least one of the Logic devices is offline;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
117 +|Low temperature (CH)|LCT|temperature is too low for charging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
118 +|Low temperature (DCH)|LDT|temperature is too low for discharging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
119 +|Main contactor feedback error|MCF|the control signals for the main contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
120 120  |Mount error|MNT| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
121 -|Need acknowledge |ACK|there is an unacknowledged error in Error journal;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
122 -|No temperature sensors |NTS|the device has no temperature sensors connected;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
121 +|Need acknowledge|ACK|there is an unacknowledged error in Error journal;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
122 +|No temperature sensors|NTS|the device has no temperature sensors connected;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
123 123  |Overcurrent|OC| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
124 124  |Overvoltage|OV| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
125 -|PCH contactor feedback error |PCF|the control signals for the precharging contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
126 -|Power fault |PF|external devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
127 -|Power switch error |PSE|short circuit in contactor coil control circuit or power switch overheating;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
128 -|Precharge error |PE|capacitive load pre-charge process did not end during the estimated time;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
125 +|PCH contactor feedback error|PCF|the control signals for the precharging contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
126 +|Power fault|PF|external devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
127 +|Power switch error|PSE|short circuit in contactor coil control circuit or power switch overheating;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
128 +|Precharge error|PE|capacitive load pre-charge process did not end during the estimated time;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
129 129  |Settings error|SET| | | | | |(% style="width:142px" %) |(% style="width:134px" %)
130 130  |Short circuit|SHC| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
131 -|Shunt error |SHE|internal error of the shunt current sensor;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
132 -|Shunt offline |SHO|connection with the shunt current sensor is lost;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
133 -|Spirit offline |SPI|connection with a Spirit forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
131 +|Shunt error|SHE|internal error of the shunt current sensor;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
132 +|Shunt offline|SHO|connection with the shunt current sensor is lost;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
133 +|Spirit offline|SPI|connection with a Spirit forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
134 134  |Stuck contactor|STC| |•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
135 -|Temperature sensor is shorted |TSS|some temperature sensors are shorted;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
136 -|Unallowable charging |UCH|charging the battery through the discharging contactor;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
135 +|Temperature sensor is shorted|TSS|some temperature sensors are shorted;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
136 +|Unallowable charging|UCH|charging the battery through the discharging contactor;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
137 137  |Undervoltage|UV| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
138 -|Water |WA|there is water in the battery enclosure;|•| |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
139 -|WDT reset |WDT|watchdog timer reset the device;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
138 +|Water|WA|there is water in the battery enclosure;|•| |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
139 +|WDT reset|WDT|watchdog timer reset the device;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
140 140  
141 141  ~* signal can be assigned to a discrete output and relay.