Changes for page BMS Main X

Last modified by Admin on 2025/05/28 10:39

From version 1.2
edited by Admin
on 2024/11/22 09:00
Change comment: There is no comment for this version
To version 7.1
edited by Admin
on 2025/05/28 10:39
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,3 +1,89 @@
1 +(% class="box infomessage" %)
2 +(((
3 +BMS Main X firmware update procedure is described [[here>>doc:Battery management systems.BMS Main X.5\. Firmware update.WebHome]].
4 +)))
5 +
6 += v2.8.0 =
7 +
8 +[[BMS_Main_X2_v2.8.0.srec>>FileManager.BMS_Main_X2_v2\.8\.0\.srec]]
9 +
10 +== Features ==
11 +
12 +* new flags that allow to interrupt (shorten) the module balancing stage if all battery modules are already joined (see the "Control - Charge", "Control - Discharge", "Control - Charge/Discharge" sections)
13 +* forwarding CLI and bootloader CAN messages from CAN EXT interface to CAN INT interface and back
14 +* new parameter for setting the type of network to which the BMS GSM communication module connects (see the "Connectivity - Cellular" section)
15 +* new flag that controls whether to use open circuit voltage or actual voltage when determining the voltage unbalance error (see the "Protections - Voltage unbalance (in any state)" section)
16 +* new regulator that maintains battery current limiting to ensure that actual module currents do not exceed their current limits (see the "Control - Charge", "Control - Discharge", "Control - Charge/Discharge" sections)
17 +* ability to select the battery module errors that cause the battery critical error (see the "Protections - Critical error" section)
18 +* ability to update the device serial number from the service account if the number is reset to the default value for some reason (see the "Service" section)
19 +
20 +== Improvements ==
21 +
22 +* dynamic calculation of data transfer schedule for optimal communication with a large number of battery modules
23 +* ability to complete device initialization after the set timeout has expired and the minimum number of modules has been detected (see the "Control - Initialization" section)
24 +* 30 second delay when remounting SD card after detecting mount error
25 +* saving the number of joined modules in log files
26 +
27 +== Fixes ==
28 +
29 +* resolving the issue of saving some battery module signals in log files
30 +
31 += v2.7.0 =
32 +
33 +[[BMS_Main_X2_v2.7.0.srec>>FileManager.BMS_Main_X2_v2\.7\.0\.srec]]
34 +
35 +== Features ==
36 +
37 +* new algorithm in the Charging/Discharging controller that allow to control the Charging/Discharging contactor independently from the Charging and Discharging signals (see the "Control - Charge/Discharge" section). The new "Independent" algorithm is preferred in the battery systems with one contactor
38 +* new "Need acknowledge" warning signal that is set when a new record is created in the errors journal. The signal can be cleared in the "Service - Errors journal" section
39 +* new Max-Min algorithm for calculating the final battery SOC in the "Control - Calculation" section
40 +* improved control of the precharging contactor, which can precharge capacitive load using multiple attempts and detect high power dissipated in the precharge resistor (see the "Control - Precharge" section)
41 +* ability to exclude errors from being saved in the error journal (see the "Service - Errors journal" section)
42 +* ability to restart the device according to a specified schedule at the moment when the battery system is preparing to charge
43 +* new error "High contactor temperature" that can be used to open the specified contactor to prevent it from overheating (see the "Protections - High contactor temperature" section)
44 +* new internal signal "Coolant pump" that can be assigned to a relay or discrete output (for signal settings, see the "Control - Coolant pump" section)
45 +* new flags indicating the readiness of battery modules to join for charging and discharging (see the "Modules" section)
46 +* new flag to set the "Voltage unbalance" errors for battery modules that are not ready to charge or discharge (see the "Protections - Voltage unbalance (in any state)" section)
47 +* initial support for Pylontech inverters
48 +* extension of the CANopen dictionary to provide additional information for the BMS Display (device serial number, battery serial number, battery address, Wi-Fi and LAN addresses, SOH, capacity, etc.)
49 +
50 +== Improvements ==
51 +
52 +* ability to finish device initialization even if the number of battery modules found is less than the number of modules enabled (see the "Control - Modules" section)
53 +* placing the device input signals to the "Battery" section and adding raw discrete inputs to the "Signals" section
54 +
55 +== Fixes ==
56 +
57 +* resolving the issue of ignoring the minimum number of battery modules allowed to join located in the "Control - Discharge" section
58 +* resolving the issue of joining battery modules the number of which must be greater than or equal to the minimum value specified in the settings
59 +* small internal fixes
60 +
61 += v2.6.3 =
62 +
63 +[[BMS_Main_X2_v2.6.3.srec>>FileManager.BMS_Main_X2_v2\.6\.3\.srec]]
64 +
65 +== Improvements ==
66 +
67 +* adaptation of the device to the production test bench
68 +
69 += v2.6.2 =
70 +
71 +[[BMS_Main_X2_v2.6.2.srec>>FileManager.BMS_Main_X2_v2\.6\.2\.srec]]
72 +
73 +== Fixes ==
74 +
75 +* resolving the problem of saving device parameters
76 +
77 += v2.6.1 =
78 +
79 +[[BMS_Main_X2_v2.6.1.srec>>FileManager.BMS_Main_X2_v2\.6\.1\.srec]]
80 +
81 +== Fixes ==
82 +
83 +* resolving the issue of preparing battery module states written to Modbus registers
84 +* resolving the problem of writing the device's working time to a non-volatile memory very often
85 +* resolving the problem of returning error states when saving device parameters (mainly via Wi-Fi)
86 +
1 1  = v2.6.0 =
2 2  
3 3  [[BMS_Main_X2_v2.6.0.srec>>FileManager.BMS_Main_X2_v2\.6\.0\.srec]]
... ... @@ -11,6 +11,10 @@
11 11  * new assignments "Charging", "Precharging", "Discharging", "Charging/Discharging", "Main contactor", "Critical error" and "General error (modules)" for the discrete outputs (see the "Signals - Output discrete signals - Assignments" section)
12 12  * new assignments "Critical error" and "General error (modules)" for the relays (see the "Signals - Relays - Assignments" section)
13 13  
14 -Improvements
100 +== Improvements ==
15 15  
16 -
102 +* rearrangements in the settings sections, which are made to simplify the setup process
103 +
104 +== Fixes ==
105 +
106 +* resolving the problem of device hanging due to high activity on the CAN bus during startup