BMS Main 3X

Version 8.1 by Admin on 2024/12/25 14:04

BMS Main 3X firmware update procedure is described here.

v3.2.0

BMS_Main_3X_v3.2.0.bin 

Features

  • new algorithm in the Charging/Discharging controller that allow to control the Charging/Discharging contactor independently from the Charging and Discharging signals (see the "Control - Charge/Discharge" section). The new "Independent" algorithm is preferred in the battery systems with one contactor
  • new "Need acknowledge" warning signal that is set when a new record is created in the errors journal. The signal can be cleared in the "Service - Errors journal" section
  • new Max-Min algorithm for calculating the final battery SOC in the "Control - Calculation" section
  • improved control of the precharging contactor, which can precharge capacitive load using multiple attempts and detect high power dissipated in the precharge resistor (see the "Control - Precharge" section)
  • ability to select errors that the device saves in the errors journal (see the "Service - Errors journal" section)

Improvements

  • ability to finish device initialization even if the number of battery modules found is less than the number of modules enabled
  • ability to configure and monitor the device via the CAN1 (ext) bus
  • placing the device input signals to the "Battery" section and adding raw discrete inputs to the "Signals" section
  • Unibat: support for functional description v3.5 (protocol v1.5)

v3.1.1

BMS_Main_3X_v3.1.1.bin 

Fixes

  • resolving the problem of incorrect range of temperature parameter values (in the "Control - Coolant pump" section)
  • resolving the possible problem of saving device parameters
  • resolving the problem of writing the device's working time to a non-volatile memory very often
  • resolving the issue of preparing battery module states written to Modbus registers

v3.1.0

BMS_Main_3X_v3.1.0.bin 

Features

  • new parameter to set the minimum number of battery modules allowed to join (see the "Control - Charge" and "Control - Discharge" sections)
  • ability to rejoin battery modules if their voltage is close to the battery voltage (see the "Control - Charge" and "Control - Discharge" sections)
  • selection of errors that cause reset of contactor control signals (see the "Control - Main contactor", "Control - Charge", "Control - Discharge", "Control - Heater", "Control - Cooler", "Control - Coolant pump" sections)
  • new internal signal "General error (modules)" which is the logical sum of the "General error" signals from the battery modules
  • new assignments "Critical error" and "General error (modules)" for the discrete outputs and power switches (see the "Signals - Output discrete signals - Assignments" and "Signals - Power switches - Assignments" sections)

Improvements

  • use the measured voltage before contactors as the battery voltage if the "Control - High voltage" function is enabled
  • Unibat: new flag to enable sending a control message to start/stop ventilation fans installed in the battery modules (see the "External equipment - Unibat vehicle" section)
  • rearrangements in the settings sections, which are made to simplify the setup process

Fixes

  • Unibat: minor changes in the communication protocol