Changes for page BMS Main X

Last modified by Admin on 2025/07/22 11:39

From version 1.2
edited by Admin
on 2024/11/22 09:00
Change comment: There is no comment for this version
To version 8.1
edited by Admin
on 2025/07/22 11:39
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,3 +1,102 @@
1 +(% class="box infomessage" %)
2 +(((
3 +BMS Main X firmware update procedure is described [[here>>doc:Battery management systems.BMS Main X.5\. Firmware update.WebHome]].
4 +)))
5 +
6 += v2.8.1 =
7 +
8 +[[BMS_Main_X2_v2.8.1.srec>>FileManager.BMS_Main_X2_v2\.8\.1\.srec]]
9 +
10 +== Improvements ==
11 +
12 +* new CLI command "find-log" which finds a log file containing a specified timestamp
13 +* ability to acknowledge battery module errors via CLI (see the "Service - Errors journal" section) and Modbus protocol
14 +
15 +== Fixes ==
16 +
17 +* resolving the issue of rebooting the device if formatting the SD card is activated
18 +
19 += v2.8.0 =
20 +
21 +[[BMS_Main_X2_v2.8.0.srec>>FileManager.BMS_Main_X2_v2\.8\.0\.srec]]
22 +
23 +== Features ==
24 +
25 +* new flags that allow to interrupt (shorten) the module balancing stage if all battery modules are already joined (see the "Control - Charge", "Control - Discharge", "Control - Charge/Discharge" sections)
26 +* forwarding CLI and bootloader CAN messages from CAN EXT interface to CAN INT interface and back
27 +* new parameter for setting the type of network to which the BMS GSM communication module connects (see the "Connectivity - Cellular" section)
28 +* new flag that controls whether to use open circuit voltage or actual voltage when determining the voltage unbalance error (see the "Protections - Voltage unbalance (in any state)" section)
29 +* new regulator that maintains battery current limiting to ensure that actual module currents do not exceed their current limits (see the "Control - Charge", "Control - Discharge", "Control - Charge/Discharge" sections)
30 +* ability to select the battery module errors that cause the battery critical error (see the "Protections - Critical error" section)
31 +* ability to update the device serial number from the service account if the number is reset to the default value for some reason (see the "Service" section)
32 +
33 +== Improvements ==
34 +
35 +* dynamic calculation of data transfer schedule for optimal communication with a large number of battery modules
36 +* ability to complete device initialization after the set timeout has expired and the minimum number of modules has been detected (see the "Control - Initialization" section)
37 +* 30 second delay when remounting SD card after detecting mount error
38 +* saving the number of joined modules in log files
39 +
40 +== Fixes ==
41 +
42 +* resolving the issue of saving some battery module signals in log files
43 +
44 += v2.7.0 =
45 +
46 +[[BMS_Main_X2_v2.7.0.srec>>FileManager.BMS_Main_X2_v2\.7\.0\.srec]]
47 +
48 +== Features ==
49 +
50 +* new algorithm in the Charging/Discharging controller that allow to control the Charging/Discharging contactor independently from the Charging and Discharging signals (see the "Control - Charge/Discharge" section). The new "Independent" algorithm is preferred in the battery systems with one contactor
51 +* new "Need acknowledge" warning signal that is set when a new record is created in the errors journal. The signal can be cleared in the "Service - Errors journal" section
52 +* new Max-Min algorithm for calculating the final battery SOC in the "Control - Calculation" section
53 +* improved control of the precharging contactor, which can precharge capacitive load using multiple attempts and detect high power dissipated in the precharge resistor (see the "Control - Precharge" section)
54 +* ability to exclude errors from being saved in the error journal (see the "Service - Errors journal" section)
55 +* ability to restart the device according to a specified schedule at the moment when the battery system is preparing to charge
56 +* new error "High contactor temperature" that can be used to open the specified contactor to prevent it from overheating (see the "Protections - High contactor temperature" section)
57 +* new internal signal "Coolant pump" that can be assigned to a relay or discrete output (for signal settings, see the "Control - Coolant pump" section)
58 +* new flags indicating the readiness of battery modules to join for charging and discharging (see the "Modules" section)
59 +* new flag to set the "Voltage unbalance" errors for battery modules that are not ready to charge or discharge (see the "Protections - Voltage unbalance (in any state)" section)
60 +* initial support for Pylontech inverters
61 +* extension of the CANopen dictionary to provide additional information for the BMS Display (device serial number, battery serial number, battery address, Wi-Fi and LAN addresses, SOH, capacity, etc.)
62 +
63 +== Improvements ==
64 +
65 +* ability to finish device initialization even if the number of battery modules found is less than the number of modules enabled (see the "Control - Modules" section)
66 +* placing the device input signals to the "Battery" section and adding raw discrete inputs to the "Signals" section
67 +
68 +== Fixes ==
69 +
70 +* resolving the issue of ignoring the minimum number of battery modules allowed to join located in the "Control - Discharge" section
71 +* resolving the issue of joining battery modules the number of which must be greater than or equal to the minimum value specified in the settings
72 +* small internal fixes
73 +
74 += v2.6.3 =
75 +
76 +[[BMS_Main_X2_v2.6.3.srec>>FileManager.BMS_Main_X2_v2\.6\.3\.srec]]
77 +
78 +== Improvements ==
79 +
80 +* adaptation of the device to the production test bench
81 +
82 += v2.6.2 =
83 +
84 +[[BMS_Main_X2_v2.6.2.srec>>FileManager.BMS_Main_X2_v2\.6\.2\.srec]]
85 +
86 +== Fixes ==
87 +
88 +* resolving the problem of saving device parameters
89 +
90 += v2.6.1 =
91 +
92 +[[BMS_Main_X2_v2.6.1.srec>>FileManager.BMS_Main_X2_v2\.6\.1\.srec]]
93 +
94 +== Fixes ==
95 +
96 +* resolving the issue of preparing battery module states written to Modbus registers
97 +* resolving the problem of writing the device's working time to a non-volatile memory very often
98 +* resolving the problem of returning error states when saving device parameters (mainly via Wi-Fi)
99 +
1 1  = v2.6.0 =
2 2  
3 3  [[BMS_Main_X2_v2.6.0.srec>>FileManager.BMS_Main_X2_v2\.6\.0\.srec]]
... ... @@ -11,6 +11,10 @@
11 11  * new assignments "Charging", "Precharging", "Discharging", "Charging/Discharging", "Main contactor", "Critical error" and "General error (modules)" for the discrete outputs (see the "Signals - Output discrete signals - Assignments" section)
12 12  * new assignments "Critical error" and "General error (modules)" for the relays (see the "Signals - Relays - Assignments" section)
13 13  
14 -Improvements
113 +== Improvements ==
15 15  
16 -
115 +* rearrangements in the settings sections, which are made to simplify the setup process
116 +
117 +== Fixes ==
118 +