| 1 | = v1.19.6 = | ||
| 2 | |||
| 3 | [[ElectricDeviceMonitorSETUP_v1.19.6.exe>>FileManager.ElectricDeviceMonitorSETUP_v1\.19\.6\.exe]] | ||
| 4 | |||
| 5 | == BMS Main 2.1 monitor (firmware 1.70.10) == | ||
| 6 | |||
| 7 | * new flag in the "External Equipment - J1939 Charger" section, which enables a compatibility mode for EFFIC chargers | ||
| 8 | |||
| 9 | = v1.19.5 = | ||
| 10 | |||
| 11 | [[ElectricDeviceMonitor_v1.19.5.exe>>https://docs.movicomelectric.com/bin/view/FileManager/ElectricDeviceMonitor_v1.19.5.exe]] | ||
| 12 | |||
| 13 | == BMS Main 2.1 monitor (firmware 1.70.8) == | ||
| 14 | |||
| 15 | * new flag in the "External equipment - Battery cycling" section that forces the discharging contactor to be closed if the battery cycling is started | ||
| 16 | |||
| 17 | = v1.19.4 = | ||
| 18 | |||
| 19 | == Unified monitor == | ||
| 20 | |||
| 21 | * resolving the problem of parameter import stopping if the file contains invalid lines | ||
| 22 | |||
| 23 | = v1.19.3 = | ||
| 24 | |||
| 25 | == Unified monitor == | ||
| 26 | |||
| 27 | * support for decompression of responses from devices capable of compressing data to speed up transmission | ||
| 28 | |||
| 29 | = v1.19.2 = | ||
| 30 | |||
| 31 | == Unified monitor == | ||
| 32 | |||
| 33 | * disable importing parameter values from files exported from devices of a different type | ||
| 34 | * disconnecting from the device after it has entered bootloader mode | ||
| 35 | * hotkeys for basic operations | ||
| 36 | |||
| 37 | == Other monitors == | ||
| 38 | |||
| 39 | * disconnecting from the device after it has entered bootloader mode | ||
| 40 | * hotkeys for basic operations | ||
| 41 | |||
| 42 | = v1.19.1 = | ||
| 43 | |||
| 44 | == Unified monitor == | ||
| 45 | |||
| 46 | * resolving the problem of importing parameter values containing the # symbol in text fields | ||
| 47 | |||
| 48 | = v1.19.0 = | ||
| 49 | |||
| 50 | == Unified monitor == | ||
| 51 | |||
| 52 | * new offline mode where the user can view and change previously saved parameter values | ||
| 53 | * instead of exporting parameters that can be reset to default values, the software exports parameters which are stored and have read/write access | ||
| 54 | |||
| 55 | = v1.18.19 = | ||
| 56 | |||
| 57 | == BMS Logic 12/18/RET monitors == | ||
| 58 | |||
| 59 | * another approach to check that the device has a 32-bit serial number | ||
| 60 | |||
| 61 | = v1.18.18 = | ||
| 62 | |||
| 63 | == BMS Main 2.1 monitor (firmware 1.70.6) == | ||
| 64 | |||
| 65 | * ability to read 32-bit BMS Logic serial numbers | ||
| 66 | |||
| 67 | == BMS Logic 12/18/RET monitors == | ||
| 68 | |||
| 69 | * ability to read and configure 32-bit serial numbers | ||
| 70 | |||
| 71 | = v1.18.17 = | ||
| 72 | |||
| 73 | == Unified monitor == | ||
| 74 | |||
| 75 | * ability to automatically reconnect to the device in the background when the connection is lost | ||
| 76 | |||
| 77 | = v1.18.16 = | ||
| 78 | |||
| 79 | == Unified monitor == | ||
| 80 | |||
| 81 | * ability to edit integer parameters whose maximum allowable values exceed 2^32 | ||
| 82 | * changed the format for displaying time parameters (they have the dimensions "Minute", "Second", "Millisecond", "Microsecond") in the middle block | ||
| 83 | |||
| 84 | = v1.18.15 = | ||
| 85 | |||
| 86 | == BMS Main 2.1 monitor == | ||
| 87 | |||
| 88 | * displaying temperature of all battery cells in the "Cell summary" section | ||
| 89 | |||
| 90 | == Unified monitor == | ||
| 91 | |||
