... ... @@ -3,6 +3,32 @@
3 3  BMS Mini S / BMS Mini firmware update procedure is described [[here>>doc:Battery management systems.BMS Mini S.5\. Firmware update.WebHome]].
4 4  )))
5 5  
6 += v1.8.0 =
7 +
8 +[[BMS_Mini_v1.8.0.srec>>FileManager.BMS_Mini_v1\.8\.0\.srec]]
9 +
10 +== Features ==
11 +
12 +* new protection for detecting battery cell imbalance (see the "Protections - Cell imbalance" section)
13 +* new protection checking that the number of cell temperature sensors is equal to the specified value. If this is not the case, the "T-sensor count error" is generated (see the "Protections - Temperature sensor count" section)
14 +* new internal protection that checks for overheating of MOSFETs and generates the "MOSFET error" (see the "Protections - MOSFET" section)
15 +* new internal protection that checks for power failures in the device and generates the "Power fault" error
16 +* new error "Main X offline" which is generated when the connection with BMS Main X is lost
17 +* detection of loss of wire connection to battery cells
18 +
19 +== Improvements ==
20 +
21 +* new parameters that control setting/clearing the "Ready to charge" and "Ready to discharge" signals based on the charge and/or discharge current limits (see the "Control - Charging status" and "Control - Discharging status" sections)
22 +* new parameters to ignore the specified errors when setting the critical error (see the "Protections - Critical error" section)
23 +* expansion of the list of parameters that are reset to default values when the device is powered on while holding the button on the board. The following parameters are affected: all CAN settings; all RS-485 (Modbus) settings; LAN settings: IP mode, IP address, Netmask, Gateway address
24 +* improved stability of the BMS Wi-Fi V2 driver
25 +* improved stability of the BMS GSM driver
26 +
27 +== Fixes ==
28 +
29 +* synchronization of the precharge procedure with the charge/discharge algorithms, so that precharge is stopped if charging and discharging are prohibited
30 +* resolving the problem of communication with the DC EV supply equipment
31 +