| 92 | * resolving the problem of importing HEX parameter values from files | ||
| 93 | |||
| 94 | = v1.18.14 = | ||
| 95 | |||
| 96 | == BMS Main 2.1 monitor (firmware 1.70.4) == | ||
| 97 | |||
| 98 | * new flags that control the generation of "Ready to charge" and "Ready to discharge" signals using the actual cell voltage instead of the calculated open circuit voltage | ||
| 99 | |||
| 100 | == Unified monitor == | ||
| 101 | |||
| 102 | * displaying connection information in the window title | ||
| 103 | |||
| 104 | = v1.18.13 = | ||
| 105 | |||
| 106 | == BMS Main 2.1 monitor (firmware 1.70.3) == | ||
| 107 | |||
| 108 | * new flags that force the precharge process to finish if the battery current is negative (in case the battery will be charging) or positive (in case the battery will be discharging); see the "Cells - Charging control" and "Cells - Discharging control" sections | ||
| 109 | * new flag to prevent the "HYG offline" error from occurring if the "Charger connected" signal is set (see the "External equipment - HYG Class I-III" section) | ||
| 110 | * new flag that controls whether to wait for confirmation from the HYG truck or not, to allow the battery to be charged (see the "External equipment - HYG Class I-III" section) | ||
| 111 | |||
| 112 | = v1.18.12 = | ||
| 113 | |||
| 114 | == BMS Main 2.1 monitor (firmware 1.70.2) == | ||
| 115 | |||
| 116 | * new parameter setting a delay before measuring battery current during precharge (see the "Cells - Discharging control" section) | ||
| 117 | * new counter of retry attempts showing the communication problems with BMS Logic devices (see the "Logic/Cell" section) | ||
| 118 | * new flag to keep the precharging contactor closed until the precharging process is finished (see the "Cells - Discharging control" section) | ||
| 119 | * new flags that force only positive and negative currents to be used to determine open circuit voltages to control the "Ready to charge" and "Ready to discharge" signals respectively (see the "Cells - Charging control" and "Cells - Discharging control" sections) | ||
| 120 | |||
| 121 | = v1.18.11 = | ||
| 122 | |||
| 123 | == BMS Main 2.1 monitor (firmware 1.70.1) == | ||
| 124 | |||
| 125 | * new assignments "Low SOC" and "High charging current" for relays (see the "Signals - Relay" section) | ||
| 126 | |||
| 127 | = v1.18.10 = | ||
| 128 | |||
| 129 | == Fixes == | ||
| 130 | |||
| 131 | * small fixes to prevent software crashes | ||
| 132 | |||
| 133 | = v1.18.9 = | ||
| 134 | |||
| 135 | == BMS Main 2.1 monitor (firmware 1.70.0) == | ||
| 136 | |||
| 137 | * new parameters setting the different delays to detect the "Overcurrent" error when the battery is discharging (see the "Protections - Overcurrent protection" section) | ||
| 138 | * new flag setting whether the BMS should wait for confirmation messages from the Combilift truck to start charging or not (see the "External equipment - Combilift truck" section) | ||
| 139 | |||
| 140 | = v1.18.8 = | ||
| 141 | |||
| 142 | == Unified bootloader == | ||
| 143 | |||
| 144 | * support for firmware updates via CAN interfaces from PEAK, Systec, Marathon, Movicom Electric | ||
| 145 | |||
| 146 | == Fixes == | ||
| 147 | |||
| 148 | * preventing CAN bus adapters from locking up until software is restarted | ||
| 149 | |||
| 150 | = v1.18.7 = | ||
| 151 | |||
| 152 | == BMS Logic 2.0, BMS Logic 12/18/RET monitors == | ||
| 153 | |||
| 154 | * marking of maximum and minimum voltage and temperature of cells | ||
| 155 | * calculation of the difference in voltage and temperature of cells | ||
| 156 | |||
| 157 | = v1.18.6 = | ||
| 158 | |||
| 159 | == BMS Display 1.x monitor (firmware 1.5.0) == | ||
| 160 | |||
| 161 | * new parameter that sets the second register of displayed errors for BMS Main X | ||
| 162 | * expanding the list of errors that can be displayed | ||
| 163 | |||
| 164 | = v1.18.5 = | ||
| 165 | |||
| 166 | == BMS Main 2.1 monitor (firmware 1.69.0) == | ||
| 167 | |||
| 168 | * new assignments for input signals "Balancing request", "Close Main contactor", "Close External 1" | ||
| 169 | * new internal signal "External 1" and corresponding assignments for discrete outputs and relays | ||
| 170 | * new error "Precharge error" | ||
| 171 | * new flags to use the OCV voltage instead of actual voltage for detecting errors "Overvoltage" and "Undervoltage" | ||
| 172 | * new flag to check the "Ready to charge" signal for allowing charging in the "Cells - Charging control" section | ||
| 173 | * new flag to check the "Ready to discharge" signals for allowing discharging in the "Cells - Discharging control" section | ||
| 174 | * new parameters related to "Precharge error" detection in the "Cells - Discharging control" section | ||
| 175 | * new parameter setting the control algorithm for the main contactor in the "Cells - Main contactor" section | ||
| 176 | * new parameters related to cell balancing in the "Cells - Cell balancing" section | ||
| 177 | * new flags that explicitly enable the use of the "Charging current limit" value in the "External equipment - CCS Fast charge controller" section | ||
| 178 | |||
| 179 | == Unified monitor == | ||
| 180 | |||
| 181 | * allowing the use of underscores and dashes to set a user password | ||
| 182 | |||
| 183 | = v1.18.4 = | ||
| 184 | |||
| 185 | == BMS Main 2.1 monitor (firmware 1.68.0) == | ||
| 186 | |||
| 187 | * new section "External equipment - XD Discharger (cycling)" | ||
| 188 | |||
| 189 | = v1.18.3 = | ||
| 190 | |||
| 191 | == BMS Main 2.1 monitor (firmware 1.67.0) == | ||
| 192 | |||
| 193 | * new section "Protections - Heater (AUX) control" | ||
| 194 | * new internal signal "Heater (AUX)" in the "Signals - Internal state" section | ||
| 195 | * new assignment "Heater (AUX)" for discrete outputs and relays | ||
| 196 | * new parameters "Deviation to stop balancing" and "Maximum allowable temperature of BMS Logic devices" in the "Cells - Cell balancing" section | ||
| 197 | |||
| 198 | = v1.18.2 = | ||
| 199 | |||
| 200 | == BMS Main 2.1 monitor (firmware 1.66.0) == | ||
| 201 | |||
| 202 | * new section "External equipment - BMS IMD device" | ||
| 203 | * new parameters to open the discharging (AUX) relay when the cell voltage is too low (see the "Cells - Discharging (AUX) control" section) | ||
| 204 | |||
| 205 | = v1.18.1 = | ||
| 206 | |||
| 207 | == BMS Main 2.1 monitor (firmware 1.65.2) == | ||
| 208 | |||
| 209 | * new parameter "Maximum SOH" in the "Cells - Cell defaults" section | ||
| 210 | * new parameter "Mask" in the "Signals - Temperature sensor" section, each bit of which hides the corresponding temperature sensor connected to the BMS Logic device | ||
| 211 | |||
| 212 | == Unified monitor == | ||
| 213 | |||
| 214 | * improvements and fixes for the BMS Main 3 device | ||
| 215 | |||
| 216 | = v1.18.0 = | ||
| 217 | |||
| 218 | * new "Unified bootloader" that is used to update the firmware of new devices (BMS Main 3 and BMS Main 3X) | ||
| 219 | |||
| 220 | == Unified monitor == | ||